Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 4
Notes
Date Text
2005-09-09 00:00:00PASSED/PROVISO
  
 SHT AI-303 REVISION REQUIRED FOR
 ELEVATION #3 SHOWING THE FOLLOWING:
 11-4.24.2 HEIGHT
 11-4.24.4 SINK DEPTH
 11-4.24.5 CLEAR FLOOR SPACE - FORWARD
 APPROACH REQUIRED.
 11-4.24.6 EXPOSED PIPES & SURFACES
 11-4.24.7 FAUCETS
 SHT P2.10 REVISION REQUIRED FOR
 EMERGENCY (SECONDARY) STORM DRAINS.
 DRAINS SHALL SHOW THE S.F. FOR THE TOTAL
 AREA DRAINED TO EACH SECONDARY STORM
 DRAIN. (SEE RED LINE CORRECTIONS) -
 PRIMARY AND SECONDARY ROOF DRAINS
 REQUIRED FOR THE RECREATION DECK. ALSO
 SUBMIT STORM RISER DIAGRAMS AND STORM
 DRAIN ISOMETRIC.
 SHT P3.12 EMERGENCY STORM DRAIN
 COLLECTION ISOMETRIC. REVISION REQUIRED
 SHOWING CORRECT S.F. FOR EACH DRAIN AND
 CORRECT PIPE SIZING. (SEE RED LINE
 CORRECTIONS ON SET).
 SHT P3.15 VOIDED - SEPARATE GAS PLANS &
 PERMIT REQUIRED. MANUF. SPECIFICATION
 SHEETS REQUIRED FOR THE FIREPLACE (#5)
 AND THE BOILER (#8).
 SHT P4.03 REVISION REQUIRED, SOVENT
 SYSTEM SHALL BE DESIGNED PER DESIGN
 MANUAL #802 PER ENGINEER. (9-1-5)