| Date |
Text |
| 2004-12-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | DESIGN MANUAL NO. 101/0 |
| | CITY CODE |
| | |
| | 1) PLANS SHALL BE SIGNED, SEALED, & |
| | DATED AS REQUIRED BY FAC 61G1-16.003, & |
| | FAC 61G15-23.002. FS 481.2055 & FS |
| | 471.025. THIS IS REQUIRED FOR ALL |
| | SHEETS |
| | SUBMITTED FOR PUBLIC RECORD, SECTION |
| | 104.2.2. |
| | 2) SHT A1-8 SHOW THE LOCATIONS FOR THE |
| | SEDCONDARY DRAINS PER SECTION 1107 AND |
| | ALL SUBSECTIONS. |
| | 3) SHTS A1.9, A1-13, & A1-14 SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS PER SECTIONS 1106, & 1107 |
| | AND ALL SUBSECTIONS. SHOW SQUARE |
| | FOOTAGE |
| | FOR EACH AREA AND SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPETS, AND |
| | ALL AREAS OF ROOFS DRAINING ON TO THE |
| | ROOF FROM ABOVE. |
| | 4) ALL UNITS SHALL BE DESIGNATED |
| | SPECIFICATION "A" OR "B" PER FHA DESIGN |
| | MANUAL PAGES 7.34 & 7.35. |
| | 5) SHT A2.0 UNIT G NO CLEAR FLOOR SPACE |
| | SHOWN IN THE BATHROOM. SEE PAGE 7.43 |
| | PARAGRAPH 1. |
| | 6) SHT A2.1 UNIT TH-2 NO CLEAR FLOOR |
| | SPACE SHOWN IN THE POWDER ROOM. PAGE |
| | 7.43. |
| | 7) SHT A2.2 ALL UNITS NO CLEAR FLOOR |
| | SPACE SHOWN IN THE POWDER ROOM. SEE |
| | PAGE |
| | 7.43. |
| | 8) SHT A2.3 UNIT B1 CLEAR NO FLOOR |
| | SPACE |
| | FOR THE KITCHEN SHOWN ON PLANS. SEE |
| | PAGES 7.3, 7.4, 7.5, & 7.6. |
| | 9) SHT A2.3 NO CLEAR FLOOR SAPCE AND |
| | TURNING AREA ARE SHOWN IN THE MENS AND |
| | WOMENS TOILET ROOMS. SECTION 11-4.22.3 |
| | 10) SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR THE FIXTURE COUNT PER |
| | TABLE 403.1 SHOW THE SQUARE FOOTAGE FOR |
| | EACH AREA OF THE COMMON AREA. (ADMIN, |
| | RECPTION DESK, MAIR ROOM, PACKAGE ROOM |
| | ECT.). |
| | 11) SHT A2-11 MENS & WOMENS TOILET |
| | ROOM, |
| | THE ACCESSIBLE STALL SHALL COMPLY WITH |
| | THE CONFIGURATION SHOWN ON FIG "E" |
| | "TOILET STALL NEW CONSTRUCTION". STALL |
| | MUST HAVE A LAV LOCATED IN IT. |
| | 12) SHT A2-11 SHOW CLEAR FLOOR SPACE |
| | FOR |
| | THE W/C'S, URINAL, AND LAVS PER |
| | SECTIONS |
| | 11-4.16.2, 11-4.18.3, & 11-4.19.3. |
| | 13) THE FLOOR PLAN FOR THE 6TH FLOOR IS |
| | NOT COMPLETE. ONLY ONE SECTION ON THE |
| | FLOOR IS SUBMITTED. SECTION 104.2.1. |
| | 14) SHT A2-12 UNIT B1 CLEAR FLOOR SPACE |
| | FOR THE KITCHEN NOT SHOWN. PAGES 7.3, |
| | 7.4, 7.5, & 7.6. |
| | 15) SHTS A-2.14 THRU A2-17, SHOW |
| | SECONDARY DRAINS FOR THE TERRACES PER |
| | SECTION 1107. |
| | 16) SHT A2-17 SHOW CLEAR FLOOR SPACE |
| | FOR |
| | KITCHEN FIXTURES. PAGES 7.3 THRU 7.6. |
| | 17) SHT A5-7 PLANS SHALL BE ROUTED TO |
| | THE PBC HEALTH UNIT FOR REVIEW. (SEE |
| | THE |
| | BAR) SECTION 101.4.7. |
| | 18) SHTS A8-3 & A9-0 PLEASE CLARIFY - |
| | BACKING GUAGE FOR TYPICAL GRAB BAR & |
| | UNIT PLAN NOTES (A9-0) INDICATES 16 |
| | GUAGE, BUT TYPICAL ACCESSIBLE TOILET |
| | DETAIL INDICATES 20 GUAGE. - SUBMIT |
| | CALCULATIONS SHOWING COMPLIANCE WITH |
| | SECTIONS 11-4.26.3(2)(3)(4). |
| | 19) SHT P1.01 PLUMBING DRAWING INDEX |
| | DRAWING #P1.01 STATES "ELECTRIC PLAN. |
| | PLEASE CLARIFY. SECTION 104.2.1 |
| | 20) SHT P2.01 SHOWER NEAR S/3 NOT |
| | VENTED. - THE TUB NEAR S7 NOT VENTED. - |
| | SHOWER NEAR S/6 BIT VEBTED. SECTION |
| | 901.2.1. |
| | 21) SHT P2.01 KITCHEN SINK NOT APPROVED |
| | IN THE WET VENT. SECTION 909.1 UNIT I |
| | 22) SHT P2.01NO BRANCH LINE TO D/7 |
| | ON |
| | THE PLANS. SECTION 104.2.1. |
| | 23) SHT P2.01 WATER CLOSET NOT APPROVED |
| | UPSTREAM OF STACK S/31. DESIGN MANUAL |
| | 101/0. |
| | 24) SHT P2.02 4" PAD TO DRAIN INTO |
| | STORM, NOT CONDENSATE SYSTEM. |
| | 25) SHT P2.10 INDICATE LOCATIONS FOR |
| | SECONDARY DRAINS/SCUPPERS FOR DECK AREA |
| | AROUND POOL. SECTION 1107. |
| | 26) SHT P3.09 ALL UNITS, KEY NOTES #4 |
| | CONDENSATE SHALL DRAIN SEPARATELY OUT |
| | OF |
| | THE BUILDING TO THE STORM LINES, CATCH |
| | BASIN, OR APPROVED DRYWELL, NOT INTO |
| | THE |
| | SANITARY SYSTEM. CITY CODE SECTION |
| | 90-125(B)(5). |
| | 27) SHT P3.08 UNIT "H" WATER ISOMETRIC, |
| | NO UNIT "H" FLOOR PLAN LOCATED. PLEASE |
| | CLARIFY. SECTION 104.2.1. KEY NOTES #4 |
| | CITY CODE SECTION 90-125(B)(5) |
| | CONDENSATE SHALL NOT DRAIN INTO THE |
| | SANITARY SYSTEM. |
| | 28) SHT P3.09 UNIT "E"W/C MISSING. - |
| | UNIT "D2" NO WASH MACHINE, AND AN EXTRA |
| | SHOWER. - UNIT "D1" SHOWER MARKED AS |
| | THB |
| | AND EXTRA LAV. MISSING A LAV IN TUB |
| | BATH |
| | SECTION 104.2.1. |
| | 29) SHT P3.10 KEY NOTES #4 CONDENSATE |
| | SHALL NOT DRAIN INTO THE SANITARY. CITY |
| | CODE SECTION 90-125(B)(5). |
| | 30) SHT P3.11 8" REQUIRED ON BRANCH |
| | LINE |
| | DOWNSTREAM OF THE 8" 9040 SF AND |
| | UPSTREAM OF THE 10" 14707SF. TABLE |
| | 1106.3. |
| | 31) SHT P3.11 WHERE DOES RWL #2 CONNECT |
| | TO THE SYSTEM? SECTION 104.2.1. |
| | 32) SHT P3.11 AT THE BASE OF RWL #15, |
| | UPSTREAM OF 12" BUILDING STORM DRAIN |
| | LINE 12" (18360 SF) SHOWS 10" |
| | DOWNSTREAM |
| | OF 12" (16940 SF). PLEASE CLARIFY. |
| | SECTION 104.2.1 & SECTION 704.2. |
| | 33)SHT P3.13 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR THE REQUIRED GAS |
| | PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING |
| | USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 34) SHT P3.13 KEY NOTES #5 NOT SHOWN ON |
| | PLANS. PLSEAS CLARIFY. SECTION 104.2.1. |
| | 35) SHT P3.13 NFPA 54 NOT ADOPTED. PIPES |
| | SHALL BE SIZED BY FBC-2001 FUEL GAS CODE |
| | TABLES. |
| | 36) SHT P4.01 GENERAL NOTES #'S 5 & 6, |
| | CLARIFY WHAT KITCHEN AND LAUNDRY, AND |
| | WHAT THESE ARE FOR? SECTION 104.2.1. |
| | 37) SHTS P3.01 & P3.02 INDICATE ALL PIPE |
| | SIZES AND SHOW DFU'S AS THEY ACCUMULATE |
| | IN THE BLDG DRAIN. SECTION 104.2.1 AND |
| | TABLE 710.1(1). |
| | 38) SHT P3.02 FIRST RISER AND LAST RISER |
| | (I), INDICATE WHERE THEY CONNECT TO THE |
| | BUILDING DRAIN. SECTION 104.2.1. |
| | 39) SHT P3.03 IDENTIFY ALL RISERS AND |
| | SHOW WHERE THEY CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | 40) SHT P3.04 SANITARY RISERS ARE |
| | MISSING. PLEASE SUBMIT A SANT. RISER FOR |
| | EACH NUMBER SHOWN ON THE SANT. BLDG. |
| | DRAIN ISOMETRIC SHOWN ON SHT P3.01. |
| | 41) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BLDG. SECTION |
| | 608.13.2. |
| | 42) THERMAL EXPANSION CONTROL IS |
| | REQUIRED PER SECTION 607.3.2. |
| | 43) SUBMIT A CONDENSATE RISER DIAGRAM. |
| | SECTION 104.2.1. |
| | 44) SEPARATE PERMITS ARE REQUIRED FOR |
| | THE GAS SYSTEM AND THE IRRIGATION |
| | SYSTEM |
| | 45) PLANS DO NOT APPEAR TO BE COMPLETE |
| | AT THIS TIME, AND MORE COMMENTS MAY |
| | FOLLOW AFTER THE RESPONSES FROM THESE |
| | COMMENTS ARE ADDRESSED. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |