Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 DESIGN MANUAL NO. 101/0
 CITY CODE
  
 1) PLANS SHALL BE SIGNED, SEALED, &
 DATED AS REQUIRED BY FAC 61G1-16.003, &
 FAC 61G15-23.002. FS 481.2055 & FS
 471.025. THIS IS REQUIRED FOR ALL
 SHEETS
 SUBMITTED FOR PUBLIC RECORD, SECTION
 104.2.2.
 2) SHT A1-8 SHOW THE LOCATIONS FOR THE
 SEDCONDARY DRAINS PER SECTION 1107 AND
 ALL SUBSECTIONS.
 3) SHTS A1.9, A1-13, & A1-14 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106, & 1107
 AND ALL SUBSECTIONS. SHOW SQUARE
 FOOTAGE
 FOR EACH AREA AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, AND
 ALL AREAS OF ROOFS DRAINING ON TO THE
 ROOF FROM ABOVE.
 4) ALL UNITS SHALL BE DESIGNATED
 SPECIFICATION "A" OR "B" PER FHA DESIGN
 MANUAL PAGES 7.34 & 7.35.
 5) SHT A2.0 UNIT G NO CLEAR FLOOR SPACE
 SHOWN IN THE BATHROOM. SEE PAGE 7.43
 PARAGRAPH 1.
 6) SHT A2.1 UNIT TH-2 NO CLEAR FLOOR
 SPACE SHOWN IN THE POWDER ROOM. PAGE
 7.43.
 7) SHT A2.2 ALL UNITS NO CLEAR FLOOR
 SPACE SHOWN IN THE POWDER ROOM. SEE
 PAGE
 7.43.
 8) SHT A2.3 UNIT B1 CLEAR NO FLOOR
 SPACE
 FOR THE KITCHEN SHOWN ON PLANS. SEE
 PAGES 7.3, 7.4, 7.5, & 7.6.
 9) SHT A2.3 NO CLEAR FLOOR SAPCE AND
 TURNING AREA ARE SHOWN IN THE MENS AND
 WOMENS TOILET ROOMS. SECTION 11-4.22.3
 10) SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR THE FIXTURE COUNT PER
 TABLE 403.1 SHOW THE SQUARE FOOTAGE FOR
 EACH AREA OF THE COMMON AREA. (ADMIN,
 RECPTION DESK, MAIR ROOM, PACKAGE ROOM
 ECT.).
 11) SHT A2-11 MENS & WOMENS TOILET
 ROOM,
 THE ACCESSIBLE STALL SHALL COMPLY WITH
 THE CONFIGURATION SHOWN ON FIG "E"
 "TOILET STALL NEW CONSTRUCTION". STALL
 MUST HAVE A LAV LOCATED IN IT.
 12) SHT A2-11 SHOW CLEAR FLOOR SPACE
 FOR
 THE W/C'S, URINAL, AND LAVS PER
 SECTIONS
 11-4.16.2, 11-4.18.3, & 11-4.19.3.
 13) THE FLOOR PLAN FOR THE 6TH FLOOR IS
 NOT COMPLETE. ONLY ONE SECTION ON THE
 FLOOR IS SUBMITTED. SECTION 104.2.1.
 14) SHT A2-12 UNIT B1 CLEAR FLOOR SPACE
 FOR THE KITCHEN NOT SHOWN. PAGES 7.3,
 7.4, 7.5, & 7.6.
 15) SHTS A-2.14 THRU A2-17, SHOW
 SECONDARY DRAINS FOR THE TERRACES PER
 SECTION 1107.
 16) SHT A2-17 SHOW CLEAR FLOOR SPACE
 FOR
 KITCHEN FIXTURES. PAGES 7.3 THRU 7.6.
 17) SHT A5-7 PLANS SHALL BE ROUTED TO
 THE PBC HEALTH UNIT FOR REVIEW. (SEE
 THE
 BAR) SECTION 101.4.7.
 18) SHTS A8-3 & A9-0 PLEASE CLARIFY -
 BACKING GUAGE FOR TYPICAL GRAB BAR &
 UNIT PLAN NOTES (A9-0) INDICATES 16
 GUAGE, BUT TYPICAL ACCESSIBLE TOILET
 DETAIL INDICATES 20 GUAGE. - SUBMIT
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)(4).
 19) SHT P1.01 PLUMBING DRAWING INDEX
 DRAWING #P1.01 STATES "ELECTRIC PLAN.
 PLEASE CLARIFY. SECTION 104.2.1
 20) SHT P2.01 SHOWER NEAR S/3 NOT
 VENTED. - THE TUB NEAR S7 NOT VENTED. -
 SHOWER NEAR S/6 BIT VEBTED. SECTION
 901.2.1.
 21) SHT P2.01 KITCHEN SINK NOT APPROVED
 IN THE WET VENT. SECTION 909.1 UNIT I
 22) SHT P2.01NO BRANCH LINE TO D/7
 ON
 THE PLANS. SECTION 104.2.1.
 23) SHT P2.01 WATER CLOSET NOT APPROVED
 UPSTREAM OF STACK S/31. DESIGN MANUAL
 101/0.
 24) SHT P2.02 4" PAD TO DRAIN INTO
 STORM, NOT CONDENSATE SYSTEM.
 25) SHT P2.10 INDICATE LOCATIONS FOR
 SECONDARY DRAINS/SCUPPERS FOR DECK AREA
 AROUND POOL. SECTION 1107.
 26) SHT P3.09 ALL UNITS, KEY NOTES #4
 CONDENSATE SHALL DRAIN SEPARATELY OUT
 OF
 THE BUILDING TO THE STORM LINES, CATCH
 BASIN, OR APPROVED DRYWELL, NOT INTO
 THE
 SANITARY SYSTEM. CITY CODE SECTION
 90-125(B)(5).
 27) SHT P3.08 UNIT "H" WATER ISOMETRIC,
 NO UNIT "H" FLOOR PLAN LOCATED. PLEASE
 CLARIFY. SECTION 104.2.1. KEY NOTES #4
 CITY CODE SECTION 90-125(B)(5)
 CONDENSATE SHALL NOT DRAIN INTO THE
 SANITARY SYSTEM.
 28) SHT P3.09 UNIT "E"W/C MISSING. -
 UNIT "D2" NO WASH MACHINE, AND AN EXTRA
 SHOWER. - UNIT "D1" SHOWER MARKED AS
 THB
 AND EXTRA LAV. MISSING A LAV IN TUB
 BATH
 SECTION 104.2.1.
 29) SHT P3.10 KEY NOTES #4 CONDENSATE
 SHALL NOT DRAIN INTO THE SANITARY. CITY
 CODE SECTION 90-125(B)(5).
 30) SHT P3.11 8" REQUIRED ON BRANCH
 LINE
 DOWNSTREAM OF THE 8" 9040 SF AND
 UPSTREAM OF THE 10" 14707SF. TABLE
 1106.3.
 31) SHT P3.11 WHERE DOES RWL #2 CONNECT
 TO THE SYSTEM? SECTION 104.2.1.
 32) SHT P3.11 AT THE BASE OF RWL #15,
 UPSTREAM OF 12" BUILDING STORM DRAIN
 LINE 12" (18360 SF) SHOWS 10"
 DOWNSTREAM
 OF 12" (16940 SF). PLEASE CLARIFY.
 SECTION 104.2.1 & SECTION 704.2.
 33)SHT P3.13 THE FOLLOWING INFORMATION
 IS REQUIRED FOR THE REQUIRED GAS
 PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING
 USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 34) SHT P3.13 KEY NOTES #5 NOT SHOWN ON
 PLANS. PLSEAS CLARIFY. SECTION 104.2.1.
 35) SHT P3.13 NFPA 54 NOT ADOPTED. PIPES
 SHALL BE SIZED BY FBC-2001 FUEL GAS CODE
 TABLES.
 36) SHT P4.01 GENERAL NOTES #'S 5 & 6,
 CLARIFY WHAT KITCHEN AND LAUNDRY, AND
 WHAT THESE ARE FOR? SECTION 104.2.1.
 37) SHTS P3.01 & P3.02 INDICATE ALL PIPE
 SIZES AND SHOW DFU'S AS THEY ACCUMULATE
 IN THE BLDG DRAIN. SECTION 104.2.1 AND
 TABLE 710.1(1).
 38) SHT P3.02 FIRST RISER AND LAST RISER
 (I), INDICATE WHERE THEY CONNECT TO THE
 BUILDING DRAIN. SECTION 104.2.1.
 39) SHT P3.03 IDENTIFY ALL RISERS AND
 SHOW WHERE THEY CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 40) SHT P3.04 SANITARY RISERS ARE
 MISSING. PLEASE SUBMIT A SANT. RISER FOR
 EACH NUMBER SHOWN ON THE SANT. BLDG.
 DRAIN ISOMETRIC SHOWN ON SHT P3.01.
 41) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BLDG. SECTION
 608.13.2.
 42) THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2.
 43) SUBMIT A CONDENSATE RISER DIAGRAM.
 SECTION 104.2.1.
 44) SEPARATE PERMITS ARE REQUIRED FOR
 THE GAS SYSTEM AND THE IRRIGATION
 SYSTEM
 45) PLANS DO NOT APPEAR TO BE COMPLETE
 AT THIS TIME, AND MORE COMMENTS MAY
 FOLLOW AFTER THE RESPONSES FROM THESE
 COMMENTS ARE ADDRESSED.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS