Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop E
Sequence Number 3
Notes
Date Text
2005-06-28 00:00:00******** UNSAT 3RD REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS.
 PLEASE SEE SOME NEW NOTES DUE TO CHANGES
 ON PLANS.
 PLEASE SEE SOME NEW NOTES.
  
  
 1)NOTE: PLEASE SEE NOTE #2 PREVIOUS
 REVIEW.
 PLEASE SEE MANY UNITS STILL SHOW DINING
 AREA RECEPTS ON GEN LT/RECEPTS CIRCUITS.
  
 210.11C1,210.52B1
 SOME OF THESE WERE CORRECTED.
  
 2)NOTE: PLEASE SEE NOTE # 9 FROM
 PREVIOUS REVIEW.
 PLEASE SEE SOME TRANSFORMER SHOWN ON
 RISER W/OUT GROUNDING/LINE DIAGRAM SHOWN
 FOR ATTACHMENT? TRANSFORMER DETAIL
 MENTIONS TO NEAREST GRND ELECTRODE?
 250.30,250.50 ETC.
  
 3)NOTE: PLEASE SEE #11, FEEDER SCHEDULE
 WAS UPDATED, HOWEVER F-11, F-12 IS STILL
 SHOWN? , HOWEVER SOME OF THE ELECTRICAL
 FOR WHICH THESE FED, HAVE BEEN DELETED.
  
 4)NOTE: PLEASE SEE NOTE #27 FROM FIRST
 REVIEW. CORRECTIONS WERE MADE TO PLANS
 ON SECOND REVIEWSET TO MEET FIRST
 REVIEW COMMENT, HOWEVER DESIGN CHANGES
 HAVE NOW CHANGED THE NOTE BACK TO
 PREVIOUS NOTE #27.
 PLEASE SEE THE MCB WHICH WILL BE
 REQUIRED IN EDPH WAS REMOVED.
 PLEASE SEE THE MANUAL MEANS OF DISC IS
 NOT PROVIDED WITH TRANSFER SWITCH.
 225.32,225.34. 230.72
  
 5)NOTE: PLEASE SEE NOTE #30 FROM
 PREVIOUS REVIEW. IT WAS NOTTHE
 INTENTION OF THIS OFFICE TO ADD GF
 PROTECTION TO MAINS MSBA AND MSBB. THESE
 ARE BOTH 120/208V SYSTEMS AND NOT
 277/480V. PLEASE SEE RESPONSE LETTER
 MENTIONS ADDED TO THESE. PLEASE SEE
 RESPONSE ALSO MENTIONS "EDPH DOES NOT
 EXCEED 1000'S". PLEASE SEE 230.95, THIS
 GF PROTECTION IS FOR DEVICES RATED
 1000'S OR MORE.
 PLEASE SEE EDP MENTIONS A GF MAIN BRKR.
  
 6)NOTE: PLEASE SEE NOTE #48 FROM
 PREVIOUS REVIEW, THIS WAS OK, HOWEVER
 PLEASE SEE SOME UNITS NOW DO NOT CONTAIN
 ROOM DESIGNATIONS ???
 PLEASE ADJUST.
  
 7)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW. PLEASE SEE MSBA AND MSBB IS
 NOTED AS BEING SHUNT TRIP,AND A NOTE
 WAS ADDED FOR MAIN REQUIRED ON OUTSIDE
 OF EQUIIPMENT, HOWEVER PLEASE SEE
 EQUIPMENT PANEL SCHEDULE WAS NOTE
 CHANGED TO INDICATE MCB? ONLY MENTIONS
 SHUNT TRIP?
 230.76,230.79 ETC.
 PLEASE ALSO SEE RISER "KEYNOTES" STILL
 MENTIONS ALL MAINS TO HAVE SHUNT TRIPS
 IN FIRE COMMAND ROOM, HOWEVER PLANS DO
 NOT REFLECT THIS. MSBE, ALSO FIRE COMM
 RM, AND RM LAYOUT.
  
 8)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL. THIS IS ONLY A NOTE
 GIVEN AT THIS TIME. THIS IS NOTED PER
 STATE STATUES.
  
  
 PLEASE SEE THE FOLLOWING TWO NOTES;
 THESE ARE NEW NOTES FOR ITEMS NOT NOTED
 IN EITHER PREVIOUS REVIEWS. PLAN REVIEW
 WAS NOT AWARE OF THESE REQUIREMENTS AT
 THE PREVIOUS REVIEW TIMES.
  
 1)NOTE: PLEASE SEE 620.23,24 FOR
 CIRCUITING OF LTS AND RECEPTS ON
 ELEVATOR MACHINE RMS.
  
 2)NOTE: PLEASE SEE EGRESS AREAS IN
 COMMON AREA HALLWAYS AND STAIRWELLS WILL
 REQUIRE ALL EM LT CIRCUITS TO BE
 ALTERNATING. THIS REQUIREMENT
 ALLEAVIATES THE AREA(S) BEING LEFT IN
 TOTAL DARKNESS AT THE SWICTH OF BRKR OR
 TRIP OF A SINGLE BRKR/OCP DEVICE.
 LS NFPA-101 7-9
  
  
 PLEASE SEE TWO NEW NOTES MAY BE ABLE TO
 BE ENCOMPASED IN A "PROVISO" BEFORE ANY
 SLAB INSPECTION.
  
 PLEASE SEE NOTES #1-8 SHOULD BE
 ADDRESSED AT THIS TIME.
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S) IN WHICH PLANS MAY BE COMING
 BACK FOR CORRECTIONS.
  
 PLEASE SEE SOME AREAS ARE REDLINED ON
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-06-27 00:00:00MEP ROLL IN ELEC FOR REV.