Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop M
Sequence Number 2
Notes
Date Text
2005-02-17 00:00:00DENIED:
 1.PLEASE IDENTIFY AND CORRELATE O.A.,
 EXHAUST RISERS, LOUVERS, HEATPUMPS,
 EXHUAST AND SUPPLY FANS.
  
 2.PLANS INDICATE CO SENSORS, PER 2001
 FBC(M)403.4 AND 502.10, INDICATE THE
 OPTION FOR THE CO SENSORS IN A "PUBLIC"
 GARAGE.THIS IS A PRIVATE GARAGE AND
 SHALL COMPLY WITH 2001 FBC(M) TABLE
 403.3 & 411.4.2.
  
 3.PLANS INDICATE THE INSTALLATION OF
 BOOSTER FANS ON THE DRYER EXHUAST.THIS
 WILL BE CONSIDERED ALTERNATE METHODS AND
 MATERIALS UNDER FBC CHAPTER 1 SECTION
 103.7.PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW BY THE BUILDING
 OFFICAL.
 - SUBMITTAL FOR THE DRYER.
 - PROVIDE MANUFACTURER'S APPROVAL FOR
 THE INSTALLATION OF THE BOOSTER FAN.
  
  
  