Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop M
Sequence Number 1
Notes
Date Text
2004-12-21 00:00:00DENIED:
 1.PLAN SHEET M1.01, INDICATES THE
 GENERATOR ROOM TO THE SOUTH SIDE OF THE
 BUILDING.PLANS DO NOT INDICATE INTENT
 FOR THE MUFFLER EXHAUST, AIR INTAKE OR
 VENTILATION FOR THIS ROOM.PROVIDE
 DISTANCES TO THE PROPERTY LINES AND OR
 ADJACENT BUILDINGS.PLEASE NOTE WHEN
 TERMINATING NOXIOUS FUMES IT SHALL BE
 DONE IN A MANNER AS TO NOT RECIRCULATE
 FUMES INTO TO AIR INTAKES, WINDOWS,
 DOORS, ETC.
  
 2.PLAN SHEET M2.02, PLEASE CLARIFY
 THE
 TERMINATION OF SEF-GL-1 & 2. WHEN
 COMPARED TO PLAN SHEET M1.01 THE
 TERMINATION IS INTO THE GARAGE NOT TO
 THE EXTERIOR.
  
 3.PLAN SHEET M2.02, TRANSFER FROM THE
 MECHANICAL ROOM INTO THE GARAGE AREA?
 WILL A BACKDRAFT DAMPER BE INSTALLED TO
 PREVENT AIR FROM INFILTRATING BACK INTO
 MECHANICAL ROOM?
  
 4.PLAN SHEET M2.02, PLEASE NOTE OA
 RISER SHALL BE LOCATED AS NOT TO
 RECEIVE
 DAMAGE FROM PARKED VECHILES PER 2001
 FBC(M)303.4.
  
 5.PLAN SHEET M2.04, OAU-4 SHOW
 COMPLIANCE WITH 2001 FBC(M)401.5 &
 401.5.1.
  
 6.PLEASE NOTE, EXHAUST SHALL NOT
 TERMINATE ONTO WALKWAYS OR IN SUCH A
 MANNER THAT IT WILL NOT BE RECIRCULATED
 INTO FRESH AIR INTAKES OR CREATE A
 NUISANCE. 2001 FBC(M)401.5, 401.5.1 &
 501.3.
  
 7.PLAN SHEET M3.01, TH1 & TH2,
 DUCTWORK AND GRILLES ARE NOT SIZED.
 PROVIDE DIMENSION FOR THE R/A TRANSFER
 GRILLES ALSO.
  
 8.PLAN SHEET M3.01 UNIT I DOES NOT
 INDICATE R/A FROM THE MASTERBEDROOM.
  
 9.PLEASE NOTE, RETURN AIR JUMPERS
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FBC(M)601.4 EXCEPTIONS 1 THROUGH 3.
  
 10. CERTAIN UNITS INDICATE RETURN AIR
 PLENUMS, PER 2001 FBC(M)602.2.1, NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.
  
 11.PROVIDE OUTSIDE AIR CALUCALTIONS
 IN
 ACCORDANCE WITH 2001 FBC(M)402.2.1 OR
 TABLE 403.3.THIS IS REQUIRED FOR
 RESIDENCE AS WELL AS ALL COMMON AREAS.
  
 12.PROVIDE SEQUENCE OF OPERATION FOR
 SMOKE CONTROL/EVAC IN ACCORDANCE WITH
 2001 FBC 412.5.
  
 13.PLEASE INDICATE ALL SYSTEMS THAT
 WILL BE SUPPLIED BY EMERGENCY POWER PER
 2001 FBC 412.7.PLEASE NOTE, GARAGE
 VENTILATION WILL BE REQUIRED TO BE ON
 STAND-BY POWER AS WELL.
  
 14.PROVIDE ADDITIONAL INFORMATION ON
 FUEL FOR THE GENERATOR AND FILL PIPING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  