Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 13
Notes
Date Text
2007-03-16 07:48:32DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P2.09 MAXIMUM SQUARE FOOTAGE OF A 4" EMERGENCY
 SECONDARY DRAIN IS 2044SF ON THE VERTICAL AND 800SF ON
 THE HORIZONTAL PER TABLE 1106.3. TWO SECONDARY ROOF
 DRAINS EXCEED THIS LIMIT AND SHALL BE A MINIMUM 5".
  
 2. SHT P3.03 THE TWO 4" HUB DRAINS FOR THE POOL
 EQUIPMENT ROOM ARE NOT VENTED AS REQUIRED IN SECTION
 901.2.1.
  
 3. SHT P3.03 THE CHANGED PIPE SIZE IN THE BUILDING
 DRAIN SHOWING 4"@18"/FT IS NOT APPROVED AS THE 8" IS
 SLOPED AT 1/16"/FT. PER SECTION 704.1, HORIZONTAL
 DRAINAGE PIPING SHALL BE IN UNIFORM ALIGNMENT AT
 UNIFORM SLOPES.
  
 4. SHT P3.07 REVISIONS 3, 4, & 6 WERE NOT FOUND. SOME
 CHANGES FOUND ON THE PLAN HAVE NO CLOUDS OR REVISION
 NUMBERS. PLEASE CLOUD AND NUMBER ALL REVISIONS NOT
 PREVIOUSLY APPROVED AND SHUT OFF ALL REVISIONS
 PREVIOUSLY APPROVED TO AVOID CONFUSION AND HELP
 EXPEDITE THE REVIEW PROCESS.--WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.--AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM THE SYSTEM. SECTION 604.9. --
 INFORMATIONAL: THE COOLING TOWERS USUALLY HAVE AN AIR
 GAP ON THE WATER SUPPLY AND THE BACKFLOW PREVENTORS,
 (4), ARE PROBABLY NOT REQUIRED. ALSO THE IRRIGATION
 LINE SHOULD BE LABELED AS SUCH SO AS TO PREVENT FUTURE
 CONNECTIONS FOR POTABLE WATER USE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]