Plan Review Notes
Plan Review Notes For Permit 04110992
Permit Number 04110992
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT SP1 SANITARY RISER DIAGRAM DOES
 NOT MEET THE CODE REQUIREMENTS, NOR DOES
 IT REFLECT THE FLOOR PLAN.
 A) ALL WATER CLOSETS SHALL NOT BE
 DOUBLE TRAPPED PER SECTION 1002.1. THE
 W/C'S HAVE AN INTEGRAL TRAP BUILT IN THE
 FIXTURE.
 B) THE WASH MACHINE REQUIRES THE
 CLEANOUT TO BE 4 FT ABOVE THE FLOOR FOR
 ACCESS, AND A STANDPIPE PER SECTIONS
 708.10, AND 1002.1
 C) THE LAV IN THE POWDER ROOM IS NOT
 VENTED AND AS SHOWN CREATES AN "S" TRAP
 WHICH IS NOT APPROVED. SECTIONS 902.1
 AND 1002.3(5)
 D) SANITARY CROSS FITTINGS SHOWN IN THE
 POWDER ROOM ARE NOT APPROVED. SEE
 EXAMPLE OF CORRECT PIPING FOR POWDER
 ROOM ON ONE SET OF PLANS. SECTION 704.2
 E) LAV IN MASTER BATH AND LAV IN SHOWER
 BATH BY SITTING ROOM ARE NOT VENTED AND
 AS SHOWN CREATE AN "S TRAP" SECTIONS
 902.1 AND 1002.3(5)
 F) TUB BATH SECOND FLOOR SHOWS AN EXTRA
 LAV ON RISER DIAGRAM NOT SHOWN ON THE
 FLOOR PLAN. SECTION 104.2.1
 G) THE SHOWER BATHROOM ON THE FAR LEFT
 OF THE FLOOR PLAN IS NOT SHOWN ON THE
 SANT. RISER DIAGRAM. CORRELATE RISER
 WITH THE FLOOR PLAN. SECTION 104.2.1
 2) 61G1-16.004(2) THE FIRM LICENSE
 NUMBER IS REQUIRED ON THE TITLE BLOCK
 FOR THE GARRISON DESIGN GROUP. FS
 481.219
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]