| Permit Number |
04110961 |
|
| Review Stop |
M |
| Sequence Number |
21 |
|
| Notes |
| Date |
Text |
| 2006-11-13 19:21:20 | ----------------DENIED-------------------- | | | PG M3.13 SUPPLY AIR DUCT SIZE IS MISSING - UNIT 'C' | | | LEAVING THE AC CLOSET. PLEASE SHOW DUCT SIZE AS BEING | | | LARGE ENOUGH TO CARRY THE AIR FOR BOTH THE 14X8 AND 8X8 | | | BRANCHES WHICH ARE FED BY THIS DUCT. | | | | | | PG M3.15 UNIT P2 BATH AND DRYER EXHAUST ARE ROUTED | | | THROUGH A RETURN AIR PLENUM. EXHAUST DUCTS UNDER | | | POSITIVE PRESSURE SHALL NOT EXTEND INTO OR PASS THROUGH | | | PLENUMS PER FBC,M 601.3. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|