| Plan Review Notes For Permit 04110961 |
| Permit Number |
04110961 |
|
| Review Stop |
M |
| Sequence Number |
20 |
|
| Notes |
| Date |
Text |
| 2006-11-13 19:13:00 | ONLY PAGES 3.12 AND 3.14 PASSED THIS REVIEW WITH THE | | | FOLLOWING PROVISO: | | | | | | ----------------PROVISO------------------ | | | M3.12 THROUGH 3.14 BEDROOM AIR TRANSFERS ARE NOT | | | DESIGNED TO MEET THE EXCEPTIONS FOR BALANCED RETURN. | | | PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE | | | RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO | | | 0.01INCH WC OR LESS PER FBC,M 601.4.A FIELD TEST WILL | | | BE REQUIRED AT FINAL INSPECTION TO VERIFY BALANCED | | | RETURN HAS BEEN ACHIEVED WITH THESE DESIGNS UNLESS THEY | | | ARE REDESIGNED TO MEET AT LEAST ONE OF THE EXCEPTIONS | | | UNDER THIS SECTION. |
|