| 2005-01-13 00:00:00 | BUILDING REVIEW PROVISO: |
| | (PROVIDE INFORMATION PRIOR TO |
| | INSTALLATION OR CONSTRUCTION TO AVOID |
| | DELAYS OR CONFLICTS) |
| | 1-PROPERTY IS LOCATED ON FLOOD ZONE "C", |
| | NOT "B". REVISE SURVEY AS REQUIRED. |
| | |
| | 2-PROVIDE PRODUCT APPROVAL FOR ADHESIVE |
| | SET SYSTEM TO BE USED ON ROOF TILE. |
| | |
| | 3-SIMPSON LUS CONNECTOR IS DESIGNED FOR |
| | WOOD TO WOOD INSTALLATION. NEED WOOD TO |
| | MASONRY CONNECTOR WHERE WOOD BEAMS ARE |
| | RESTING ON MASONRY WALLS. REVISE AS |
| | REQUIRED. PROVIDE COMPLETE ENGINEERING |
| | CALCULATIONS FOR CONNECTORS AND |
| | FASTENERS TO BE USED IF THEYDIFFER |
| | FROM THOSE ALREADY ENGINEERED AND |
| | PUBLISHED ON SIMPSON CATALOGUE. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 4-REVISE FRAMING DETAIL FOR ARCHED |
| | OPENINGS. 1X4 BLOCKS ALONG ARCH DON'T |
| | WORK. NEED 2X BLOCKS TO INSTALL WINDOW |
| | FRAME. SEE PRODUCT APPROVAL. REVISE AS |
| | REQUIRED. |
| | |
| | 5-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| | ENTRY DOOR SHOWING 2X BUCK AS REQUIRED |
| | BY DOOR PRODUCT APPROVAL. |
| | |
| | 6-PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL (2 COPIES) FOR: |
| | A) ENTRY DOOR AS SHOWN ON PLANS WITH |
| | COMPLETE DRAWINGS. |
| | B) GUARDRAILS WITH SPECS TO BE INSTALLED |
| | ON WOOD FRAMED FLOORS. NOT CONCRETE |
| | SLAB |
| | |
| | 7-REVISE PLANS TO SHOW ENTRY DOOR WITH |
| | INSWING AS PER PRODUCT APPROVAL. |
| | |
| | 8-REVISE/CLARIFY FOOTING F3 FOR WOOD |
| | COLUMNS. |
| | APPROVED PER JULIO'S PROVISOLM |