2006-11-01 19:15:17-------------DENIED-------------
  
 1. M3.12 THERE ARE SEVERAL AREAS WHICH SHOW CHANGES
 FROM THE PREVIOUS PLAN DATED 8/16/06 BUT ARE NOT MARKED
 AS CHANGES ON THIS PLAN. IS THE INTENT TO MAKE THESE
 CHANGES BUT THEY WERE NOT CLOUDED? IT SEEMS LIKELY THAT
 THESE AREAS HAVE INADVERTANTLY REVERTED TO A PREVIOUS
 DESIGN. PLEASE CORRECT BY EITHER CLOUDING ALL RELEVANT
 CHANGES FOR REVISION 7 OR CORRECT AREAS WHICH ARE
 INTENDED TO BE UNCHANGED FROM PREVIOUS APPROVED PLAN
 (8/16/06).
  
 2. M3.13 SAME SITUATION AS ABOVE. SEVERAL AREAS ARE
 CHANGED FROM PREVIOUS PLAN DATED 8/16/06 BUT ARE NOT
 SHOWN AS BEING REVISED. PLEASE CLARIFY OR CORRECT.
  
 3. M3.14 UNIT F DUCT SIZE AND ROUTING HAS CHANGED FROM
 PREVIOUS PLAN (8/16/06) AND IS NOT SHOWN AS BEING
 REVISED ON THIS PAGE. PLEASE CLARIFY OR CORRECT.
  
 4. M3.18 HAS BEEN SUBMITTED AS REV 5. THERE ARE NO
 PREVIOUS VERSIONS OF THIS PAGE IN THE PERMIT SET OF
 PLANS. WE ALSO APPEAR TO BE MISSING PAGES M3.15,3.16
 AND 3.17.
  