Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-23 00:00:001. SITE PLAN DOES NOT DISPLAY ANY
 EXISTING OR NEW FIRE HYDRANTS.
  
 2. NO INFORMATION PROVIDED WITH
 REGARDS TO EXISTING OR NEW UNDERGROUND
 FIRE MAINS.
  
 3. IT APPEARS THAT THE SECOND PHASE
 BUILDINGS ARE CONNECTED TO THE PHASE
 ONE BUILDINGS. PLEASE EXPLAIN
 OWNERSHIP AND UTILITY ARRANGEMENTS.
  
 4. PLEASE EXPLAIN USE OF RAMPS FOR
 EXIT ACCESS IN THE GARAGE.
  
 5. PLEASE INDICATE EXIT ROUTES FROM
 GARAGE SECOND LEVEL PLAN.
  
 6. PARKING STRUCTURE TO COMPLY WITH
 NFPA 88A.
  
 7. EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 8. NO DOOR PRESENT ADJACENT TO UNIT H,
 SECOND FLOOR LEVEL, OPPOSITE OF THE
 GARAGE EXIT DOOR.
  
 9. PLEASE INDICATE HOW STAIR # 1 CAN
 ACCOMODATE EXIT LOADS FROM BOTH THE
 RESIDENTIAL AND PARKING PORTIONS OF THE
 BUILDING.
  
 10. PLEASE INDICATE THE OCCUPANT LOAD
 FOR THE POOL AND RECREATION DECK.
  
 11. ALL STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 12. ALL STAIRS SHALL BE SLIP RESISTANT.
  
 13. THE BUILDING IS TO COMPLY WITH
 THE FLORIDA BUILDING CODE SECTION 412
 AND SECTION 11-8 OF THE LIFE SAFETY
 CODE 2000 EDITION.
  
 14. KNOX-BOXES WILL BE REQUIRED FOR
 THE PROJECT.
  
 15. THE FIRE COMMAND ROOM SHALL CONTAIN
 ALL OF THE REQUIRED EQUIPMENT PER
 412 OF THE FLORIDA BUILDING CODE AND
 SECTION 11-8 OF THE LIFE SAFETY CODE,
 2000 EDITION.
  
 16. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 17. PLEASE EXPLAIN TEMPORARY 42" HIGH
 ALUMINUM PICKET RAILING ON PAGE A1-9.
  
 18. CURVED STAIRS OPPOSITE OF THE
 FITNESS ROOM AND PLANTER ON PAGE A1-9
 APPEARS TO BE MISSING HANDRAILS.
  
 19. BUILDING ADDRESS IS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 20. KNOX-BOX LOCKING CAPS ARE REQUIRED
 ON THE TWO FIRE DEPARTMENT CONNECTIONS.
  
 21. EXIT SIGNS APPEAR TO OPPOSE ONE
 ANOTHER IN SEVERAL LOCALES.
  
 22. NO FIRE ALARM AUDIBILITY DEVICES
 IN GROUND LEVEL PLAN (SOUTH) FIRE
 ALARM PLAN. THE MANUAL PULL STATION
 AND SPEAKER STROBE APPEAR TO BE
 LOCATED OUTSIDE OF EXIT DOOR.
  
 23. NO FIRE ALARM EQUIPMENT SHOWN TO
 ALERT PERSONS ABOUT AN EMERGENCY WHO
 ARE ON THE POOL DECK.
  
 24. PLEASE NOTE ON THE PLANS THAT ALL
 SMOKE DETECTORS SHALL BE PLACED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 25. ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED ON EVERY LEVEL OF THE
 RESIDENTIAL UNITS.
  
 26. PLEASE INDICATE WHAT THE SMOKE
 CONTROL PANEL WILL LOOK LIKE. A GRAPHIC
 REPRESENTATION OF THE BUILDING SHALL
 BE DISPLAYED ON THE SMOKE CONTROL
 PANEL.
  
 27. PLEASE VERIFY ALL EXIT DOOR SWINGS.
  
  
 28. PLEASE EXPLAIN EMPTY CONDUIT
 FOR FUTURE PHASE II EMERGENCY
 SERVICE.
  
 29. WHERE DO PERSONS GO AFTER LEAVING
 STAIR # 4 GROUND FLOOR EXIT DOOR.
  
 30. MORE DETAILS NEEDED ON THE PRESSURE
 REGULATING VALVES PLANNED FOR THE
 FIRE PROTECTION SYSTEM.
  
 31. WHAT WILL BE THE PROPOSED FIRE
 ACCESS LOCATIONS FOR PHASE I AND PHASE
 II BE WHEN THE CONPLEX IS COMPLETE.
  
 32. PLEASE INDICATE ON THE PLANS THAT
 THE PROPOSED GENERATOR SYSTEM COMPLIES
 WITH ALL OF THE REQUIREMENTS OF
 11.8.4 OF THE LIFE SAFETY CODE,
 2000 EDITION.
  
 33. SINCE THE PROPOSED PROJECT IS
 OF THE MIXED OCCUPANCY TYPE THE
 MOST STRINGENT OF THE OCCUPANCY
 TYPES WILL PREVAIL.
  
 34. THE RESIDENTIAL PORTION SHALL
 BE CONSIDERED ORDINARY HAZARD FOR
 DESIGN PURPOSES.
  
 35. EMERGENCY INSTRUCTIONS SHALL
 BE PROVIDED TO THE RESIDENTS EVERY
 YEAR.
  
 36. THE FIRE SPRINKLER HEADS PLANNED
 FOR USE SHALL BE QUICK RESPONSE OR
 OF THE RESIDENTIAL TYPE.
  
 37. ALL ELEVATORS SHALL COMPLY WITH
 SECTION 9.4. OF THE LIFE SAFETY CODE,
 2000 EDITION. PLEASE NOTE THIS ON THE
 PLANS.
  
 38. PLEASE INDICATE WHICH UNITS
 ARE EQUIPPPED WITH HEARING IMPAIRED
 VISIBILITY DEVICES.
  
 39. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 40. PLEASE INDICATE ON THE PLANS THE
 REQUIRED WATER COLUMN REQUIREMENTS
 FOR THE STAIRWELL PRESSURIZATION
 SYSTEMS.
  
 41. WILL THE GARAGE AND THE TOWER
 BE CONSTRUCTED AT THE SAME TIME.
  
 42. NO CUTTING OR WELDING OPERATIONS
 CAN BE PERFORMED WITHOUT THE APPROVAL
 OF THE BUREAU OF FIRE PREVENTION INSIDE
 THE BUILDINGS AND SAID OPERATIONS ARE
 TO COMPLY WITH NFPA 51B, THE STANDARD
 FOR CUTTING AND WELDING OPERATIONS.
  
 43. CHAPTER 7 OF NFPA 241 REQUIRES
 A FIRE SAFETY PROGRAM BE IMPLEMENTED
 FOR BUILDINGS UNDER CONSTRUCTION,
 RENOVATION AND DEMOLITION. PLEASE
 PROVIDE A COPY OF THIS PLAN FOR REVIEW.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910