| Date |
Text |
| 2004-12-10 00:00:00 | CHECKLIST: |
| | 1-SURVEY DOESN'T MATCH PLANS. ALSO, |
| | PROVIDE 2 COPIES. |
| | |
| | 2-PROVIDE SPECIFICATIONS FOR ATTIC LIVE |
| | LOAD (BOTTOM CHORD OF TRUSSES) AS |
| | REQ'DBY TABLE 1604.1 FBC 2001. ALSO, |
| | SPECIFY 10PSF OR 30PSF IF IT'S FOR |
| | STORAGE OR NOT. |
| | |
| | 3-SPECIFY TYPE AND SPACING FOR WWM |
| | SUPPORTS AS REQ'D BY SEC. 1909.3 FBC. |
| | ***NOTE: SPECIFY JOINTS AS REQUIRED ON |
| | SOIL TEST REPORT INDICATIONS. |
| | |
| | 4-SPECIFY TILE FASTENING AS REQUIRED BY |
| | SEC. 104.2.1.1 CITY AMENDMENTS TO FBC. |
| | |
| | 5-ENTRY DOOR TO PROVIDE 32" MIN. CLEAR |
| | OPENING PER LEAF AS REQUIRED BY TABLE |
| | 1004 FBC 2001. REVISE AS REQUIRED. |
| | |
| | 6-AREA CALCULATIONS DON'T ADD UP. |
| | REVISE |
| | AS REQUIRED. |
| | |
| | 7-PROVIDE 1ST FLOOR COMPLETE BATHROOM |
| | WITH DOOR THAT ALLOWS 29" MIN. CLEAR |
| | OPENING AS REQ'D BY SEC. 11-11 FBC |
| | 2001. |
| | REVISE DOOR SIZE AT TOILET ROOM. |
| | |
| | 8-STAIRS: A) PROVIDE COMPLETE FRAMING |
| | DETAIL. |
| | B) DETAIL/SECTIONS TO MATCH PLANS. |
| | C) REVISE STAIRS RATIO SPECIFIED ON |
| | SHEET A1. SEE SEC. 1007.3 EXCEPTION 1. |
| | D) REVISE HANDRAIL HEIGHT SPECIFIED ON |
| | DRAWING A10. SEE SEC. 1007.5 FBC 2001. |
| | E) SPECIFY FIREBLOCKING LOCATION AND |
| | MATERIAL AS REQ'D BY SEC. 2305.1.4 FBC. |
| | |
| | 9-ALL ATTIC ACCESS AT 2ND FLOOR TO BE |
| | 20X36 MIN AS REQ'D BY SEC. 2309.6 FBC. |
| | |
| | 10-SPECIFY ALL CONNECTORS ON ROOF |
| | FRAMING PLANS. SEE COMMENTS ON PLANS |
| | FOR |
| | MISSING CONNECTORS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11-SPECIFY TOP CONNECTORS FOR COLUMNS |
| | AT |
| | LANAI AREA. PROVIDE DETAIL SHOWING HOW |
| | THE CONNECTOR WORKS. SEC. 104.2.1.2 |
| | CITY |
| | AMENDEMNTS TO FBC 2001.SPECIFY |
| | CONNECTORS FOR (3)2X12 BEAM AT ENTRY. |
| | SEC. 104.2.1.2 CITY AMENDEMTNS TO FBC. |
| | |
| | 12-SPECIFY CONNECTORS FOR LANAI BEAMS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 13-AFTER CORRECTIONS ARE DONE TO THE |
| | DWGS, BRING THEM FOR HISTORICAL |
| | APPROVAL |
| | AND STAMPING OF PLANS PRIOR TO |
| | SUBMITTAL |
| | TO THIS OFFICE TO EXPEDITE REVIEW. |
| | |
| | 14-UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| | LATEST CATALOGUE THAT IS UPDATED TO |
| | COMPLY WITH SEC. 1609.4.3 FBC 2001 |
| | REGARDING THE STEEL STRESS INCREASE. |
| | **NOTE: PROVIDE COMPLETE ENGINEEING FOR |
| | TYPE AND NUMBER OF FASTENERS THAT |
| | DIFFER |
| | FROM THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 15-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | FRAMING AT ARCHED WINDOWS/DOORS. |
| | SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 16-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| | 2X |
| | BUCK AS REQUIRED ON STANLEY DOOR |
| | PRODUCT |
| | APPROVAL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS |
| | TO FBC 2001. |
| | |
| | 17-PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL FOR: A)ARCHED ENTRY DOORS AS |
| | SHOWN ON PLANS. |
| | B) STRUCTURAL CONNECTORS USED |
| | (SIMPSON/USP). |
| | C) MULLIONS AND CLEARLY INDICATE SIZE |
| | AND FASTENER TYPE USED. |
| | |
| | 18-PROVIDE COMPLETE DETAILS AND SPECS |
| | FOR |
| | GUARDRAIL AT 2ND STORY VERANDA. SEE |
| | SEC. |
| | 1015 FBC 2001. |
| | |
| | 19-CONTRACTOR TO UPDATE WORKERS COMP. |
| | |
| | 20-SPECIFY LOCATION AND MATERIAL FOR |
| | DRAFSTOPPING REQUIRED AT 2ND FLOOR BY |
| | SEC. 2305.2.2 FBC 2001. |
| | |
| | 21-NORTH ARROW ORIENTATION SHOWN ON |
| | SITE |
| | PLAN SHEET SP1 IS INCORRECT. REVISE. |
| | |
| | 22-SHEET A1: WALLS AROUND FUTURE |
| | ELEVATOR ARE BEARING WALLS, BUT THEY |
| | ARE |
| | SHOWN AS NON-BEARING WALLS. REVISE. |
| | |
| | 23-SHEET A5: A) SPECIFY FOOTING SIZE |
| | FOR |
| | |
| | BEARING WALLS AT FUTURE ELEVATOR AREA. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | B) SPECIFY MISSING CONNECTORS AT GARAGE |
| | WALKWAY AND LANAI. SEE COMMENTS ON |
| | PLAN. |
| | |
| | 24-SHEET A6: SPECIFY MISSING |
| | CONNECTORS. |
| | SEE PLANS FOR COMMENTS. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 25-SHEET A7: A) PROVIDE WALL SECTION |
| | DETAIL THRU EXTERIOR BEARING WALL |
| | SUPPORTED ON GIRDER TRUSSES. SPECIFY |
| | ALL |
| | FASTENERS. SEC. 104.2.1.2 CITY |
| | AMENDMENT |
| | B) PROVIDE DETAIL SECTION AT VERANDA |
| | COLUMN SHOWING HOW ARE SPECIFIED |
| | CONNECTORS INSTALLED. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. SEE PLANS. |
| | C) PROVIDE DETAIL SECTION AT TRANSITION |
| | OF WOOD FRAMING TO MASONRY WALL. |
| | SPECIFY |
| | ALL FASTENERS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 26-SHEET A9: A) 2 STORY BLOCK/WOOD WALL |
| | SECTION: HOW IS 2X BOTTOM PLATE |
| | ATTACHED |
| | TO TRUSS WITH 8D NAIL THAT IS 1 1/2" |
| | LONG. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | B) SPECIFY SPACING OF ROOF VENTS. SEC. |
| | 2309.7 FBC 2001. |
| | C) WHERE IS THE WINDOW SILL DETAIL. SEE |
| | COMMENTS ON PLANS. |
| | |
| | 27-SHEET A10: A) TYP. ANCHOR DETAIL: |
| | CLARIFY HOW IS PT 2X8 LEDGER ANCHOR |
| | FASTENED WITH 8D NAILS?. ALSO, LEDGER |
| | IS |
| | NOT SHOWN ON DETAIL. SEC. 104.2.1.2 |
| | CITY |
| | AMENDMENTS TO FBC 2001. |
| | B) BEARING WALL DETAIL WITH OPENINGS. |
| | SPECIFY HOW IS WOOD HEADER FASTENED. |
| | SEC |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | C) SEE COMMENTS ON PLAN. |
| | |
| | 28-PROVIDE ONLY DETAILS THAT APPLY TO |
| | THIS PROJECT TO EXPEDITE REVIEW PROCESS |
| | AND AVOID CONFUSIONS. |
| | |
| | 29-SHEET A12:UPDATE REFERENCE |
| | STANDARDS. |
| | SEE COMMNETS ON SHEET AND CHAPTER 35 |
| | FBC |
| | 2001 FOR PROPER REFERENCE AND EDITION |
| | TO |
| | BE USED. |
| | |
| | 30-APPLICATION FOR EXISTING USE CREDIT |
| | HAS A DIFFERENT ADDRES. CLARIFY AS |
| | REQUIRED. |
| | |
| | 31-ENERGY CALCULATIONS: COMPLET BUILDER |
| | INFORMATION AND OWNER/AGENT TO SIGN AND |
| | DATE BOTTOM OF FORM AS WELL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |