Plan Review Notes
Plan Review Notes For Permit 04110992
Permit Number 04110992
Review Stop B
Sequence Number 2
Notes
Date Text
2005-01-13 00:00:00BUILDING REVIEW PROVISO:
 (PROVIDE INFORMATION PRIOR TO
 INSTALLATION OR CONSTRUCTION TO AVOID
 DELAYS OR CONFLICTS)
 1-PROPERTY IS LOCATED ON FLOOD ZONE "C",
 NOT "B". REVISE SURVEY AS REQUIRED.
  
 2-PROVIDE PRODUCT APPROVAL FOR ADHESIVE
 SET SYSTEM TO BE USED ON ROOF TILE.
  
 3-SIMPSON LUS CONNECTOR IS DESIGNED FOR
 WOOD TO WOOD INSTALLATION. NEED WOOD TO
 MASONRY CONNECTOR WHERE WOOD BEAMS ARE
 RESTING ON MASONRY WALLS. REVISE AS
 REQUIRED. PROVIDE COMPLETE ENGINEERING
 CALCULATIONS FOR CONNECTORS AND
 FASTENERS TO BE USED IF THEYDIFFER
 FROM THOSE ALREADY ENGINEERED AND
 PUBLISHED ON SIMPSON CATALOGUE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 4-REVISE FRAMING DETAIL FOR ARCHED
 OPENINGS. 1X4 BLOCKS ALONG ARCH DON'T
 WORK. NEED 2X BLOCKS TO INSTALL WINDOW
 FRAME. SEE PRODUCT APPROVAL. REVISE AS
 REQUIRED.
  
 5-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOOR SHOWING 2X BUCK AS REQUIRED
 BY DOOR PRODUCT APPROVAL.
  
 6-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (2 COPIES) FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS WITH
 COMPLETE DRAWINGS.
 B) GUARDRAILS WITH SPECS TO BE INSTALLED
 ON WOOD FRAMED FLOORS. NOT CONCRETE
 SLAB
  
 7-REVISE PLANS TO SHOW ENTRY DOOR WITH
 INSWING AS PER PRODUCT APPROVAL.
  
 8-REVISE/CLARIFY FOOTING F3 FOR WOOD
 COLUMNS.
 APPROVED PER JULIO'S PROVISOLM