| Plan Review Notes For Permit 04110961 |
| Permit Number |
04110961 |
|
| Review Stop |
B |
| Sequence Number |
95 |
|
| Notes |
| Date |
Text |
| 2006-09-06 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL AND STRUCTURAL REVISION | | | SUBMITTED ON 6/28/06 OK EXCEPT REVISED | | | SHEETS A4-2 AND A5-4 WHICH ARE DENIED. | | | SEE COMMENT BELOW. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC (PLUMBING) 1107.1OVERFLOW | | | SCUPPERS.THE REVISION TO SHEET A4-2 | | | (WEST ELEVATION) AND SHEET A5-4, DETAIL | | | 4, SHOWS THE OMISSION OF SECONDARY | | | OVERFLOW SCUPPERS FROM THE ROOF AT 11TH | | | FLOOR LEVEL.THE SCUPPERS ARE REQUIRED | | | IN CASE THE PRIMARY ROOF DRAINS BECOME | | | BLOCKED AND ALLOW WATER BUILD-UP. | | | SUBMIT AN ALTERNATIVE REVISION OR | | | CONSTRUCT TO THE PLAN REVISION ALREADY | | | ON FILE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|