| 2005-09-19 00:00:00 | BUILDING PLAN REVIEW |
| | ******PROVISO******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | -PROVISO- |
| | WINDOW WALLS: THE WINDOW SHOP DRAWING |
| | SUBMITTAL SHALL INCLUDE A STRUCTURAL |
| | MULLION.THE MULLION MUST BE CAPABLE OF |
| | SPANNING HORIZONTALLY ACROSS THE ENTIRE |
| | WIDTH OF THE OPENING FOR THOSE WINDOWS |
| | THAT EXCEED THE MAXIMUM HEIGHT STATED IN |
| | THE SUBMITTED MIAMI WALL SYSTEMS INC. |
| | FIXED WINDOW LARGE MISSILE IMPACT SERIES |
| | 101 AND SMALL MISSILE IMPACT SERIES 101 |
| | PRODUCT APPROVAL NOA'S 03-0415.18 AND |
| | 05-0420.01. |
| | |
| | -PROVISO- |
| | SLIDING GLASS DOORS:THE WINDOW/DOOR |
| | SUBCONTRACTOR SHALL PROVIDE RATIONAL |
| | ANALYSIS FROM A FLORIDA REGISTERED |
| | ENGINEER TO JUSTIFY THE USE OF THE |
| | PROPOSED SLIDING GLASS DOOR IN SIZES |
| | THAT EXCEED THE MAXIMUM IN THE SUBMITTED |
| | MIAMI WALL SYSTEMS INC. SERIES 100 |
| | SLIDING GLASS DOOR PRODUCT APPROVAL |
| | NOA'S 04-0908.02 AND 01-1108.03. |
| | NOTE: MISSILE IMPACT RATING FOR THESE |
| | LARGER SIZES CANNOT BE JUSTIFIED BY |
| | RATIONAL ANALYSIS.MISSILE IMPACT TEST |
| | RESULTS MUST BE SUBMITTED. |
| | |
| | -PROVISO- |
| | HORIZONTAL SLIDER WINDOWS: IT IS NOTED |
| | THAT 'CUT-DOWN' SLIDING GLASS DOORS WILL |
| | BE USED FOR THOSE HORIZONTAL SLIDER |
| | WINDOWS WHICH EXCEED 6'-6" WIDE X 6'-0" |
| | HIGH (FOR EXAMPLE W2, W2.1, W3, W3.1, |
| | W3.2, W4, W4.1, W5, W5.1, W6, W6.1, |
| | W6.2). |
| | |
| | -PROVISO- |
| | FIXED WINDOWS:THE WINDOW SHOP DRAWING |
| | SUBMITTAL SHALL INCLUDE A STRUCTURAL |
| | MULLION.THE MULLION MUST BE CAPABLE OF |
| | SPANNING HORIZONTALLY ACROSS THE ENTIRE |
| | WIDTH OF THE OPENING FOR THOSE WINDOWS |
| | THAT EXCEED THE 6'-0" MAXIMUM HEIGHT |
| | STATED IN THE SUBMITTED MIAMI WALL |
| | SYSTEMS INC. SERIES 122 ALUMINUM FIXED |
| | WINDOW PRODUCT APPROVAL NOA 04-0322.09. |