2006-11-13 19:21:20----------------DENIED--------------------
 PG M3.13 SUPPLY AIR DUCT SIZE IS MISSING - UNIT 'C'
 LEAVING THE AC CLOSET. PLEASE SHOW DUCT SIZE AS BEING
 LARGE ENOUGH TO CARRY THE AIR FOR BOTH THE 14X8 AND 8X8
 BRANCHES WHICH ARE FED BY THIS DUCT.
  
 PG M3.15 UNIT P2 BATH AND DRYER EXHAUST ARE ROUTED
 THROUGH A RETURN AIR PLENUM. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT EXTEND INTO OR PASS THROUGH
 PLENUMS PER FBC,M 601.3.
  