| 2007-03-16 07:48:32 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1. SHT P2.09 MAXIMUM SQUARE FOOTAGE OF A 4" EMERGENCY |
| | SECONDARY DRAIN IS 2044SF ON THE VERTICAL AND 800SF ON |
| | THE HORIZONTAL PER TABLE 1106.3. TWO SECONDARY ROOF |
| | DRAINS EXCEED THIS LIMIT AND SHALL BE A MINIMUM 5". |
| | |
| | 2. SHT P3.03 THE TWO 4" HUB DRAINS FOR THE POOL |
| | EQUIPMENT ROOM ARE NOT VENTED AS REQUIRED IN SECTION |
| | 901.2.1. |
| | |
| | 3. SHT P3.03 THE CHANGED PIPE SIZE IN THE BUILDING |
| | DRAIN SHOWING 4"@18"/FT IS NOT APPROVED AS THE 8" IS |
| | SLOPED AT 1/16"/FT. PER SECTION 704.1, HORIZONTAL |
| | DRAINAGE PIPING SHALL BE IN UNIFORM ALIGNMENT AT |
| | UNIFORM SLOPES. |
| | |
| | 4. SHT P3.07 REVISIONS 3, 4, & 6 WERE NOT FOUND. SOME |
| | CHANGES FOUND ON THE PLAN HAVE NO CLOUDS OR REVISION |
| | NUMBERS. PLEASE CLOUD AND NUMBER ALL REVISIONS NOT |
| | PREVIOUSLY APPROVED AND SHUT OFF ALL REVISIONS |
| | PREVIOUSLY APPROVED TO AVOID CONFUSION AND HELP |
| | EXPEDITE THE REVIEW PROCESS.--WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS.--AIR CHAMBERS ARE |
| | NOT APPROVED. DELETE FROM THE SYSTEM. SECTION 604.9. -- |
| | INFORMATIONAL: THE COOLING TOWERS USUALLY HAVE AN AIR |
| | GAP ON THE WATER SUPPLY AND THE BACKFLOW PREVENTORS, |
| | (4), ARE PROBABLY NOT REQUIRED. ALSO THE IRRIGATION |
| | LINE SHOULD BE LABELED AS SUCH SO AS TO PREVENT FUTURE |
| | CONNECTIONS FOR POTABLE WATER USE. |
| | |