Date Text
2005-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 DESIGN MANUAL NO 101/0
 CITY CODE
  
 A. FROM PREVIOUS REVIEWS: COMMENT NUMBER
 TO REMAIN THE SAME TO AVOID CONFUSION.
  
 2. SHT A1-8 SHOW THE LOCATIONS FOR THE
 SECONDARY DRAINS PER SECTION 1107 AND
 ALL SUBSECTIONS. SHT A1.9 ALSO. THE
 INNER ROOF DRAINS THAT CAN NOT TRANSFER
 TO THE OUTER DRAINS THAT HAVE SECONDARY
 ROOF DRAINS SHALL HAVE SECONDARY ROOF
 DRAINS.
 18. SUBMIT CALCULATIONS SHOWING
 COMPLIANCE WITH SECTIONS
 11-4.26.3(2)(3)(4). CALCULATIONS SHALL
 BE SIGNED, SEALED, AND DATED, AND THE
 TITLE BLOCK SHALL INCLUDE THE PRINTED
 NAME AND LICENSE NUMBER OF THE ENGINEER
 SEALING THE DOCUMENT, AND THE
 CERTIFICATE OF AUTHROIZATION NUMBER OF
 THE ENGINEERING BUSINESS ON EACH SHEET.
 FAC 61G15-23.002(1)(2) & FS 471.025. NOT
 ALL INFORMATION REQUIRED IS ON EACH
 SHEET.
 25. SHT P2-10 INDICATE LOCATIONS FOR
 SECONDARY DRAINS/SCUPPERS FOR DECK AREA
 AROUND THE POOL. SECTION 1107. - THIS IS
 FOR THE ROOF DRAINS THAT CAN NOT
 TRANSFER TO THE OUTER DRAIN LOCATIONS
 WITH SCUPPERS, OR HAVE GUARD RAILS THAT
 LET THE DECK AREA DRAIN.
 33. SHT P3-15 THE FOLLOWING INFORMATION
 IS REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - SOME LENGTHS FROM THE
 METER TO THE FIRST RISER AFTER THE SLEVE
 STILL ARE NOT SHOWN. - ALSO THE NEW
 ISOMETRIC IS ONLY SHOWING 1 POOL HEATER,
 AND THE BTUS ONLY ADD UP TO 2,281,000,
 BUT THE NOTE STILL INDICATES A TOTAL OF
 4,550,000 BTUS. PLEASE CLARIFY. PLEASE
 CORRELATE ISOMETRIC WITH TOTAL BTUS
 INDICATED ON NOTES.
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 CODE. NO RESPONSE NOTED FOR THE
 FIREPLACE. - ALSO CUT SHEET FOR BOILER
 NOT SUBMITTED.
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 SECTIONS 502 THRU
 506. RESPONSE NOTED, BUT NO DETAIL FOR
 THE FIREPLACE HAS BEEN SUBMITTED.
 H. SUBMIT MANUF. SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, AND THE FBC-2001 FUEL
 GAS CODE SECTION 402.2. RESPONSE NOTED,
 BUT NO SUBMITTAL FOR THE BOILER FOUND IN
 SUBMITTALS, AND THE FIREPLACE SHOW NO
 LISTING FROM A RECOGNIZED TESTING
 AGENCY.
 7B. SHT P2-14 CALCULATIONS FOR ROOF
 DRAIN AREAS ADJACENT TO THE UPPER ROOFS
 OF THE MECHANICAL ROOM, STAIRWAYS, &
 ELEVATORS ARE NOT SHOWN AS BEING ADDED
 TO THE SF FOR THE SIZING OF PRIMARY ROOF
 DRAINS. PLEASE CLARIFY. SECTIONS 1104 &
 1107. RESPONSE NOTES ADDED CALCULATIONS
 ON SHEETS P2-14 & P2-15. NO P2-15 SHEETS
 WERE SUBMITTED. PLEASE CLARIFY.
 ***************NEW COMMENTS*************
 1C. SHT A2.3 DOOR SHALL NOT OPEN INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE.
 SECTION 11-4.22.2
 2C. SHTS A0-7 & A2-3 A DRINKING FOUNTAIN
 IS REQUIRED PER TABLE 403.1.
 3C. SHT A2-11B SINK SHALL BE COMPLIANT
 WITH SECTION 11-4.24 AND "ALL
 SUBSECTIONS". PLEASE PROVIDE A DETAIL.
  