| 2004-11-23 00:00:00 | ********** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE PLANS INDICATE |
| | ELECTRICAL PANELS A,B,& C, YET THERE ARE |
| | ALSO 3 OTHER PANELS SHOWN ON PLANS? |
| | PLEASE CORRELATE PLANS WITH RISER |
| | DIAGRAM. IF THERE ARE MORE PANELS, |
| | PLEASE REVISE RISER DIAGRAM. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 PLEASE SEE THERE ARE MANY |
| | LOCATIONS ON PLANS. |
| | |
| | 3)NOTE: PLEASE VERIFY RECEPT SPACING |
| | ALONG KITCHEN COUNTERSPACE PER 210.52C1 |
| | IT APPEAR THERE MAY BE A COUPLE |
| | MISSING? |
| | THIS IS A NOTE ONNLY TO VERIFY. |
| | |
| | 4)NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | ON GROUNDING ELECTRODE SYSTEM. |
| | PER 250.50 |
| | |
| | 5)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM PANEL "B" TO |
| | PANEL"A".250.110,250.24 |
| | |
| | 6)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | NFPA-72 8-1.4.1.6.2, 8-1.4.2 |
| | PLEASE SEE MISSING SD LEADING TO FLOOR |
| | ABOVE |
| | |
| | 7)NOTE: PLEASE SEE MISSING GFI RECEPT IN |
| | UPSTAIRS BATHRM. |
| | 210.52D,210.11C3 |
| | |
| | 8)NOTE: PLEASE SEE 210.52E FOR MISSING |
| | FRONT AND REAR GFI RECEPTS. |
| | |
| | |
| | 9)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 10)NOTE: PLEASE SEE MISSING LICENSE #'S |
| | ON TITLE BLOCK FOR THE GARRISON GROUP. |
| | REQUIRED PER FS 481.223 |
| | |
| | PLEASE SEE ONE SET OF PLANS HAS MANY OF |
| | THE ABOVE ITEMS REDLINED FOR THE ABOVE |
| | COMMENTS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW ONLY. |
| | ONE COPY/SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |