| Plan Review Notes For Permit 04110961 |
| Permit Number |
04110961 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-17 00:00:00 | DENIED: | | | 1.PLEASE IDENTIFY AND CORRELATE O.A., | | | EXHAUST RISERS, LOUVERS, HEATPUMPS, | | | EXHUAST AND SUPPLY FANS. | | | | | | 2.PLANS INDICATE CO SENSORS, PER 2001 | | | FBC(M)403.4 AND 502.10, INDICATE THE | | | OPTION FOR THE CO SENSORS IN A "PUBLIC" | | | GARAGE.THIS IS A PRIVATE GARAGE AND | | | SHALL COMPLY WITH 2001 FBC(M) TABLE | | | 403.3 & 411.4.2. | | | | | | 3.PLANS INDICATE THE INSTALLATION OF | | | BOOSTER FANS ON THE DRYER EXHUAST.THIS | | | WILL BE CONSIDERED ALTERNATE METHODS AND | | | MATERIALS UNDER FBC CHAPTER 1 SECTION | | | 103.7.PLEASE PROVIDE THE FOLLOWING | | | INFORMATION FOR REVIEW BY THE BUILDING | | | OFFICAL. | | | - SUBMITTAL FOR THE DRYER. | | | - PROVIDE MANUFACTURER'S APPROVAL FOR | | | THE INSTALLATION OF THE BOOSTER FAN. | | | | | | | | | |
|