Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 2
Notes
Date Text
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 DESIGN MANUAL NO 101/0
 CITY CODE
  
 A) FROM PREVIOUS REVIEW: THE COMMENT
 NUMBER WILL STAY THE SAME TO AVOID
 CONFUSION.
 2) SHT A1-8 SHOW THE LOCATIONS FOR THE
 SECONDARY DRAINS PER SECTION 1107 AND
 ALL SUBSECTIONS. NO RESPONSE NOTED
 3) SHTS A1-9, A1.13, & A1-14 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS. SHOW SF FOR EACH AREA,
 1/2 AREA OF ALL VERTICAL WALLS,
 INCLUDING PARAPETS, AND ALL AREAS OF
 ROOFS DRAININ ON TO THE ROOF AREA FROM
 ABOVE. RESPONSE NOTED, BUT THE ROOF
 AREAS FROM THE MECHANICAL ROOM, STAIRWAY
 ROOFS, AND ELEVATOR ROOFS ARE NOT SHOWN
 ON THE AREAS WHERE THEY DRAIN.
 4) ALL UNITS SHALL BE DESIGNATED
 SPECIFICATION "A" OR "B" PER FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. SHT A9-1 UNIT
 "I", AND SHT P-9-7 UNITS "P1", "P2", &
 "P3" DO NOT INDICATE SPECIFICATION "A"
 OR "B".
 10) SUBMIT CALCULATIONS FOR MIMIMUM
 FACILITIES FOR THE FIXTURE COUNT PER
 TABLE 403.1. SHOW THE SF FOR EACH AREA
 OF THE COMMON AREA. NOT ALL AREAS OF THE
 COMMON AREA ARE SHOWING THE SF AND THE
 CALCULATIONS WERE NOT FOUND. PLEASE
 CLARIFY. SECTION 104.2.1.
 11) SHT A2-11 MENS AND WOMENS TOILET
 ROOM. THE ACCESSIBLE STALL SHALL COMPLY
 WITH THE CONFIGURATION SHOWN ON FIG. "E"
 TOILET STALL NEW CONSTRUCTION. STALL
 SHALL HAVE A LAV LOCATED IN IT. "IF
 TOILET ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE TOILET ROOM SHALL
 COMPLY WITH 11-4.22. (SECTIONS
 11-4.1.3(11), 11-4.22.4, 11-4.17.3, AND
 FIG. 30E PAGE 11.77.
 12) SHT A2-11 SHOW CLEAR FLOOR SPACE FOR
 W/C'S, URINAL, LAVS, AND DRINKING
 FOUNTAIN PER SECTIONS 11-4.15, 11-4.16,
 11-4.18, & 11-4.19. RESPONSE NOTED, BUT
 NO CLEAR FLOOR SPACE SHOWN.
 13) THE FLOOR PLAN FOR THE 6TH FLOOR IS
 NOT COMPLETE. ONLY ONE SECTION OF THE
 FLOOR IS SUBMITTED. SECTION 104.2.1.
 RESPONSE NOTED, BUT A 1/4" SCALE SHOWING
 CLEAR FLOOR SPACE FOR THE AMMENITIES IS
 NOT FOUND. PLEASE CLARIFY.
 17) SHT A5-7 PLANS SHALL BE ROUTED TO
 THE PBC HEALTH UNIT FOR REVIEW. (SEE THE
 BAR) SECTION 101.4.7. RESPONSE NOTED,
 BUT THE PLANS SHALL BE STAMPED PRIOR TO
 RESUBMITTING TO WPB FOR PLAN REVIEW.
 18) SUBMIT CALCULATIONS SHOWING
 COMPLIANCE WITH SECTIONS
 11-4.26.3(2)(3)(4). RESPONSE NOTED, BUT
 CALCULATIONS SHALL BE
 SIGNED/SEALED/DATED AND THE TITLE BLOCK
 SHALL INCLUDE THE PRINTED NAME AND
 LICENSE NUMBER OF THE ENGINEER SEALING
 THE DOCUMENT, AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
 FAC 61G15-23.002(1)(2) & FS 471.025
 25) SHT P2-10 INDICATE LOCATIONS FOR
 SECONDARY DRAINS/SCUPPERS FOR DECK AREA
 AROUND THE POOL. SECTION 1107. RESPONSE
 NOTED, BUT THESE ARE NOT SHOWN BY THE
 ARCHITECT ON SHT A1-9 (I WILL MAKE NEW
 COMMENT FOR SHT A1-9).
 26) SHT P3.09 ALL UNITS, KEY NOTES #4.
 CONDENSATE SHALL DRAIN SEPARATELY OUT OF
 THE BUILDING TO THE STORM LINES, CATCH
 BASIN, OR APPROVED DRYWELL, NOT INTO THE
 SANITARY SYSTEM. CITY CODE SECTION
 90-125(B)(5). RESPONSE NOTED, BUT THE
 P/T, PAN DRAIN AND THE THERMAL EXPANSION
 VALVE DISCHARGE SHALL DRAIN TO SANITARY,
 AND THE CONDENSATE SHALL DISCHARGE
 SEPARATELY TO THE PROPER DISPOSAL SITE.
 33) SHT P3-13 THE FOLLOWING INFORMATION
 IS REQUIRED FOR THE GAS PERMIT:
 A) SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS CODE. RESPONSE NOTED, BUT SOME
 LENGTHS FROM THE METER TO THE FIRST
 RISER AFTER THE SLEEVE ARE NOT SHOWN.
 ALSO 3" PIPE IS REQUIRED UP TO THE FIRST
 BOILER FOR THE POOL. (SEE RED LINE
 CORRECTIONS ON ISOMETRIC ONE SET OF
 PLANS).
 E) SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE ) PER FBC-2001 FUEL
 GAS CODE SECTION 304. NO RESPONSE NOTED.
 G) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECTS. 502 THRU 506. NO RESPONSE NOTED.
 H) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, AND THE FBC-2001 FUEL
 GAS CODE SECTION 402.2. NO RESPONSE
 NOTED.
 34)SHT P3.13, (CHANGED TO P3.15) KEY
 NOTES #5. GAS APPLIANCE NOT SHOWN PLANS.
 PLEASE CLARIFY. SECTION 104.2.1.
 RESPONSE NOTED, BUT IT SEEMS AS IF THE
 PIPING FOR THIS APPLIANCE IS ATTACHED TO
 THE VENT FOR THE BOILERS FOR THE POOL.
 PLEASE CLARIFY.
 35) SHT P4.01 GENERAL NOTES #'S 5 & 6,
 CLARIFY WHAT KITCHEN AND LAUNDRY AND
 WHAT THESE ARE FOR? SECTION 104.2.1.
 RESPONSE NOTED, BUT WHERE ARE THE
 KITCHEN AND LAUNDRY REFERED TO? ARE THEY
 COMMON USE OR IN A UNIT? PLEASE CLARIFY.
 *****************NEW COMMENTS***********
 1B)SHT A9.2 UNITS "C" AND "E" CLEAR
 FLOOR SPACE IS REQUIRED FOR BOTH LAVS
 AND BOTH LAVS SHALL BE CENTERED ON THE
 CLEAR FLOOR SPACE 48" DIMENSION IN EACH
 UNIT. SPECIFICATION "A" IS FOR ALL
 FIXTURES. PAGE 7.35 FHA-98 DESIGN MANUAL
 2B) SHT A9.3UNIT "D1" SHOW CLEAR FLOOR
 SPACE FOR THE SHOWER. ALL CFS FOR
 SHOWERS SHALL BE PARALLEL TO THE SHOWER
 AND FLUSH WITH THE CONTROL WALL PER PAGE
 7.56 PARAGRAPH #2. BOTH LAVS SHALL SHOW
 THE CLEAR FLOOR SPACE AND BE CENTERED ON
 THE 48" DIM. OF THE CFS. SPEC. "A"
 3B) SHT A9.4 UNIT "F2" BOTH LAVS TO SHOW
 CLEAR FLOOR SPACE & BE CENTERED ON THE
 48" DIMENSION. SPECIFICATION "A" - UNIT
 "B" WHICH BATHROOM SHALL COMPLY? BOTH
 SHOW CLEAR FLOOR SPACE. SPECIFICATION
 "B".
 4B) SHT A9.5 UNIT "H" WHICH BATHROOM
 SHALL COMPLY? BOTH SHOW CLEAR FLOOR
 SPACE. - UNIT "G' BOTH LAVS SHALL SHOW
 THE CLEAR FLOOR SPACE AND BE CENTERED ON
 THE 48" DIMENSION. SPECIFICATION "A".
 THE CLEAR FLOOR SPACE FOR THE SHOWER
 SHALL BE PARALLEL TO THE SHOWER AND BE
 FLUSH WITH THE CONTROL WALL. PAGE 7.56
 PARAGRAPH #2
 5B) SHT P9.7 SHOWER CLEAR FLOOR SPACE
 SHALL BE PARALLEL AND BE FLUSH WITH THE
 CONTROL WALL. PAGE 7.56 PARA. #2
 6B) SHT P2.01A IS NOT INSERTED IN ORDER.
 AFTER P2.02. SECTION 104.2.1.
 7B) SHT P2.14 CALCULATIONS FOR ROOF
 DRAIN AREAS ADJACENT TO THE UPPER ROOFS
 OF THE MECHANICAL ROOM, STAIRWAYS, &
 ELEVATORS ARE NOT SHOWN AS BEING ADDED
 TO THE SF FOR SIZING PRIMARY ROOF
 DRAINS. PLEASE CLARIFY. SECTIONS 1106 &
 1107.
 8B) SHT P2.14 ALL (25) INTERNAL ROOF
 AREAS HAVE NO SECONDARY ROOF DRAINS AS
 REQUIRED IN SECTION 1107. PLEASE CLARIFY
 9B) SHT P3.13 DRAINAGE FITTINGS SHALL BE
 INSTALLED TO GUIDE STORM WATER IN THE
 DIRECTION OF FLOW. SECTION 706.3. A
 COUPLE FITTINGS FROM BRANCH LINES TO
 BLDG STORM DRAIN ARE SHOWN INCORRECTLY.
 10B) SHT P3.15 GAS PIPING, IF THE 3" GAS
 PIPE IS WELD PIPE, THE CERTIFICATION AND
 PICTURE I.D. OF THE PERSON WELDING THE
 PIPE, AND THE WELD PROCEEDURE ARE
 REQUIRED AT THE TIME OF APPLICATION.
 PLEASE INDICATE IF THE PIPE WILL BE WELD
 PIPE OR THREADED PIPE. SECTION 104.2.1.
 11B) SHT P3.02 BUILDING SANITARY DRAIN
 ISOMETRIC SHOWS 8" PIPE, REDUCING TO 6"
 UPSTREAM OF RISER "C", THEN INCREASING
 BACK TO 8" THRU DOWNSTREAM OF RISER "H",
 ONLY TO REDUCE TO 6". THEN INCREASING TO
 8" PRIOR TO CHANGING DIRECTION ONLY TO
 REDUCE TO 6" THERE AFTER. PLEASE
 CLARIFY. PIPING SHALL NOT REDUCE IN SIZE
 IN THE DIRECT OF FLOW. SECTION 704.2.
 12B) ALL SOVENT FITTINGS SHALL BE
 APPROVED BY AN APPROVED TESTING AGENCY
 AND WILL BE INSPECTED FOR THIS AT THE
 TIME OF INSTALLATION.
 13B) PLANS HAVE CHANGED SO THAT
 INFORMATION ON ONE SHEET 1ST REVIEW IS
 LOCATED ON ANOTHE SHEET 2ND REVIEW. THE
 ORIGINAL SHEETS WERE NOT RESUBMITTED FOR
 COMPAIRSON SO MORE COMMENTS MAY FOLLOW.
 WHEN RESUBMITTING FOR THE 3RD REVIEW,
 SUBMIT A COPY OF ORIGINAL PLANS AND A
 COPY OF PLANS SUBMITTED FOR 2ND REVIEW
 TO HELP EXPEDITE THE REVIEW PROCESS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  