2006-11-10 16:36:33BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 10/26/06 FOR GRAB BAR LOAD TEST RESULTS.
  
 61G15-23.002(2)FL. ADMIN. CODE.
 THE LOAD TEST RESULTS ARE GOOD, BUT THE ENGINEER'S
 SIGNATURES ON THE LETTER AND TEST RESULT SHEETS ARE ALL
 PHOTOCOPIES, AND THE TEST RESULT SHEETS DO NOT HAVE A
 RAISED SEAL.ALL SHEETS SHALL HAVE THE ORIGINAL
 SIGNATURE AND RAISED SEAL OF THE ENGINEER. (471.025
 F.S. AND 471.023 F.S.).
  