| 2006-10-22 16:27:35 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | SUBMITTAL ON 10/18/06 FOR PRODUCT DATA ON RAISED |
| | STUCCO/FOAM ARCHITECTURAL TRIM. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC TABLE 600 REQUIRES THE MATERIALS USED IN THE |
| | EXTERIOR NONBEARING WALLS, OF TYPE I BUILDINGS, TO BE |
| | NONCOMBUSTIBLE.FBC 1404.1.1 GIVES EXCEPTION TO THIS |
| | ONLY FOR ARCHITECTURAL TRIM NOT MORE THAN 40 FT ABOVE |
| | GRADE.TO MEET THE FBC 202 DEFINITION OF |
| | 'NONCOMBUSTIBLE', ALL OTHER ARCHITECTURAL TRIM SHALL |
| | EITHER [1] PASS THE TEST PROCEDURE SET FORTH IN ASTM E |
| | 136, OR [2] HAVE A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL (WHICH MUST COMPLY WITH [1]), AND A SURFACING |
| | NOT MORE THAN 1/8 INCH THICK THAT HAS A FLAMESPREAD |
| | RATING NOT GREATER THAN 50, WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84.THE SUBMITTED DATA SHOWS THAT THE |
| | DRYVIT COATING HAS A FLAMESPREAD OF LESS THAN 50, WHEN |
| | TESTED PER ASTM E 84, BUT THE 'STRUCTURAL BASE' (OR |
| | FOAMED PLASTIC) HAS NOT BEEN SHOWN TO PASS THE TEST |
| | PROCEDURE SET FORTH IN ASTM E 136 "TEST METHOD FOR |
| | BEHAVIOR OF MATERIALS IN A VERTICAL TUBE FURNACE AT 750 |
| | DEGREES C".THE DEFINITION OF NONCOMBUSTIBLE REQUIRES |
| | THAT THE MATERIAL PASS THIS TEST.PLEASE SUBMIT A TEST |
| | REPORT TO SHOW THAT THE FOAMED PLASTIC HAS PASSED THE |
| | ASTM E 136 TEST. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: |
| | (561) 805 6652ROBERT BROWN |