| Notes |
| Date |
Text |
| 2006-11-21 17:14:02 | ---------------PROVISO---------------- | | | EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND | | | INTO OR PASS THROUGH PLENUMS PER FBC,M 601.3. | | | THERE IS NO PROVISION IN THE CODE FOR AN "AIR TIGHT | | | SEAL" AROUND EXHAUST DUCTS IN PLENUMS. THIS SYSTEM WILL | | | NEED TO BE SUBMITTED TO THE BUILDING OFFICIAL FOR | | | APPROVAL UNDER FBC SEC.104.11 ALTERNATIVE MATERIALS, | | | DESIGN AND METHODS. |
|