| 2005-08-29 00:00:00 | *********** PROVISO ************ | | | | | | 1)NOTE: ALLMAIN ELECTRICAL ROOMS AND | | | THE FIRE COMMAND ROOM WILL BE REQUIRED | | | TO HAVE A BATTERY BACK UP TYPE OF | | | FIXTURE IN ADDITION TO LTS ON EM | | | CIRCUIT(S). | | | | | | 2)NOTE: PLEASE SEE CIRCUITING FOR | | | ELEVATOR RMS/HOISTWAYS, 620.23,620.24 | | | THIS IS MINOR ADJUSTMEN IN CIRCUITING. | | | | | | 3)NOTE: PLEASE SEE CIRCUTING OF | | | EMERGENCY CIRCUITS WILL STILL NEED TO BE | | | ADDRESSED. | | | AT THIS TIME, THE TRIPPING OF A SINGLE | | | BRKR ON EMERGENCY POWER WOULD LEAVE | | | EGRESS HALLWAYS,STAIRWAYS IN TOTAL | | | DARKNESS, EVEN ON GENERATOR BACK-UP. | | | | | | PLEASE KNOW A MEETING EITHER VIA PHONE | | | OR IN PERSON MAY BE NEEDED TO GO OVER | | | THIS COMMENT FURTHER. | | 2005-08-26 00:00:00 | MEP PLANS IN ELECTRICAL FOR REVIEW. | | | REVIEW STARTED. | | | PLANS WILL BE THE "P"(PASSED STATUS ON | | | MONDAY 8/29/05 WITH A PROVISO FOR TWO | | | ITEMS MENTIONED ON PREVIOUS REVIEW. | | | ALL OTHER COMMENTS OK. | | | ELECTRICAL PLANS TO BE STAMPED 8/29 |
|