Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-22 00:00:00************** UNSAT 2ND REVIEW *******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1, OK.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE UNIT(S)
 TH-1,D1 (SD BR#2) ALSO UNIT "G".
 PLEASE SEE CIRCUITING OF HALL/FOYER AREA
 RECEPTS SHOWN ONSMALL APPLIANCE
 CIRCUITS? THESE ARE NOT PERMITTED.D2, G,
 B ETC.
  
 3)NOTE: NOTE #3 OK, TREADMILL EQUIPMENT
 CIRCUITS TO BE SIZED AND ADJUSTED FOR
 LOAD.
  
 4)NOTE: NOTE#4 OK.
  
 5)NOTE: NOTE#5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK. PHASE II TO HAVE
 "FIRE RATED SEPARATION"DUE TO SEPARATE
 SERVICE FEEDING PHASE II.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE MSBB,
 MSBA ON E3.00
  
 9)NOTE: NOTE #9 NO, PLEASE SEE SOME
 TRANSFORMERS ARE SHOWN WITH CONNECTION
 TO BLDG GROUNDING ELECTRODE SYSTEM,
 HOWEVER MANY ARE NOT.
 REPLY MENTIONS TO SEE TRANSFORMER
 SCHEDULE, HOWEVER THESE ARE FOR THE
 SIZING OF EQUIPMENT GROUNDS AND DOES NOT
 INCDICATE ATTACHMENT POINT.
 PLEASE SEE REDLINED AREAS ON RISER.
 250.30,215.5
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11, ??, FEEDER SCHEDULE
 UPDATED. HOWEVER, PLEASE SEE EQUIPMENT
 GROUNDING CONDUCTORS HAVE NOW BEEN ADDED
 FROM METER/FPL TO FIRST MEANS OF DISC.
 PLEASE SEE 250.6,250.24, NO EQUIPMENT
 GROUNDING FROM METER.
  
 12)NOTE: NOTE #12 NO, PLEASE A-SHEET
 INDICATES 307 UNITS, YET SCHEDULEON
 ELECTRICAL METER CENT SUMMARY ADDS UP TO
 312? PLEASE CLARIFY,
  
 13)NOTE : NOTE# 13 N, PLEASE SEE SPECS
 FOR FOR PUMP ETC WERE SUBMITTED, HOWEVER
 COULD NOT FIND ANY INDICATION OF MANUAL
 MEANS OF DISCONNECT LOCATED ON OUTSIDE
 OF EQUIPMENT. PLEASE EITHER SHOW OR
 PROVIDE NOTE. 230.76,230.79,110.27
  
 14)NOTE: NOTE #14 NO, PLEASE SEE RISER
 AND CONDUCTORS SHOWN FOR GDP;(F-9) TO
 EDPH. PLEASE CORRELATE GDP AND RISER
 FEEDER SCHEDULE.
 215.5,240.4
  
 15)NOTE: NOTE #15 OK,HOWEVER, PLEASE
 SEE RATING OF GENERATOR AND LOAD ON
 NOTES TO FOLLOW.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK, DETAIL LOCATED ON
 6.02. REPLY MENTIONS, 6.01
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 NO,NOTES ON 6.01
 STILL MENTIONS THE USE OF ALUM OK.
 PLEASE ALSO SEE REFERENCE TO WRONG CODE
 IN NOTES ON 6.01 AND 3.00 FROM 1999.
 PLEASE SEE WE ARE UNDER 2001 AMENDMENTS
 AND 2002 NEC.
 COULD NOT LOCATE COLOR CODING.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 OK, HOWEVER NOW
 EQUIPMENT GROUNDS HAVE BEEN ADDED TO
 SEC'S. PLEASE SEE 250.6,250.24.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 NO/, NOTE ADDED TO
 4.01, YET NOTE FOR LAYOUT FOR MAINS,
 DISC'S, LOCATIONS ETC TO BE IN FIRE
 COMMAND RM.
 PLEASE ALSO SEE NOTE #13.
  
 29)NOTE: NOTE #29 NO, PLEASE SEE PLANS
 MENTIONS LOAD SHEDDING , HOWEVER NO
 EQUIPMENT FOR LOAD SHEDDING ETC WAS
 PROVIDED. PLEASE SEE LOAD SUMMARY
 INDICATES ELEVATORSBEING SHEDDED.
 PLEASE VERIFY/NOTE ONE STRECHER
 ACCESSIBLE ELEVATOR TO REMAIN.
 PLEASE ALSO SEE LSC 101, SECTION
 11.8.4.2.AS PER CONVERSATION WITH MIKE
 CARSILLO, ONE ELEVATOR (MIN) WILL BE
 REQUIRED TO BE ON GENERATOR POWER EVEN
 WITH RUNNING OF OTHER REQUIRED SYSTEMS.
 *** PLEASE SEE LOAD ON GDP INDICATES
 LOAD ON EDPH AS 552A'S, YET EDPH SHOWS
 LOAD AT 782A'S??
 PLEASE CORRELATE.
 PLEASE ALSO SEE LOAD SHOWN ON GDP IS
 SHOWN AS 1214 A'S YET GEN IS ONLY RATED
 FOR 1205A'S?
 PLEASE VERIFY LOAD, SIZE ETC.
  
 30)NOTE: NOTE #30, NO, PLEASE STILL SEE
 MSBB,MSBA.OTHERS ARE NOTED FOR GROUND
 FAULT PROTECTION. 230.95,240.13 ETC
  
 31)NOTE: NOTE #31 OK.
  
 32)NOTE: NOTE #32 OK?
  
 33)NOTE: NOTE #33 NO, RESPONSE MENTIONS
 THAT GENERATOR IS A SEPARATELY DERIVED
 SUYSTEM, HOWEVER ATS IS SHOWN AS A
 3-POLE UNIT, THERE IS NO GROUNDING
 ELECTRODE SYSTEM SHOWN ON RISER FOR
 GENERATOR. 250.30
 PLEASE ALSO SEE EQUIPMENT GROUNDS SHOWN
 FROM GEN TO GDP? PLEASE SEE
 250.6,250.24.
  
 34)NOTE: NOTE #34, OK. PLEASE SEE
 PREVIOUS NOTES FOR LOAD, LOAD SHEDDING
 ETC.
  
 35)NOTE: NOTE #35. OK, NOTES ON PREVIOUS
 NOTE THIS REVIEW.
  
 36)NOTE: NOTE #36 NO.
  
 37)NOTE: NOTE: #37 OK.
  
 38)NOTE: NOTE #38 OK.
  
 39)NOTE: NOTE #39 OK.
  
 40)NOTE: NOTE #40 OK.
  
 41)NOTE: NOTE #41 NO, PLEASE SEE SOME
 CIRCUITING AS NOTED ON REVIEW NOTE #2.
 SOME OF THESE HAVE BEEN REDLINED ON ONE
 SET.
  
 42)NOTE: NOTE #42 NO, NOTE COULD NOT BE
 LOCATED TO INCLUDE EXCEPTIONS.
 PER NFPA-72 8-1.4.2
  
 43)NOTE: NOTE #43 OK.
  
 44)NOTE: NOTE #44 OK.
  
 45)NOTE: NOTE #45 NO, PLEASE SEE SOME
 UNITS(D1,G, B ) GFI'S REQUIRED W/IN 3'
 OF SINK EDGE. PLEASE EITHER ADD ONE, OR
 MOVE GFI TO CENTER BETWEEN SINKS.
 210.52D
  
 46)NOTE: NOTE #46 OK.
  
 47)NOTE: NOTE #47 OK, PLEASE SEE
 PREVIOUS NOTES WITH REFERENCE TO
 CIRCUITING OF HALL/FOYER RECEPTS.
  
 48)NOTE: NOTE #48 OK.
  
 NEW NOTES>
  
 1)NOTE: PLEASE SEE DRAWING "KEYNOTES" #7
 MENTIONS ALL MAINS TO HAVE "SHUNT TRIPS"
 LOCATED IN FIRE COMMAND RM.
 PLEASE SEE MSBA, MSBB, ARE THE ONLY
 "MIANS" NOTED AS HAVING "SHUNT TRIP
 MAINS" PLEASE VERIFY OTHERS.
 PLEASE ALSO SEE MSBB AND MSBB, SHUNT
 TRIP TYPE BREAKER TO BE SELECTED MUST
 ALSO HAVE A MANUAL MEANS OF DISCAND
 MUST BE EXTERNAL.
 230.76,230.79,110.27
  
 2)NOTE: PLEASE SEE GENERATOR SUBMITTALS:
  
 FUEL TANK CHECKED FOR USE INDICATES A
 600KW GEN? PLEASE SEE SPEC BOOKS AND
 PLEASE ADJUST.
  
  
 PLEASE SEE MANY OF THESE ABOVE ITEMS
 HAVE BEEN REDLINED ON ONE SET OF PLANS
 FOR REFERENCE.
  
 PLEASE SEE ANY POSSIBLE NOTES FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO REMOVED ALL OLD/
 VOIDED SHEETS AND INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF ALL OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE WHEN
 RESUBMITTING PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  