2007-06-15 09:23:51TEST AND BALANCE REPORT:
  
 TWO OF THE READINGS ON THE REPORT ARE OUTSIDE OF THE
 10% ACCEPTABLE RANGE OF VARIANCE FROM DESIGN CFM. ONE
 IS ON PG.29 AND THE OTHER IS ON PG. 51. THE ITEMS HAVE
 BEEN HIGHLIGHTED IN ONE OF THE COPIES OF THE REPORT FOR
 YOUR CONVENIENCE. ONCE THE CORRECTIONS HAVE BEEN MADE
 AND THE REPORT IS RE-CERTIFIED, IT MAY BE GIVEN TO THE
 INSPECTOR IN THE FIELD.
  