Text |
| 2005-07-08 00:00:00 | ******DENIED****** |
| | |
| | 1) 1) THE EXIT SIGN ON SHEET AO-3 STILL |
| | APPEARS TO BE TOO FAR FROM THE EXIT |
| | DOOR. |
| | |
| | 2) THE TURN AROUND ILLUSTRATES 52' FROM |
| | THE CENTER TO THE OUTSIDE OF THE LANE. |
| | IT WOULD APPEAR THAT THIS MEASUREMENT |
| | DOES NOT COMPLY WITH NFPA-1. PLEASE |
| | CLARIFY. |
| | |
| | 3) NEW FIRE ALARM SYSTEM MONITORING |
| | SHALL BE CERTIFIED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 4) FIRE ALARM SYSTEMS IN HIGHRISE |
| | STRUCTURES SHALL MEET THE NFPA-72 |
| | REQUIREMENT FOR SURVIVABILITY. |
| | |
| | 5) IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, SMOKE DUCT DETECTORS WHERE |
| | PROVIDED SHALL BE WIRED INTO THE FIRE |
| | ALARM SYSTEM TO INITIATE A GENERAL FIRE |
| | ALARM WHEN ACTIVATED. |
| | |
| | 6) IN ADDITION TO THE FIRE SPRINKLER |
| | DETAIL PROVIDED FOR THE COOLING TOWER, |
| | COMPLIANCE WITH NFPA-214 WILL BE |
| | REQUIRED. |
| | |
| | 7) THE LAST FIRE REVIEW COMMENT #6 |
| | REFERS TO THE AREA NEXT TO THE MAIN |
| | LOBBY IN REGARDS TO FIRE APPARATUS |
| | TURN-AROUND. PLEASE EXPLAIN. |
| | |
| | 8) REFERENCE HAS BEEN MADE TO REVISIONS |
| | ON SHEETS #2.02 AND #2.14 REGARDING |
| | SMOKE DETECTORS. NO REVISION CAN BE |
| | FOUND ON THE DRAWINGS OR TITLE BLOCK. |
| | |
| | |
| | MIKE WENNERGREN, A/CAPTAIN |
| | WPBFR(561) 805-6722 OR 835-2951 |