| 2005-02-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | DESIGN MANUAL NO 101/0 |
| | CITY CODE |
| | |
| | A) FROM PREVIOUS REVIEW: THE COMMENT |
| | NUMBER WILL STAY THE SAME TO AVOID |
| | CONFUSION. |
| | 2) SHT A1-8 SHOW THE LOCATIONS FOR THE |
| | SECONDARY DRAINS PER SECTION 1107 AND |
| | ALL SUBSECTIONS. NO RESPONSE NOTED |
| | 3) SHTS A1-9, A1.13, & A1-14 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS PER SECTIONS 1106 & 1107 AND |
| | ALL SUBSECTIONS. SHOW SF FOR EACH AREA, |
| | 1/2 AREA OF ALL VERTICAL WALLS, |
| | INCLUDING PARAPETS, AND ALL AREAS OF |
| | ROOFS DRAININ ON TO THE ROOF AREA FROM |
| | ABOVE. RESPONSE NOTED, BUT THE ROOF |
| | AREAS FROM THE MECHANICAL ROOM, STAIRWAY |
| | ROOFS, AND ELEVATOR ROOFS ARE NOT SHOWN |
| | ON THE AREAS WHERE THEY DRAIN. |
| | 4) ALL UNITS SHALL BE DESIGNATED |
| | SPECIFICATION "A" OR "B" PER FHA DESIGN |
| | MANUAL PAGES 7.34 & 7.35. SHT A9-1 UNIT |
| | "I", AND SHT P-9-7 UNITS "P1", "P2", & |
| | "P3" DO NOT INDICATE SPECIFICATION "A" |
| | OR "B". |
| | 10) SUBMIT CALCULATIONS FOR MIMIMUM |
| | FACILITIES FOR THE FIXTURE COUNT PER |
| | TABLE 403.1. SHOW THE SF FOR EACH AREA |
| | OF THE COMMON AREA. NOT ALL AREAS OF THE |
| | COMMON AREA ARE SHOWING THE SF AND THE |
| | CALCULATIONS WERE NOT FOUND. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 11) SHT A2-11 MENS AND WOMENS TOILET |
| | ROOM. THE ACCESSIBLE STALL SHALL COMPLY |
| | WITH THE CONFIGURATION SHOWN ON FIG. "E" |
| | TOILET STALL NEW CONSTRUCTION. STALL |
| | SHALL HAVE A LAV LOCATED IN IT. "IF |
| | TOILET ROOMS ARE PROVIDED, THEN EACH |
| | PUBLIC AND COMMON USE TOILET ROOM SHALL |
| | COMPLY WITH 11-4.22. (SECTIONS |
| | 11-4.1.3(11), 11-4.22.4, 11-4.17.3, AND |
| | FIG. 30E PAGE 11.77. |
| | 12) SHT A2-11 SHOW CLEAR FLOOR SPACE FOR |
| | W/C'S, URINAL, LAVS, AND DRINKING |
| | FOUNTAIN PER SECTIONS 11-4.15, 11-4.16, |
| | 11-4.18, & 11-4.19. RESPONSE NOTED, BUT |
| | NO CLEAR FLOOR SPACE SHOWN. |
| | 13) THE FLOOR PLAN FOR THE 6TH FLOOR IS |
| | NOT COMPLETE. ONLY ONE SECTION OF THE |
| | FLOOR IS SUBMITTED. SECTION 104.2.1. |
| | RESPONSE NOTED, BUT A 1/4" SCALE SHOWING |
| | CLEAR FLOOR SPACE FOR THE AMMENITIES IS |
| | NOT FOUND. PLEASE CLARIFY. |
| | 17) SHT A5-7 PLANS SHALL BE ROUTED TO |
| | THE PBC HEALTH UNIT FOR REVIEW. (SEE THE |
| | BAR) SECTION 101.4.7. RESPONSE NOTED, |
| | BUT THE PLANS SHALL BE STAMPED PRIOR TO |
| | RESUBMITTING TO WPB FOR PLAN REVIEW. |
| | 18) SUBMIT CALCULATIONS SHOWING |
| | COMPLIANCE WITH SECTIONS |
| | 11-4.26.3(2)(3)(4). RESPONSE NOTED, BUT |
| | CALCULATIONS SHALL BE |
| | SIGNED/SEALED/DATED AND THE TITLE BLOCK |
| | SHALL INCLUDE THE PRINTED NAME AND |
| | LICENSE NUMBER OF THE ENGINEER SEALING |
| | THE DOCUMENT, AND THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. |
| | FAC 61G15-23.002(1)(2) & FS 471.025 |
| | 25) SHT P2-10 INDICATE LOCATIONS FOR |
| | SECONDARY DRAINS/SCUPPERS FOR DECK AREA |
| | AROUND THE POOL. SECTION 1107. RESPONSE |
| | NOTED, BUT THESE ARE NOT SHOWN BY THE |
| | ARCHITECT ON SHT A1-9 (I WILL MAKE NEW |
| | COMMENT FOR SHT A1-9). |
| | 26) SHT P3.09 ALL UNITS, KEY NOTES #4. |
| | CONDENSATE SHALL DRAIN SEPARATELY OUT OF |
| | THE BUILDING TO THE STORM LINES, CATCH |
| | BASIN, OR APPROVED DRYWELL, NOT INTO THE |
| | SANITARY SYSTEM. CITY CODE SECTION |
| | 90-125(B)(5). RESPONSE NOTED, BUT THE |
| | P/T, PAN DRAIN AND THE THERMAL EXPANSION |
| | VALVE DISCHARGE SHALL DRAIN TO SANITARY, |
| | AND THE CONDENSATE SHALL DISCHARGE |
| | SEPARATELY TO THE PROPER DISPOSAL SITE. |
| | 33) SHT P3-13 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR THE GAS PERMIT: |
| | A) SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGHTS PER FBC-2001 |
| | FUEL GAS CODE. RESPONSE NOTED, BUT SOME |
| | LENGTHS FROM THE METER TO THE FIRST |
| | RISER AFTER THE SLEEVE ARE NOT SHOWN. |
| | ALSO 3" PIPE IS REQUIRED UP TO THE FIRST |
| | BOILER FOR THE POOL. (SEE RED LINE |
| | CORRECTIONS ON ISOMETRIC ONE SET OF |
| | PLANS). |
| | E) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE ) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. NO RESPONSE NOTED. |
| | G) SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECTS. 502 THRU 506. NO RESPONSE NOTED. |
| | H) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, AND THE FBC-2001 FUEL |
| | GAS CODE SECTION 402.2. NO RESPONSE |
| | NOTED. |
| | 34)SHT P3.13, (CHANGED TO P3.15) KEY |
| | NOTES #5. GAS APPLIANCE NOT SHOWN PLANS. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | RESPONSE NOTED, BUT IT SEEMS AS IF THE |
| | PIPING FOR THIS APPLIANCE IS ATTACHED TO |
| | THE VENT FOR THE BOILERS FOR THE POOL. |
| | PLEASE CLARIFY. |
| | 35) SHT P4.01 GENERAL NOTES #'S 5 & 6, |
| | CLARIFY WHAT KITCHEN AND LAUNDRY AND |
| | WHAT THESE ARE FOR? SECTION 104.2.1. |
| | RESPONSE NOTED, BUT WHERE ARE THE |
| | KITCHEN AND LAUNDRY REFERED TO? ARE THEY |
| | COMMON USE OR IN A UNIT? PLEASE CLARIFY. |
| | *****************NEW COMMENTS*********** |
| | 1B)SHT A9.2 UNITS "C" AND "E" CLEAR |
| | FLOOR SPACE IS REQUIRED FOR BOTH LAVS |
| | AND BOTH LAVS SHALL BE CENTERED ON THE |
| | CLEAR FLOOR SPACE 48" DIMENSION IN EACH |
| | UNIT. SPECIFICATION "A" IS FOR ALL |
| | FIXTURES. PAGE 7.35 FHA-98 DESIGN MANUAL |
| | 2B) SHT A9.3UNIT "D1" SHOW CLEAR FLOOR |
| | SPACE FOR THE SHOWER. ALL CFS FOR |
| | SHOWERS SHALL BE PARALLEL TO THE SHOWER |
| | AND FLUSH WITH THE CONTROL WALL PER PAGE |
| | 7.56 PARAGRAPH #2. BOTH LAVS SHALL SHOW |
| | THE CLEAR FLOOR SPACE AND BE CENTERED ON |
| | THE 48" DIM. OF THE CFS. SPEC. "A" |
| | 3B) SHT A9.4 UNIT "F2" BOTH LAVS TO SHOW |
| | CLEAR FLOOR SPACE & BE CENTERED ON THE |
| | 48" DIMENSION. SPECIFICATION "A" - UNIT |
| | "B" WHICH BATHROOM SHALL COMPLY? BOTH |
| | SHOW CLEAR FLOOR SPACE. SPECIFICATION |
| | "B". |
| | 4B) SHT A9.5 UNIT "H" WHICH BATHROOM |
| | SHALL COMPLY? BOTH SHOW CLEAR FLOOR |
| | SPACE. - UNIT "G' BOTH LAVS SHALL SHOW |
| | THE CLEAR FLOOR SPACE AND BE CENTERED ON |
| | THE 48" DIMENSION. SPECIFICATION "A". |
| | THE CLEAR FLOOR SPACE FOR THE SHOWER |
| | SHALL BE PARALLEL TO THE SHOWER AND BE |
| | FLUSH WITH THE CONTROL WALL. PAGE 7.56 |
| | PARAGRAPH #2 |
| | 5B) SHT P9.7 SHOWER CLEAR FLOOR SPACE |
| | SHALL BE PARALLEL AND BE FLUSH WITH THE |
| | CONTROL WALL. PAGE 7.56 PARA. #2 |
| | 6B) SHT P2.01A IS NOT INSERTED IN ORDER. |
| | AFTER P2.02. SECTION 104.2.1. |
| | 7B) SHT P2.14 CALCULATIONS FOR ROOF |
| | DRAIN AREAS ADJACENT TO THE UPPER ROOFS |
| | OF THE MECHANICAL ROOM, STAIRWAYS, & |
| | ELEVATORS ARE NOT SHOWN AS BEING ADDED |
| | TO THE SF FOR SIZING PRIMARY ROOF |
| | DRAINS. PLEASE CLARIFY. SECTIONS 1106 & |
| | 1107. |
| | 8B) SHT P2.14 ALL (25) INTERNAL ROOF |
| | AREAS HAVE NO SECONDARY ROOF DRAINS AS |
| | REQUIRED IN SECTION 1107. PLEASE CLARIFY |
| | 9B) SHT P3.13 DRAINAGE FITTINGS SHALL BE |
| | INSTALLED TO GUIDE STORM WATER IN THE |
| | DIRECTION OF FLOW. SECTION 706.3. A |
| | COUPLE FITTINGS FROM BRANCH LINES TO |
| | BLDG STORM DRAIN ARE SHOWN INCORRECTLY. |
| | 10B) SHT P3.15 GAS PIPING, IF THE 3" GAS |
| | PIPE IS WELD PIPE, THE CERTIFICATION AND |
| | PICTURE I.D. OF THE PERSON WELDING THE |
| | PIPE, AND THE WELD PROCEEDURE ARE |
| | REQUIRED AT THE TIME OF APPLICATION. |
| | PLEASE INDICATE IF THE PIPE WILL BE WELD |
| | PIPE OR THREADED PIPE. SECTION 104.2.1. |
| | 11B) SHT P3.02 BUILDING SANITARY DRAIN |
| | ISOMETRIC SHOWS 8" PIPE, REDUCING TO 6" |
| | UPSTREAM OF RISER "C", THEN INCREASING |
| | BACK TO 8" THRU DOWNSTREAM OF RISER "H", |
| | ONLY TO REDUCE TO 6". THEN INCREASING TO |
| | 8" PRIOR TO CHANGING DIRECTION ONLY TO |
| | REDUCE TO 6" THERE AFTER. PLEASE |
| | CLARIFY. PIPING SHALL NOT REDUCE IN SIZE |
| | IN THE DIRECT OF FLOW. SECTION 704.2. |
| | 12B) ALL SOVENT FITTINGS SHALL BE |
| | APPROVED BY AN APPROVED TESTING AGENCY |
| | AND WILL BE INSPECTED FOR THIS AT THE |
| | TIME OF INSTALLATION. |
| | 13B) PLANS HAVE CHANGED SO THAT |
| | INFORMATION ON ONE SHEET 1ST REVIEW IS |
| | LOCATED ON ANOTHE SHEET 2ND REVIEW. THE |
| | ORIGINAL SHEETS WERE NOT RESUBMITTED FOR |
| | COMPAIRSON SO MORE COMMENTS MAY FOLLOW. |
| | WHEN RESUBMITTING FOR THE 3RD REVIEW, |
| | SUBMIT A COPY OF ORIGINAL PLANS AND A |
| | COPY OF PLANS SUBMITTED FOR 2ND REVIEW |
| | TO HELP EXPEDITE THE REVIEW PROCESS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |