Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 11
Notes
Date Text
2006-11-01 06:34:37DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1. SHT P2.08 A CROSS CONNECTION IS SHOWN. KEY NOTES #8
 COLD WATER TO HOSE BIBB IN UNIT 'F2' CONNECTED TO THE
 STORM LINE. (INDICATED ON PREVIOUS REVIEW). - IDENTIFY
 NEW RWL RISERS AT COL. LINE P-20/P.H, BETWEEN COL. LINE
 P-20 BETWEEN COL. LINES P.G & P.H, COL LINE P-25 BELOW
 P.G, AND BETWEEN COL. LINES P-24/P-25& P.C/P.D.
 SECTION 104.2.1.
  
 2. SHT P2.10 FITNESS SINK SHOWN IN CABINET, BUT THE
 SANITARY PIPING HAS BEEN DELETED ON THE RISER DIAGRAM
 AND FLOOR PLAN. PLEASE CLARIFY. - KEY NOTES #18 ADD
 THIS REVISION WAS NOT FOUND. PLEASE CLARIFY. SECTION
 104.2.1.
  
 3. SHT P3.03 REVISION 4 NOT APPROVED AT THE BUILDING
 DRAIN, (8" 1/16"/FT SLOPE). OTHER SECTIONS OF THE
 BUILDING DRAIN SHOW 4" 1/4"/FT SLOPE, AND HORIZONTAL
 DRAINAGE PIPING SHALL BE INSTALLED IN UNIFORM ALIGNMENT
 AT UNIFORM SLOPES. SECTION 704.1.
  
 4. SHT P3.15 THIS SHEET WAS VOIDED IN ORDER TO ISSUE
 THE PERMIT FOR THE BUILDING. THE GAS PLANS WERE TO BE
 SUBMITTED SEPARATELY UNDER A SEPARATE GAS PERMIT. ALL
 REVISIONS TO THE GAS PLANS SHALL BE SUBMITTED UNDER THE
 GAS PERMIT NUMBER. (TO THIS DATE NO GAS PERMIT HAS BEEN
 ISSUED. THE GAS PERMIT HAS BEEN DENIED ON 4-12-06 AND
 HAS NOT BEEN PICKED UP BY THE CONTRACTOR TO ADDRESS
 COMMENTS. CONTRACTORS HAS BEEN CALLED 10-30-6 FOR
 P/U).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731