2007-01-18 15:43:57-----------------------DENIED-----------------------
  
 1) M2.08 FBC,FG SECTION 304.3.2 (METHOD 1B) IS SHOWN
 FOR PROVIDING COMBUSTION AIR TO THE POOL EQUIPMENT
 ROOM. THIS METHOD IS ONLY APPLICABLE WHEN COMMUNICATING
 DIRECTLY WITH THE OUTDOORS. THE LOUVERS AS SHOWN ON
 REVISED PLAN ARE COMMUNICATING WITH AN ENCLOSED PARKING
 GARAGE. THIS IS NOT OUTDOORS. THESE OPENINGS MUST
 COMMUNICATE DIRECTLY WITH THE OUTDOORS TO COMPLY WITH
 THIS METHOD.
  
 2) M5.02 VERTICAL HEAT PUMP UNIT DETAIL: USE OF THE
 EMERGENCY DRAIN PAN UNDER THE WATER HEATER IS NOT IN
 COMPLIANCE WITH THE AUXILIARY/SECONDARY DRAIN
 REQUIREMENTS OF FBC,M 307.2.3 OR 307.2.4.
  