| 2004-11-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT SP1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET THE CODE REQUIREMENTS, NOR DOES |
| | IT REFLECT THE FLOOR PLAN. |
| | A) ALL WATER CLOSETS SHALL NOT BE |
| | DOUBLE TRAPPED PER SECTION 1002.1. THE |
| | W/C'S HAVE AN INTEGRAL TRAP BUILT IN THE |
| | FIXTURE. |
| | B) THE WASH MACHINE REQUIRES THE |
| | CLEANOUT TO BE 4 FT ABOVE THE FLOOR FOR |
| | ACCESS, AND A STANDPIPE PER SECTIONS |
| | 708.10, AND 1002.1 |
| | C) THE LAV IN THE POWDER ROOM IS NOT |
| | VENTED AND AS SHOWN CREATES AN "S" TRAP |
| | WHICH IS NOT APPROVED. SECTIONS 902.1 |
| | AND 1002.3(5) |
| | D) SANITARY CROSS FITTINGS SHOWN IN THE |
| | POWDER ROOM ARE NOT APPROVED. SEE |
| | EXAMPLE OF CORRECT PIPING FOR POWDER |
| | ROOM ON ONE SET OF PLANS. SECTION 704.2 |
| | E) LAV IN MASTER BATH AND LAV IN SHOWER |
| | BATH BY SITTING ROOM ARE NOT VENTED AND |
| | AS SHOWN CREATE AN "S TRAP" SECTIONS |
| | 902.1 AND 1002.3(5) |
| | F) TUB BATH SECOND FLOOR SHOWS AN EXTRA |
| | LAV ON RISER DIAGRAM NOT SHOWN ON THE |
| | FLOOR PLAN. SECTION 104.2.1 |
| | G) THE SHOWER BATHROOM ON THE FAR LEFT |
| | OF THE FLOOR PLAN IS NOT SHOWN ON THE |
| | SANT. RISER DIAGRAM. CORRELATE RISER |
| | WITH THE FLOOR PLAN. SECTION 104.2.1 |
| | 2) 61G1-16.004(2) THE FIRM LICENSE |
| | NUMBER IS REQUIRED ON THE TITLE BLOCK |
| | FOR THE GARRISON DESIGN GROUP. FS |
| | 481.219 |
| | |
| | |
| | |