Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop B
Sequence Number 4
Notes
Date Text
2005-08-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 7/29/05:
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 8) PRODUCT APPROVALS.
 (A) GENERAL: SOME OF THE OPTIONS
 COVERED BY THE SUBMITTED PRODUCT
 APPROVALS MAY NOT BE CODE COMPLIANT IF
 USED FOR THIS PROJECT/LOCATION.FOR
 EACH PRODUCT APPROVAL, THE SHEETS SHALL
 BE MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED AND THE DESIGN PRESSURES.
 THIS COMMENT WAS MADE PREVIOUSLY BUT HAS
 NOT BEEN ADDRESSED.
 (B) ROOF: THE SUBMITTED STATEWIDE
 PRODUCT APPROVAL COVER SHEET FL1579 DOES
 NOT MATCH THE SUBMITTED SARNAFIL SINGLE
 PLY PVC ROOF SYSTEM PRODUCT APPROVAL
 NOA# 02-0603.06.SARNAFIL DOES NOT HAVE
 A STATEWIDE PRODUCT APPROVAL FOR THIS
 PRODUCT AND WOULD HAVE TO SUBMIT AN
 APPLICATION FORM FOR LOCAL PRODUCT
 APPROVAL.
 (C) WINDOW WALLS: SHEET A3-3, THE
 OVERALL HEIGHT OF TOWER FIXED GLASS
 WINDOW SF-4 AND STOREFRONT STF-1, 2, 4,
 5 AND 11 RANGES FROM 12'-0" TO 17'-4".
 THIS EXCEEDS THE MAXIMUM HEIGHT COVERED
 BY THE SUBMITTED MIAMI WALL SYSTEMS INC.
 FIXED WINDOW LARGE MISSILE IMPACT SERIES
 101 AND SMALL MISSILE IMPACT SERIES 101
 PRODUCT APPROVAL NOA'S 03-0415.18 AND
 05-0420.01.SUBMIT A PRODUCT APPROVAL
 FOR A STRUCTURAL MULLION CAPABLE OF
 SPANNING HORIZONTALLY ACROSS THE ENTIRE
 WIDTH OF THE OPENING SO THAT THE WINDOWS
 ARE NOT REQUIRED TO SPAN THE ENTIRE
 HEIGHT OF THE OPENING.
 (D) SLIDING GLASS DOORS:SHEET A3-3,
 THE HEIGHT OF THE SLIDING GLASS DOORS IS
 10'-1" WHICH EXCEEDS THE MAXIMUM HEIGHT
 COVERED BY THE SUBMITTED MIAMI WALL
 SYSTEMS INC. SERIES 100 SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA'S 04-0908.02
 AND 01-1108.03.SUBMIT ALTERNATIVE
 PRODUCT APPROVALS.ALSO, THE FIRST
 FLOOR SLIDING GLASS DOORS HAVE FIXED
 GLASS WINDOWS ABOVE 10'-1" SO A
 STRUCTURAL MULLION CAPABLE OF SPANNING
 HORIZONTALLY ACROSS THE ENTIRE WIDTH OF
 THE OPENING IS REQUIRED. SUBMIT A
 PRODUCT APPROVAL FOR A STRUCTURAL
 MULLION.
 (E) STOREFRONT DOORS:NO PRODUCT
 APPROVAL WAS SUBMITTED.SUBMIT A
 STOREFRONT DOOR PRODUCT APPROVAL.
 (F) ALUMINUM PICKET RAILING SYSTEM:
 THE APPLICATION FOR LOCAL PRODUCT
 APPROVAL TOGETHER WITH THE SUBMITTED
 MIAMI-DADE PRODUCT APPROVAL NOA#
 01-0206.14 HAS BEEN SUBMITTED TO THE
 BUILDING OFFICIAL FOR FINAL
 REVIEW/APPROVAL.
 (H) HOLLOW METAL DOORS: THE DOORS
 COVERED BY THE SUBMITTED CECO DOOR
 PRODUCTS PRODUCT APPROVAL NOA'S
 03-0411.02 AND 03-0411.03 HAVE MAXIMUM
 DESIGN PRESSURES OF +53PSF/-45PSF AND
 +45PSF/-45PSF, WHICH ARE NOT SUFFICIENT
 TO RESIST THE DESIGN PRESSURES STATED IN
 THE SUBMITTED RWDI WIND LOAD REPORT FOR
 THE BUILDING.FOR EXAMPLE THE ROOF
 LEVEL DOORS 120, 121 AND 122 HAVE DESIGN
 PRESSURES OF +85PSF/-95PSF AND THE
 GROUND LEVEL DOORS 03, 05, 06, 09, 11,
 21 AND 26 HAVE DESIGN PRESSURES OF UPTO
 +85PSF/-85PSF.
 (J) HORIZONTAL SLIDER WINDOWS: SHEET
 A3-2, THE SUBMITTED MIAMI WALL SYSTEMS
 INC HORIZONTAL SLIDER WINDOW PRODUCT
 APPROVAL NOA'S 04-1122.02 AND 04-1215.03
 COVER WINDOWS UPTO 6'-6" WIDE X 6'-0"
 HIGH WHICH IS NOT SUFFICIENT FOR SOME OF
 THE SPECIFIED WINDOWS (E.G. W2, W2.1,
 W3, W3.1, W3.2, W4, W4.1, W5, W5.1, W6,
 W6.1, W6.2).SUBMIT A PRODUCT APPROVAL
 FOR WINDOWS SIZED TO MATCH OR EXCEED THE
 SIZES OF THE PROPOSED WINDOWS.
 (K) WHEN ALL OF THE REQUIRED PRODUCT
 APPROVALS HAVE BEEN COLLATED, PLEASE
 ENSURE THAT THEY ARE MARKED UP, AS
 DESCRIBED IN COMMENT 8(A) ABOVE, BEFORE
 RE-SUBMITTAL.
 (L) NO PRODUCT APPROVAL WAS SUBMITTED
 FOR FIXED WINDOWS.WILL THE STOREFRONT
 WINDOW BE USED AS FIXED WINDOWS?IF
 NOT, SUBMIT A SEPARATE PRODUCT APPROVAL
 FOR THE FIXED WINDOWS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]