2005-07-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 3/21/05:
  
 2) 713.13 F.S. THE NOTICE OF
 COMMENCEMENT SUBMITTED FOR PERMIT#
 04110964 DESRIBES THE WORK AS 'SITE
 IMPROVEMENTS....'BECAUSE THAT
 DESCRIPTION DOES NOT INCLUDE
 CONSTRUCTION OF THE NEW BUILDING, A
 NOTICE OF COMMENCEMENT, DESCRIBING THE
 PROPOSED CONSTRUCTION, WILL HAVE TO BE
 RECORDED. THE NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 8) PRODUCT APPROVALS.
 (A) GENERAL: SOME OF THE OPTIONS
 COVERED BY THE SUBMITTED PRODUCT
 APPROVALS MAY NOT BE CODE COMPLIANT IF
 USED FOR THIS PROJECT/LOCATION.FOR
 EACH PRODUCT APPROVAL, THE SHEETS SHALL
 BE MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED AND THE DESIGN PRESSURES.
 THIS COMMENT WAS MADE PREVIOUSLY BUT HAS
 NOT BEEN ADDRESSED.
 (B) ROOF: THE SUBMITTED STATEWIDE
 PRODUCT APPROVAL COVER SHEET FL1579 DOES
 NOT MATCH THE SUBMITTED SARNAFIL SINGLE
 PLY PVC ROOF SYSTEM PRODUCT APPROVAL
 NOA# 02-0603.06.SARNAFIL DOES NOT HAVE
 A STATEWIDE PRODUCT APPROVAL FOR THIS
 PRODUCT AND WOULD HAVE TO SUBMIT AN
 APPLICATION FORM FOR LOCAL PRODUCT
 APPROVAL.
 (C) WINDOW WALLS: SUBMITTAL OF LOCAL
 PRODUCT APPROVAL APPLICATION FORMS FOR
 MIAMI WALL SYSTEMS INC. FIXED WINDOW
 LARGE MISSILE IMPACT SERIES 101 AND
 SMALL MISSILE IMPACT SERIES 101 IS
 NOTED, BUT THE REFERENCED PRODUCT
 APPROVAL NOA'S (03-0415.18 AND
 05-0420.01) WERE NOT SUBMITTED FOR
 REVIEW.SUBMIT THREE COPIES OF THE
 REFERENCED MIAMI-DADE NOA'S
 (D) SLIDING GLASS DOORS:SUBMITTAL
 OF MIAMI WALL SYSTEMS INC. LETTER DATED
 5/27/05 ABOUT THEIR APPLICATION FOR
 STATEWIDE PRODUCT APPROVAL IS NOTED.
 THE LETTER STATES THAT THEY EXPECT TO
 HAVE STATEWIDE PRODUCT APPROVAL FOR
 THEIR PRODUCTS BY EARLY JULY.AS OF
 JULY 29TH THE ONLY STATEWIDE PRODUCT
 APPROVAL FOR MIAMI WALL SYSTEMS INC. IS
 FOR THEIR S.106 HORIZONTAL SLIDER
 WINDOW.THE LOCAL PRODUCT APPROVAL
 APPLICATION FORMS SUBMITTED FOR THE
 SERIES 100 SLIDING GLASS DOOR REFERENCES
 MIAMI-DADE PRODUCT APPROVAL NOA#
 04-0908.02.THE NOA SUBMITTED IS
 01-0123.02 WHICH WAS REVISED BY THE
 ABOVE-MENTIONED NOA.SUBMIT THREE
 COPIES OF NOA#-0908.02 AS REFERENCED BY
 THE SUBMITTED LOCAL PRODUCT APPROVAL
 APPLICATION FORM.
 (E) STOREFRONT DOORS:SOME OF THE
 DOORS (E.G. DOORS 01,02,43,45,46,47 AND
 87 WERE STATED IN THE PREVIOUS REVIEW TO
 BE LARGER THAN THE 6070 SIZE LIMIT OF
 THE FIREDOOR LLC STOREFRONT DOOR PRODUCT
 APPROVAL PREVIOUSLY SUBMITTED.THAT
 PRODUCT APPROVAL WAS NOT INCLUDED WITH
 THE CURRENT RE-SUBMITTAL AND NO
 REPLACEMENT/ALTERNATIVE WAS PROVIDED.
 SUBMIT A PRODUCT APPROVAL FOR THE
 STOREFRONT DOORS.
 (F) ALUMINUM PICKET RAILING SYSTEM:
 THE APPLICATION FOR LOCAL PRODUCT
 APPROVAL TOGETHER WITH THE SUBMITTED
 MIAMI-DADE PRODUCT APPROVAL NOA#
 01-0206.14 HAS BEEN GIVEN TO LUIS
 MARTINEZ (INTERIM ASSISTANT BUILDING
 OFFICIAL) FOR FINAL REVIEW/APPROVAL.
 (H) HOLLOW METAL DOORS: THE SUBMITTED
 CECO DOOR PRODUCTS LOCAL PRODUCT
 APPROVAL APPLICATION FORM DOES NOT STATE
 THE MANUFACTURER'S REFERENCE OR NOA# TO
 WHICH THE APPLICATION FORM RELATES (ITEM
 #1 ON THE FORM).NEITHER DOES THE FORM
 STATE THE TELEPHONE NO. AND E-MAIL
 ADDRESS OF THE MANUFACTURER'S TECHNICAL
 REPRESENTATIVE OR THE NAME AND E-MAIL
 ADDRESS OF THE THIRD PARTY QUALITY
 ASSURANCE ENTITY'S AUTHORIZED
 REPRESENTATIVE.ALSO, THERE ARE TWO
 DIFFERENT NOA'S (SINGLE DOOR AND DOUBLE
 DOOR) SO A SEPARATE LOCAL PRODUCT
 APPROVAL FORM IS REQUIRED FOR EACH, BUT
 ONLY ONE FORM WAS SUBMITTED.
 (I) DOOR NO. 6 (PUMP ROOM) IS SHOWN
 ON THE NORTH ELEVATION SHEET A4-0 AS A
 S.C. WOOD DOOR.THE SAME DOOR IS LISTED
 ON THE DOOR SCHEDULE SHEET A3-1 AS A
 HOLLOW METAL.AMEND THE PLANS TO
 CLARIFY WHICH IS CORRECT.IF IT IS NOT
 A HOLLOW METAL DOOR COVERED BY THE
 PRODUCT APPROVAL, REFERENCED IN THE
 ABOVE COMMENT 8(H), THEN A SEPARATE
 PRODUCT APPROVAL WILL BE REQUIRED.
 (J) SUBMIT PRODUCT APPROVALS FOR THE
 HORIZONTAL SLIDER WINDOWS SHOWN ON
 WINDOW DETAIL SHEET A3-2.
 (K) WHEN ALL OF THE REQUIRED PRODUCT
 APPROVALS HAVE BEEN COLLATED, PLEASE
 ENSURE THAT THEY ARE MARKED UP, AS
 DESCRIBED IN COMMENT 8(A) ABOVE, BEFORE
 RE-SUBMITTAL.
  
 39) FBC 1015.2GUARDRAIL HEIGHTS ON
 BUILDING ELEVATION SHEETS A4-1, A4-3,
 A4-4, A4-5, A4-6 AND A4-7.THE TOP OF
 THE GUARDRAIL SHOWN AT 2ND FLOOR TO 5TH
 FLOOR PARKING GARAGE LEVELS HAS BEEN
 REVISED SUCH THAT IT IS NOW ONLY 24"
 ABOVE FINISHED FLOOR.THE REQUIRED
 HEIGHT IS 42" ABOVE FINISHED FLOOR.
 AMEND THE PLANS.
  
 40) FBC 1015.3GUARDRAIL OPENINGS ON
 BUILDING ELEVATION SHEETS A4-1, A4-3,
 A4-4, A4-5, A4-6, A4-7 AND DETAIL
 18/A8-0.THE 6"X 6" ALUMINUM GRILLE
 SHOWN AT LANDING LEVELWILL NOT REJECT
 THE PASSAGE OF A 4" SPHERE AS REQUIRED.
 AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 41) FBC 11-4.9.4(2)SHEET A7-0, STAIR
 #2 AT GROUND, 2ND AND 3RD FLOORS AND
 STAIR #3 AT 2ND AND 16TH FLOORS.AT THE
 BOTTOM OF EACH FLIGHT THE HANDRAIL SHALL
 CONINTUE TO SLOPE FOR A DISTANCE EQUAL
 TO THE WIDTH OF ONE TREAD AND THEN
 EXTEND HORIZONTALLY FOR ANOTHER 12".IN
 THIS CASE, THE TOTAL EXTENSION SHOULD BE
 1'-11".ON THE ABOVE-MENTIONED PLANS,
 THE DIMENSION IS SHOWN AS 1'-0", 1'-9"
 OR 1'-10".AMEND THE PLANS.
  
 42) FBC 1007.6.2SHEET A7-0, STAIR #2
 GROUND LEVEL PLAN.PROVIDE A DIMENSION
 FOR THE WIDTH OF THE OPENING BETWEEN
 THE COLUMN AND OPPOSITE WALL AT THE
 RIGHT TURN BETWEEN THE FIRST RISER AND
 THE EXIT DISCHARGE, SO THAT IT CAN BE
 VERIFIED AS NOT LESS THAN THE STAIR
 WIDTH.
  
 43) FBC 1007.3.1THE TOWNHOUSE STAIR
 RISER HEIGHTS ARE SHOWN AS 8".THE
 MAXIMUM RISER HEIGHT ALLOWABLE (FOR A
 STAIR OTHER THAN A SPIRAL STAIR) INSIDE
 A DWELLING UNIT IS 7-3/4".AMEND THE
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  