| Date |
Text |
| 2005-07-29 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 3/21/05: |
| | |
| | 2) 713.13 F.S. THE NOTICE OF |
| | COMMENCEMENT SUBMITTED FOR PERMIT# |
| | 04110964 DESRIBES THE WORK AS 'SITE |
| | IMPROVEMENTS....'BECAUSE THAT |
| | DESCRIPTION DOES NOT INCLUDE |
| | CONSTRUCTION OF THE NEW BUILDING, A |
| | NOTICE OF COMMENCEMENT, DESCRIBING THE |
| | PROPOSED CONSTRUCTION, WILL HAVE TO BE |
| | RECORDED. THE NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 8) PRODUCT APPROVALS. |
| | (A) GENERAL: SOME OF THE OPTIONS |
| | COVERED BY THE SUBMITTED PRODUCT |
| | APPROVALS MAY NOT BE CODE COMPLIANT IF |
| | USED FOR THIS PROJECT/LOCATION.FOR |
| | EACH PRODUCT APPROVAL, THE SHEETS SHALL |
| | BE MARKED, AS APPROPRIATE, TO IDENTIFY |
| | WHICH PRODUCT OPTIONS/MATERIALS/SIZES |
| | ARE TO BE USED AND THE DESIGN PRESSURES. |
| | THIS COMMENT WAS MADE PREVIOUSLY BUT HAS |
| | NOT BEEN ADDRESSED. |
| | (B) ROOF: THE SUBMITTED STATEWIDE |
| | PRODUCT APPROVAL COVER SHEET FL1579 DOES |
| | NOT MATCH THE SUBMITTED SARNAFIL SINGLE |
| | PLY PVC ROOF SYSTEM PRODUCT APPROVAL |
| | NOA# 02-0603.06.SARNAFIL DOES NOT HAVE |
| | A STATEWIDE PRODUCT APPROVAL FOR THIS |
| | PRODUCT AND WOULD HAVE TO SUBMIT AN |
| | APPLICATION FORM FOR LOCAL PRODUCT |
| | APPROVAL. |
| | (C) WINDOW WALLS: SUBMITTAL OF LOCAL |
| | PRODUCT APPROVAL APPLICATION FORMS FOR |
| | MIAMI WALL SYSTEMS INC. FIXED WINDOW |
| | LARGE MISSILE IMPACT SERIES 101 AND |
| | SMALL MISSILE IMPACT SERIES 101 IS |
| | NOTED, BUT THE REFERENCED PRODUCT |
| | APPROVAL NOA'S (03-0415.18 AND |
| | 05-0420.01) WERE NOT SUBMITTED FOR |
| | REVIEW.SUBMIT THREE COPIES OF THE |
| | REFERENCED MIAMI-DADE NOA'S |
| | (D) SLIDING GLASS DOORS:SUBMITTAL |
| | OF MIAMI WALL SYSTEMS INC. LETTER DATED |
| | 5/27/05 ABOUT THEIR APPLICATION FOR |
| | STATEWIDE PRODUCT APPROVAL IS NOTED. |
| | THE LETTER STATES THAT THEY EXPECT TO |
| | HAVE STATEWIDE PRODUCT APPROVAL FOR |
| | THEIR PRODUCTS BY EARLY JULY.AS OF |
| | JULY 29TH THE ONLY STATEWIDE PRODUCT |
| | APPROVAL FOR MIAMI WALL SYSTEMS INC. IS |
| | FOR THEIR S.106 HORIZONTAL SLIDER |
| | WINDOW.THE LOCAL PRODUCT APPROVAL |
| | APPLICATION FORMS SUBMITTED FOR THE |
| | SERIES 100 SLIDING GLASS DOOR REFERENCES |
| | MIAMI-DADE PRODUCT APPROVAL NOA# |
| | 04-0908.02.THE NOA SUBMITTED IS |
| | 01-0123.02 WHICH WAS REVISED BY THE |
| | ABOVE-MENTIONED NOA.SUBMIT THREE |
| | COPIES OF NOA#-0908.02 AS REFERENCED BY |
| | THE SUBMITTED LOCAL PRODUCT APPROVAL |
| | APPLICATION FORM. |
| | (E) STOREFRONT DOORS:SOME OF THE |
| | DOORS (E.G. DOORS 01,02,43,45,46,47 AND |
| | 87 WERE STATED IN THE PREVIOUS REVIEW TO |
| | BE LARGER THAN THE 6070 SIZE LIMIT OF |
| | THE FIREDOOR LLC STOREFRONT DOOR PRODUCT |
| | APPROVAL PREVIOUSLY SUBMITTED.THAT |
| | PRODUCT APPROVAL WAS NOT INCLUDED WITH |
| | THE CURRENT RE-SUBMITTAL AND NO |
| | REPLACEMENT/ALTERNATIVE WAS PROVIDED. |
| | SUBMIT A PRODUCT APPROVAL FOR THE |
| | STOREFRONT DOORS. |
| | (F) ALUMINUM PICKET RAILING SYSTEM: |
| | THE APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL TOGETHER WITH THE SUBMITTED |
| | MIAMI-DADE PRODUCT APPROVAL NOA# |
| | 01-0206.14 HAS BEEN GIVEN TO LUIS |
| | MARTINEZ (INTERIM ASSISTANT BUILDING |
| | OFFICIAL) FOR FINAL REVIEW/APPROVAL. |
| | (H) HOLLOW METAL DOORS: THE SUBMITTED |
| | CECO DOOR PRODUCTS LOCAL PRODUCT |
| | APPROVAL APPLICATION FORM DOES NOT STATE |
| | THE MANUFACTURER'S REFERENCE OR NOA# TO |
| | WHICH THE APPLICATION FORM RELATES (ITEM |
| | #1 ON THE FORM).NEITHER DOES THE FORM |
| | STATE THE TELEPHONE NO. AND E-MAIL |
| | ADDRESS OF THE MANUFACTURER'S TECHNICAL |
| | REPRESENTATIVE OR THE NAME AND E-MAIL |
| | ADDRESS OF THE THIRD PARTY QUALITY |
| | ASSURANCE ENTITY'S AUTHORIZED |
| | REPRESENTATIVE.ALSO, THERE ARE TWO |
| | DIFFERENT NOA'S (SINGLE DOOR AND DOUBLE |
| | DOOR) SO A SEPARATE LOCAL PRODUCT |
| | APPROVAL FORM IS REQUIRED FOR EACH, BUT |
| | ONLY ONE FORM WAS SUBMITTED. |
| | (I) DOOR NO. 6 (PUMP ROOM) IS SHOWN |
| | ON THE NORTH ELEVATION SHEET A4-0 AS A |
| | S.C. WOOD DOOR.THE SAME DOOR IS LISTED |
| | ON THE DOOR SCHEDULE SHEET A3-1 AS A |
| | HOLLOW METAL.AMEND THE PLANS TO |
| | CLARIFY WHICH IS CORRECT.IF IT IS NOT |
| | A HOLLOW METAL DOOR COVERED BY THE |
| | PRODUCT APPROVAL, REFERENCED IN THE |
| | ABOVE COMMENT 8(H), THEN A SEPARATE |
| | PRODUCT APPROVAL WILL BE REQUIRED. |
| | (J) SUBMIT PRODUCT APPROVALS FOR THE |
| | HORIZONTAL SLIDER WINDOWS SHOWN ON |
| | WINDOW DETAIL SHEET A3-2. |
| | (K) WHEN ALL OF THE REQUIRED PRODUCT |
| | APPROVALS HAVE BEEN COLLATED, PLEASE |
| | ENSURE THAT THEY ARE MARKED UP, AS |
| | DESCRIBED IN COMMENT 8(A) ABOVE, BEFORE |
| | RE-SUBMITTAL. |
| | |
| | 39) FBC 1015.2GUARDRAIL HEIGHTS ON |
| | BUILDING ELEVATION SHEETS A4-1, A4-3, |
| | A4-4, A4-5, A4-6 AND A4-7.THE TOP OF |
| | THE GUARDRAIL SHOWN AT 2ND FLOOR TO 5TH |
| | FLOOR PARKING GARAGE LEVELS HAS BEEN |
| | REVISED SUCH THAT IT IS NOW ONLY 24" |
| | ABOVE FINISHED FLOOR.THE REQUIRED |
| | HEIGHT IS 42" ABOVE FINISHED FLOOR. |
| | AMEND THE PLANS. |
| | |
| | 40) FBC 1015.3GUARDRAIL OPENINGS ON |
| | BUILDING ELEVATION SHEETS A4-1, A4-3, |
| | A4-4, A4-5, A4-6, A4-7 AND DETAIL |
| | 18/A8-0.THE 6"X 6" ALUMINUM GRILLE |
| | SHOWN AT LANDING LEVELWILL NOT REJECT |
| | THE PASSAGE OF A 4" SPHERE AS REQUIRED. |
| | AMEND THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 41) FBC 11-4.9.4(2)SHEET A7-0, STAIR |
| | #2 AT GROUND, 2ND AND 3RD FLOORS AND |
| | STAIR #3 AT 2ND AND 16TH FLOORS.AT THE |
| | BOTTOM OF EACH FLIGHT THE HANDRAIL SHALL |
| | CONINTUE TO SLOPE FOR A DISTANCE EQUAL |
| | TO THE WIDTH OF ONE TREAD AND THEN |
| | EXTEND HORIZONTALLY FOR ANOTHER 12".IN |
| | THIS CASE, THE TOTAL EXTENSION SHOULD BE |
| | 1'-11".ON THE ABOVE-MENTIONED PLANS, |
| | THE DIMENSION IS SHOWN AS 1'-0", 1'-9" |
| | OR 1'-10".AMEND THE PLANS. |
| | |
| | 42) FBC 1007.6.2SHEET A7-0, STAIR #2 |
| | GROUND LEVEL PLAN.PROVIDE A DIMENSION |
| | FOR THE WIDTH OF THE OPENING BETWEEN |
| | THE COLUMN AND OPPOSITE WALL AT THE |
| | RIGHT TURN BETWEEN THE FIRST RISER AND |
| | THE EXIT DISCHARGE, SO THAT IT CAN BE |
| | VERIFIED AS NOT LESS THAN THE STAIR |
| | WIDTH. |
| | |
| | 43) FBC 1007.3.1THE TOWNHOUSE STAIR |
| | RISER HEIGHTS ARE SHOWN AS 8".THE |
| | MAXIMUM RISER HEIGHT ALLOWABLE (FOR A |
| | STAIR OTHER THAN A SPIRAL STAIR) INSIDE |
| | A DWELLING UNIT IS 7-3/4".AMEND THE |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |
| | |