| 2004-12-21 00:00:00 | DENIED: |
| | 1.PLAN SHEET M1.01, INDICATES THE |
| | GENERATOR ROOM TO THE SOUTH SIDE OF THE |
| | BUILDING.PLANS DO NOT INDICATE INTENT |
| | FOR THE MUFFLER EXHAUST, AIR INTAKE OR |
| | VENTILATION FOR THIS ROOM.PROVIDE |
| | DISTANCES TO THE PROPERTY LINES AND OR |
| | ADJACENT BUILDINGS.PLEASE NOTE WHEN |
| | TERMINATING NOXIOUS FUMES IT SHALL BE |
| | DONE IN A MANNER AS TO NOT RECIRCULATE |
| | FUMES INTO TO AIR INTAKES, WINDOWS, |
| | DOORS, ETC. |
| | |
| | 2.PLAN SHEET M2.02, PLEASE CLARIFY |
| | THE |
| | TERMINATION OF SEF-GL-1 & 2. WHEN |
| | COMPARED TO PLAN SHEET M1.01 THE |
| | TERMINATION IS INTO THE GARAGE NOT TO |
| | THE EXTERIOR. |
| | |
| | 3.PLAN SHEET M2.02, TRANSFER FROM THE |
| | MECHANICAL ROOM INTO THE GARAGE AREA? |
| | WILL A BACKDRAFT DAMPER BE INSTALLED TO |
| | PREVENT AIR FROM INFILTRATING BACK INTO |
| | MECHANICAL ROOM? |
| | |
| | 4.PLAN SHEET M2.02, PLEASE NOTE OA |
| | RISER SHALL BE LOCATED AS NOT TO |
| | RECEIVE |
| | DAMAGE FROM PARKED VECHILES PER 2001 |
| | FBC(M)303.4. |
| | |
| | 5.PLAN SHEET M2.04, OAU-4 SHOW |
| | COMPLIANCE WITH 2001 FBC(M)401.5 & |
| | 401.5.1. |
| | |
| | 6.PLEASE NOTE, EXHAUST SHALL NOT |
| | TERMINATE ONTO WALKWAYS OR IN SUCH A |
| | MANNER THAT IT WILL NOT BE RECIRCULATED |
| | INTO FRESH AIR INTAKES OR CREATE A |
| | NUISANCE. 2001 FBC(M)401.5, 401.5.1 & |
| | 501.3. |
| | |
| | 7.PLAN SHEET M3.01, TH1 & TH2, |
| | DUCTWORK AND GRILLES ARE NOT SIZED. |
| | PROVIDE DIMENSION FOR THE R/A TRANSFER |
| | GRILLES ALSO. |
| | |
| | 8.PLAN SHEET M3.01 UNIT I DOES NOT |
| | INDICATE R/A FROM THE MASTERBEDROOM. |
| | |
| | 9.PLEASE NOTE, RETURN AIR JUMPERS |
| | SHALL BE SIZED IN ACCORDANCE WITH 2001 |
| | FBC(M)601.4 EXCEPTIONS 1 THROUGH 3. |
| | |
| | 10. CERTAIN UNITS INDICATE RETURN AIR |
| | PLENUMS, PER 2001 FBC(M)602.2.1, NO |
| | COMBUSTIBLES ALLOWED IN THE RETURN AIR |
| | PLENUM. |
| | |
| | 11.PROVIDE OUTSIDE AIR CALUCALTIONS |
| | IN |
| | ACCORDANCE WITH 2001 FBC(M)402.2.1 OR |
| | TABLE 403.3.THIS IS REQUIRED FOR |
| | RESIDENCE AS WELL AS ALL COMMON AREAS. |
| | |
| | 12.PROVIDE SEQUENCE OF OPERATION FOR |
| | SMOKE CONTROL/EVAC IN ACCORDANCE WITH |
| | 2001 FBC 412.5. |
| | |
| | 13.PLEASE INDICATE ALL SYSTEMS THAT |
| | WILL BE SUPPLIED BY EMERGENCY POWER PER |
| | 2001 FBC 412.7.PLEASE NOTE, GARAGE |
| | VENTILATION WILL BE REQUIRED TO BE ON |
| | STAND-BY POWER AS WELL. |
| | |
| | 14.PROVIDE ADDITIONAL INFORMATION ON |
| | FUEL FOR THE GENERATOR AND FILL PIPING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |