Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 8
Notes
Date Text
2006-08-17 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHT P2.08 NO GAS PIPING SHOWN TO NEW
 SPA HEATER. - SHOWS WATER PIPING FOR
 HOSE BIBB CONNECTING TO STORM DRAINAGE
 AT UNIT F2. PLEASE CLARIFY. SECTION
 104.2.1.
  
 2. SHT P2.09 EMERGENCY DRAINS AT B1
 UNITS SHALL BE MINIMUM 5". ONE DRAINS
 2340SF AND THE OTHER DRAINS 2510SF AND
 BOTH SHOW 4". TABLE 1106.3.
  
 3. SHT P2.10 REVISION #6 NOT FOUND.
 PLEASE INDICATE WHERE REVISION CAN BE
 LOCATED. SECTION 104.2.1.
  
 4. SHT P3.13 RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE INDICATE
 WHERE THE OFFSETS FOR THE "A" SECTION
 CAN BE LOCATED ON THE FLOOR PLANS. THE
 FIRST FLOOR DOES NOT REFLECT THE FLOOR
 PLAN NOR DOES THE SECOND FLOOR.
  
 5. SHT P3.15 THE FOLLOWING INFORMATION
 IS REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. **** NOT ALL CUT SECTIONS
 SHOW THE CORRESPONDING LENGTHS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED. **** INDICATE IF THE 3" PIPE
 WILL BE SCREW PIPE OR WELDED.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). **** #13 INDICATES 1,050,000
 BTU'S BUT SUBMITTAL INDICATES 1,260,000
 BTU'S. CORRELATE SUBMITTALS AND RISER
 DIAGRAM INFORMATION. SECTION 104.2.1.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. ****
 MANUF. SPECIFICATION SHEETS FOR POOL
 HEATERIN SUBMITTAL BOOK INDICATES A
 DIFFERENT POOL HEATER AND DIFFERENT
 BTU'S THAN SHOWN ON THE RISER DIAGRAM. -
 SUBMIT THE MANUF. SPEC'S FOR THE SPA
 HEATER. THE MANUF. SPEC'S FOR THE
 FIREPLACE SHOWS NO LISTING. SUBMIT
 MANUF. SPEC'S FOR THE MECH. GAS BOILER
 (#8). SUBMIT MANUF. SPECIFICATION SHEETS
 FOR BBQ GRILLS.
  
 F. SUBMIT THE MANUF. SPECIFICATION
 SHEETS FOR EACH GAS REGULATOR. SHOW
 LISTING FOR REGULATOR. INDICATE MODEL
 NUMBER.
  
 G. INDICATE MATERIAL FOR REGULATOR VENT
 LINES. NFPA 54 SECTION 5.6.4.
 5.6.4 PLASTIC PIPE, TUBING, AND
 FITTINGS. PLASTIC PIPE, TUBING, AND
 FITTINGS SHALL BE USED OUTSIDE
 UNDERGROUND ONLY .
  
 H. GAS CODE REFERENCE IS INFICATED AS
 FBC-2201 ON PLANS. PLEASE CORRECT TO
 FBC-2001 FUEL GAS CODE.
  
 I. SHUT OFF VALVE REQUIRED UPSTREAM OF
 THE REGULATORS. (SEE BBQ GRILLS).
 SECTION 410.2(5). A UNION IS REQUIRED
 BETWEEN SHUT OFF VALVE AND REGULATOR FOR
 THE POOL HEATERS.
  
 6. THREE SETS OF REVISIONS REQUIRED FOR
 REVIEW. (ONLY 2 SETS SUBMITTED).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  