Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop B
Sequence Number 96
Notes
Date Text
2006-10-22 16:27:35BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 10/18/06 FOR PRODUCT DATA ON RAISED
 STUCCO/FOAM ARCHITECTURAL TRIM.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC TABLE 600 REQUIRES THE MATERIALS USED IN THE
 EXTERIOR NONBEARING WALLS, OF TYPE I BUILDINGS, TO BE
 NONCOMBUSTIBLE.FBC 1404.1.1 GIVES EXCEPTION TO THIS
 ONLY FOR ARCHITECTURAL TRIM NOT MORE THAN 40 FT ABOVE
 GRADE.TO MEET THE FBC 202 DEFINITION OF
 'NONCOMBUSTIBLE', ALL OTHER ARCHITECTURAL TRIM SHALL
 EITHER [1] PASS THE TEST PROCEDURE SET FORTH IN ASTM E
 136, OR [2] HAVE A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL (WHICH MUST COMPLY WITH [1]), AND A SURFACING
 NOT MORE THAN 1/8 INCH THICK THAT HAS A FLAMESPREAD
 RATING NOT GREATER THAN 50, WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84.THE SUBMITTED DATA SHOWS THAT THE
 DRYVIT COATING HAS A FLAMESPREAD OF LESS THAN 50, WHEN
 TESTED PER ASTM E 84, BUT THE 'STRUCTURAL BASE' (OR
 FOAMED PLASTIC) HAS NOT BEEN SHOWN TO PASS THE TEST
 PROCEDURE SET FORTH IN ASTM E 136 "TEST METHOD FOR
 BEHAVIOR OF MATERIALS IN A VERTICAL TUBE FURNACE AT 750
 DEGREES C".THE DEFINITION OF NONCOMBUSTIBLE REQUIRES
 THAT THE MATERIAL PASS THIS TEST.PLEASE SUBMIT A TEST
 REPORT TO SHOW THAT THE FOAMED PLASTIC HAS PASSED THE
 ASTM E 136 TEST.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]