Plan Review Notes
Plan Review Notes For Permit 04110984
Permit Number 04110984
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00** UNSAT **
  
 1)NOTE: PLEASE PROVIDE INFORMATION ON
 MOTOR CONTROL PANEL.:
 DISCONNECTING MEANS FOR PUMPS?
 OVERCURRENT PROTECTION FOR PUMPS?
 GROUNDING?
  
 *PLEASE ALSO PROVIDE SIZE OF PUMPS.
 PLANS APPEAR TO LEAD THAT PUMPS ARE ALL
 EXSITING? ONLY CHANGING CONTROL PANEL
 AND CONDUCTORS.?
  
 SUBMITTING SPEC SHEETS FOR CONTROL PANEL
 ETC MAY HELP WITH SOME CLARIFICATION.
  
  
 PLEASE SEE PLANS ARE ONLY IN FOR PLAN
 REVIEW AND NOT FOR PERMIT AT THIS TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND INSERT ANY NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]