| 2006-08-17 00:00:00 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | FROM PLUMBING REVIEW: |
| | |
| | 1. SHT P2.08 NO GAS PIPING SHOWN TO NEW |
| | SPA HEATER. - SHOWS WATER PIPING FOR |
| | HOSE BIBB CONNECTING TO STORM DRAINAGE |
| | AT UNIT F2. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 2. SHT P2.09 EMERGENCY DRAINS AT B1 |
| | UNITS SHALL BE MINIMUM 5". ONE DRAINS |
| | 2340SF AND THE OTHER DRAINS 2510SF AND |
| | BOTH SHOW 4". TABLE 1106.3. |
| | |
| | 3. SHT P2.10 REVISIO #6 NOT FOUND. |
| | PLEASE INDICATE WHERE REVISION CAN BE |
| | LOCATED. SECTION 104.2.1. |
| | |
| | 4. SHT P3.13 RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. PLEASE INDICATE |
| | WHERE THE OFFSETS FOR THE "A" SECTION |
| | CAN BE LOCATED ON THE FLOOR PLANS. THE |
| | FIRST FLOOR DOES NOT REFLECT THE FLOOR |
| | PLAN NOR DOES THE SECOND FLOOR. |
| | |
| | 5. SHT P3.15 THE FOLLOWING INFORMATION |
| | IS REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. **** NOT ALL CUTSECTIONS |
| | SHOW THE CORRESPONDING LENGTHS. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED. **** INDICATE IF THE 3" PIPE |
| | WILL BE SCREW PIPE OR WELDED. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). **** #13 INDICATES 1,050,000 |
| | BTU'S BUT SUBMITTAL INDICATES 1,260,000 |
| | BTU'S. CORRELATE SUBMITTALS AND RISER |
| | DIAGRAM INFORMATION. SECTION 104.2.1. |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. **** |
| | MANUF. SPECIFICATION SHEETS FOR POOL |
| | HEATERIN SUBMITTAL BOOK INDICATES A |
| | DIFFERENT POOL HEATER AND DIFFERENT |
| | BTU'S THAN SHOWN ON THE RISER DIAGRAM. - |
| | SUBMIT THE MANUF. SPEC'S FOR THE SPA |
| | HEATER. THE MANUF. SPEC'S FOR THE |
| | FIREPLACE SHOWS NO LISTING. SUBMIT |
| | MANUF. SPEC'S FOR THE MECH. GAS BOILER |
| | (#8). SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR BBQ GRILLS. |
| | |
| | F. SUBMIT THE MANUF. SPECIFICATION |
| | SHEETS FOR EACH GAS REGULATOR. SHOW |
| | LISTING FOR REGULATOR. INDICATE MODEL |
| | NUMBER. |
| | |
| | G. INDICATE MATERIAL FOR REGULATOR VENT |
| | LINES. |
| | |
| | H. GAS CODE REFERENCE IS FBC-2201. |
| | PLEASE CORRECT TO FBC-2001 FUEL GAS |
| | CODE. |
| | |
| | I. SHUT OFF VALVE REQUIRED UPSTREAM OF |
| | THE REGULATORS. (SEE BBQ GRILLS). |
| | SECTION 410.2(5). A UNION IS REQUIRED |
| | BETWEEN SHUT OFF VALVE AND REGULATOR FOR |
| | THE POOL HEATERS. |
| | |
| | 6. THREE SETS OF REVISIONS REQUIRED FOR |
| | REVIEW. (ONLY 2 SETS SUBMITTED). |
| | |