Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 15
Notes
Date Text
2007-03-16 17:29:39DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P2.15 UPPER ROOF SECTIONS. SOME ROOF SECTIONS DO
 NOT HAVE SECONDARY ROOF DRAINS AS REQUIRED BY SECTION
 1107.1. PLEASE INDICATE THE LOCATION OF THE SECONDARY
 ROOF DRAINS.(SEE RED LINE MARKINGS ONE SHEET P2.15).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]