| 2005-07-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | DESIGN MANUAL NO 101/0 |
| | CITY CODE |
| | |
| | A. FROM PREVIOUS REVIEWS: COMMENT NUMBER |
| | TO REMAIN THE SAME TO AVOID CONFUSION. |
| | |
| | 2. SHT A1-8 SHOW THE LOCATIONS FOR THE |
| | SECONDARY DRAINS PER SECTION 1107 AND |
| | ALL SUBSECTIONS. SHT A1.9 ALSO. THE |
| | INNER ROOF DRAINS THAT CAN NOT TRANSFER |
| | TO THE OUTER DRAINS THAT HAVE SECONDARY |
| | ROOF DRAINS SHALL HAVE SECONDARY ROOF |
| | DRAINS. |
| | 18. SUBMIT CALCULATIONS SHOWING |
| | COMPLIANCE WITH SECTIONS |
| | 11-4.26.3(2)(3)(4). CALCULATIONS SHALL |
| | BE SIGNED, SEALED, AND DATED, AND THE |
| | TITLE BLOCK SHALL INCLUDE THE PRINTED |
| | NAME AND LICENSE NUMBER OF THE ENGINEER |
| | SEALING THE DOCUMENT, AND THE |
| | CERTIFICATE OF AUTHROIZATION NUMBER OF |
| | THE ENGINEERING BUSINESS ON EACH SHEET. |
| | FAC 61G15-23.002(1)(2) & FS 471.025. NOT |
| | ALL INFORMATION REQUIRED IS ON EACH |
| | SHEET. |
| | 25. SHT P2-10 INDICATE LOCATIONS FOR |
| | SECONDARY DRAINS/SCUPPERS FOR DECK AREA |
| | AROUND THE POOL. SECTION 1107. - THIS IS |
| | FOR THE ROOF DRAINS THAT CAN NOT |
| | TRANSFER TO THE OUTER DRAIN LOCATIONS |
| | WITH SCUPPERS, OR HAVE GUARD RAILS THAT |
| | LET THE DECK AREA DRAIN. |
| | 33. SHT P3-15 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - SOME LENGTHS FROM THE |
| | METER TO THE FIRST RISER AFTER THE SLEVE |
| | STILL ARE NOT SHOWN. - ALSO THE NEW |
| | ISOMETRIC IS ONLY SHOWING 1 POOL HEATER, |
| | AND THE BTUS ONLY ADD UP TO 2,281,000, |
| | BUT THE NOTE STILL INDICATES A TOTAL OF |
| | 4,550,000 BTUS. PLEASE CLARIFY. PLEASE |
| | CORRELATE ISOMETRIC WITH TOTAL BTUS |
| | INDICATED ON NOTES. |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | CODE. NO RESPONSE NOTED FOR THE |
| | FIREPLACE. - ALSO CUT SHEET FOR BOILER |
| | NOT SUBMITTED. |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 SECTIONS 502 THRU |
| | 506. RESPONSE NOTED, BUT NO DETAIL FOR |
| | THE FIREPLACE HAS BEEN SUBMITTED. |
| | H. SUBMIT MANUF. SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, AND THE FBC-2001 FUEL |
| | GAS CODE SECTION 402.2. RESPONSE NOTED, |
| | BUT NO SUBMITTAL FOR THE BOILER FOUND IN |
| | SUBMITTALS, AND THE FIREPLACE SHOW NO |
| | LISTING FROM A RECOGNIZED TESTING |
| | AGENCY. |
| | 7B. SHT P2-14 CALCULATIONS FOR ROOF |
| | DRAIN AREAS ADJACENT TO THE UPPER ROOFS |
| | OF THE MECHANICAL ROOM, STAIRWAYS, & |
| | ELEVATORS ARE NOT SHOWN AS BEING ADDED |
| | TO THE SF FOR THE SIZING OF PRIMARY ROOF |
| | DRAINS. PLEASE CLARIFY. SECTIONS 1104 & |
| | 1107. RESPONSE NOTES ADDED CALCULATIONS |
| | ON SHEETS P2-14 & P2-15. NO P2-15 SHEETS |
| | WERE SUBMITTED. PLEASE CLARIFY. |
| | ***************NEW COMMENTS************* |
| | 1C. SHT A2.3 DOOR SHALL NOT OPEN INTO |
| | THE CLEAR FLOOR SPACE OF ANY FIXTURE. |
| | SECTION 11-4.22.2 |
| | 2C. SHTS A0-7 & A2-3 A DRINKING FOUNTAIN |
| | IS REQUIRED PER TABLE 403.1. |
| | 3C. SHT A2-11B SINK SHALL BE COMPLIANT |
| | WITH SECTION 11-4.24 AND "ALL |
| | SUBSECTIONS". PLEASE PROVIDE A DETAIL. |
| | |
| | REVIEW BY KEN STEVENS |