Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop B
Sequence Number 112
Notes
Date Text
2006-11-10 18:03:19BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 ARCHITECTURAL SUBMITTAL ON 9/27/06 FOR ARCHITECT'S MEMO
 IN RESPONSE TO PLAN REVIEW (#95) DATED 9/6/06 ON
 OMISSION OF OVERFLOW SCUPPERS.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC (PLUMBING) 1107.1OVERFLOW SCUPPERS.THE
 ORIGINAL PLAN REVIEW COMMENT REFERS TO WALL SECTION 4
 ON SHEET A5-4.ON THAT SHEET, THE WALL SECTION MARKER
 IS SHOWN, ON THE ADJACENT "KEY PLAN / PARTIAL
 ELEVATION", TO BE CUTTING THOUGH THE BALCONY, BUT THE
 WALL SECTION SHOWS A 3'-6" WALL, NOT AN "OPEN RAILING".
 IF WALL SECTION 4 ON SHEET A5-4 IS NOT CORRECT, IT MUST
 BE REVISED BEFORE THE PROPOSED OMISSION OF THE SCUPPERS
 CAN BE REVIEWED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS