2007-03-26 14:46:09SOME PAGES APPROVED, OTHERS DENIED AS LISTED BELOW:
  
 M1.01A: SEF-LR2 ON EXHAUST FAN SCHEDULE, M6.02 DATED
 10/5/06, SHOWS 4200 CFM. RISER DIAGRAM SHOWS 1400 CFM,
 BRANCH SIZES ON THIS PAGE DO NOT MATCH SIZES ON RISER
 DETAIL ON M4.06 DATED 3/1/07
  
 M2.06: BRANCH DUCT SIZES FOR OUTSIDE AIR AND EXHAUST
 FROM OAR-5 AND EAR-4A & 4B DO NOT MATCH SIZES ON RISER
 DETAIL AT PAGES M4.06 AND M4.07 DATED 3/1/07
  
 M2.06A: SEF-LR1 ON EXHAUST FAN SCHEDULE, PG M6.02 DATED
 10/5/06, SHOWS 1400 CFM. RISER DETAIL ON M4.06 SHOWS
 2100 CFM, BUT SHOWS 6 INTAKES FOR A TOTAL OF 4200 CFM.
 OA-G5 SHOWS A 26X8 DUCT FEEDING OAR-5, RISER DIAGRAM ON
 M4.07 DATED 3/1/07 SHOWS A 20X12 FEEDING THE RISER.
 RISER BRANCH DUCTS ARE ALSO IN CONFLICT WITH THE
 PREVIOUSLY MENTIONED RISER DETAILS.
  
 M2.08: BRANCH DUCTS NOT SIZED PER RISER DETAIL (SEE
 ABOVE COMMENTS).
 POOL EQUIPMENT ROOM: LOUVER CALCULATIONS DO NOT
 CORRESPOND WITH THE METHOD USED FOR COMBUSTION AIR. ONE
 OPENING COMMUNICATING DIRECTLY TO THE OUTDOORS SHOULD
 BE DESIGNED PER FBC,FG 304.3.2(2A). PLANS SHOW TWO
 40X40 GRILLS IN ROOM FOR COMBUSTION. IF TWO OPENINGS
 ARE TO BE USED, EACH OPENING SHALL HAVE AN INDEPENDENT
 DUCT COMMUNICATING DIRECTLY WITH THE OUTDOORS PER
 FBC,FG 304.7(4). PLEASE CLARIFY METHOD TO BE USED AND
 ENSURE DESIGN IS IN COMPLIANCE WITH ALL RELEVANT
 PORTIONS OF FBC,FG 304.
  
 M2.10: OK
  
 M2.14A: OK
  
 M 5.04: FLAMEBAR/DAMPER ASSEMBLY DETAIL IS NOT LEGIBLE.
 PLEASE CORRECT AND RESUBMIT PER FBC 106.1.1.
  