| Plan Review Notes For Permit 04110961 |
| Permit Number |
04110961 |
|
| Review Stop |
B |
| Sequence Number |
112 |
|
| Notes |
| Date |
Text |
| 2006-11-10 18:03:19 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL SUBMITTAL ON 9/27/06 FOR ARCHITECT'S MEMO | | | IN RESPONSE TO PLAN REVIEW (#95) DATED 9/6/06 ON | | | OMISSION OF OVERFLOW SCUPPERS. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC (PLUMBING) 1107.1OVERFLOW SCUPPERS.THE | | | ORIGINAL PLAN REVIEW COMMENT REFERS TO WALL SECTION 4 | | | ON SHEET A5-4.ON THAT SHEET, THE WALL SECTION MARKER | | | IS SHOWN, ON THE ADJACENT "KEY PLAN / PARTIAL | | | ELEVATION", TO BE CUTTING THOUGH THE BALCONY, BUT THE | | | WALL SECTION SHOWS A 3'-6" WALL, NOT AN "OPEN RAILING". | | | IF WALL SECTION 4 ON SHEET A5-4 IS NOT CORRECT, IT MUST | | | BE REVISED BEFORE THE PROPOSED OMISSION OF THE SCUPPERS | | | CAN BE REVIEWED. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] |
|