| 2007-03-26 14:46:09 | SOME PAGES APPROVED, OTHERS DENIED AS LISTED BELOW: |
| | |
| | M1.01A: SEF-LR2 ON EXHAUST FAN SCHEDULE, M6.02 DATED |
| | 10/5/06, SHOWS 4200 CFM. RISER DIAGRAM SHOWS 1400 CFM, |
| | BRANCH SIZES ON THIS PAGE DO NOT MATCH SIZES ON RISER |
| | DETAIL ON M4.06 DATED 3/1/07 |
| | |
| | M2.06: BRANCH DUCT SIZES FOR OUTSIDE AIR AND EXHAUST |
| | FROM OAR-5 AND EAR-4A & 4B DO NOT MATCH SIZES ON RISER |
| | DETAIL AT PAGES M4.06 AND M4.07 DATED 3/1/07 |
| | |
| | M2.06A: SEF-LR1 ON EXHAUST FAN SCHEDULE, PG M6.02 DATED |
| | 10/5/06, SHOWS 1400 CFM. RISER DETAIL ON M4.06 SHOWS |
| | 2100 CFM, BUT SHOWS 6 INTAKES FOR A TOTAL OF 4200 CFM. |
| | OA-G5 SHOWS A 26X8 DUCT FEEDING OAR-5, RISER DIAGRAM ON |
| | M4.07 DATED 3/1/07 SHOWS A 20X12 FEEDING THE RISER. |
| | RISER BRANCH DUCTS ARE ALSO IN CONFLICT WITH THE |
| | PREVIOUSLY MENTIONED RISER DETAILS. |
| | |
| | M2.08: BRANCH DUCTS NOT SIZED PER RISER DETAIL (SEE |
| | ABOVE COMMENTS). |
| | POOL EQUIPMENT ROOM: LOUVER CALCULATIONS DO NOT |
| | CORRESPOND WITH THE METHOD USED FOR COMBUSTION AIR. ONE |
| | OPENING COMMUNICATING DIRECTLY TO THE OUTDOORS SHOULD |
| | BE DESIGNED PER FBC,FG 304.3.2(2A). PLANS SHOW TWO |
| | 40X40 GRILLS IN ROOM FOR COMBUSTION. IF TWO OPENINGS |
| | ARE TO BE USED, EACH OPENING SHALL HAVE AN INDEPENDENT |
| | DUCT COMMUNICATING DIRECTLY WITH THE OUTDOORS PER |
| | FBC,FG 304.7(4). PLEASE CLARIFY METHOD TO BE USED AND |
| | ENSURE DESIGN IS IN COMPLIANCE WITH ALL RELEVANT |
| | PORTIONS OF FBC,FG 304. |
| | |
| | M2.10: OK |
| | |
| | M2.14A: OK |
| | |
| | M 5.04: FLAMEBAR/DAMPER ASSEMBLY DETAIL IS NOT LEGIBLE. |
| | PLEASE CORRECT AND RESUBMIT PER FBC 106.1.1. |
| | |