| 2004-12-23 00:00:00 | 1. SITE PLAN DOES NOT DISPLAY ANY |
| | EXISTING OR NEW FIRE HYDRANTS. |
| | |
| | 2. NO INFORMATION PROVIDED WITH |
| | REGARDS TO EXISTING OR NEW UNDERGROUND |
| | FIRE MAINS. |
| | |
| | 3. IT APPEARS THAT THE SECOND PHASE |
| | BUILDINGS ARE CONNECTED TO THE PHASE |
| | ONE BUILDINGS. PLEASE EXPLAIN |
| | OWNERSHIP AND UTILITY ARRANGEMENTS. |
| | |
| | 4. PLEASE EXPLAIN USE OF RAMPS FOR |
| | EXIT ACCESS IN THE GARAGE. |
| | |
| | 5. PLEASE INDICATE EXIT ROUTES FROM |
| | GARAGE SECOND LEVEL PLAN. |
| | |
| | 6. PARKING STRUCTURE TO COMPLY WITH |
| | NFPA 88A. |
| | |
| | 7. EXIT SIGN PLACEMENT SHALL NOT |
| | EXCEED 100 FEET. |
| | |
| | 8. NO DOOR PRESENT ADJACENT TO UNIT H, |
| | SECOND FLOOR LEVEL, OPPOSITE OF THE |
| | GARAGE EXIT DOOR. |
| | |
| | 9. PLEASE INDICATE HOW STAIR # 1 CAN |
| | ACCOMODATE EXIT LOADS FROM BOTH THE |
| | RESIDENTIAL AND PARKING PORTIONS OF THE |
| | BUILDING. |
| | |
| | 10. PLEASE INDICATE THE OCCUPANT LOAD |
| | FOR THE POOL AND RECREATION DECK. |
| | |
| | 11. ALL STAIRS AND RAMPS SHALL HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 12. ALL STAIRS SHALL BE SLIP RESISTANT. |
| | |
| | 13. THE BUILDING IS TO COMPLY WITH |
| | THE FLORIDA BUILDING CODE SECTION 412 |
| | AND SECTION 11-8 OF THE LIFE SAFETY |
| | CODE 2000 EDITION. |
| | |
| | 14. KNOX-BOXES WILL BE REQUIRED FOR |
| | THE PROJECT. |
| | |
| | 15. THE FIRE COMMAND ROOM SHALL CONTAIN |
| | ALL OF THE REQUIRED EQUIPMENT PER |
| | 412 OF THE FLORIDA BUILDING CODE AND |
| | SECTION 11-8 OF THE LIFE SAFETY CODE, |
| | 2000 EDITION. |
| | |
| | 16. PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 17. PLEASE EXPLAIN TEMPORARY 42" HIGH |
| | ALUMINUM PICKET RAILING ON PAGE A1-9. |
| | |
| | 18. CURVED STAIRS OPPOSITE OF THE |
| | FITNESS ROOM AND PLANTER ON PAGE A1-9 |
| | APPEARS TO BE MISSING HANDRAILS. |
| | |
| | 19. BUILDING ADDRESS IS REQUIRED. A |
| | MINIMUM OF 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 20. KNOX-BOX LOCKING CAPS ARE REQUIRED |
| | ON THE TWO FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 21. EXIT SIGNS APPEAR TO OPPOSE ONE |
| | ANOTHER IN SEVERAL LOCALES. |
| | |
| | 22. NO FIRE ALARM AUDIBILITY DEVICES |
| | IN GROUND LEVEL PLAN (SOUTH) FIRE |
| | ALARM PLAN. THE MANUAL PULL STATION |
| | AND SPEAKER STROBE APPEAR TO BE |
| | LOCATED OUTSIDE OF EXIT DOOR. |
| | |
| | 23. NO FIRE ALARM EQUIPMENT SHOWN TO |
| | ALERT PERSONS ABOUT AN EMERGENCY WHO |
| | ARE ON THE POOL DECK. |
| | |
| | 24. PLEASE NOTE ON THE PLANS THAT ALL |
| | SMOKE DETECTORS SHALL BE PLACED A |
| | MINIMUM OF THREE FEET FROM AIR |
| | CONDITIONER DIFFUSERS. |
| | |
| | 25. ELECTRIC POWERED SMOKE DETECTORS |
| | ARE REQUIRED ON EVERY LEVEL OF THE |
| | RESIDENTIAL UNITS. |
| | |
| | 26. PLEASE INDICATE WHAT THE SMOKE |
| | CONTROL PANEL WILL LOOK LIKE. A GRAPHIC |
| | REPRESENTATION OF THE BUILDING SHALL |
| | BE DISPLAYED ON THE SMOKE CONTROL |
| | PANEL. |
| | |
| | 27. PLEASE VERIFY ALL EXIT DOOR SWINGS. |
| | |
| | |
| | 28. PLEASE EXPLAIN EMPTY CONDUIT |
| | FOR FUTURE PHASE II EMERGENCY |
| | SERVICE. |
| | |
| | 29. WHERE DO PERSONS GO AFTER LEAVING |
| | STAIR # 4 GROUND FLOOR EXIT DOOR. |
| | |
| | 30. MORE DETAILS NEEDED ON THE PRESSURE |
| | REGULATING VALVES PLANNED FOR THE |
| | FIRE PROTECTION SYSTEM. |
| | |
| | 31. WHAT WILL BE THE PROPOSED FIRE |
| | ACCESS LOCATIONS FOR PHASE I AND PHASE |
| | II BE WHEN THE CONPLEX IS COMPLETE. |
| | |
| | 32. PLEASE INDICATE ON THE PLANS THAT |
| | THE PROPOSED GENERATOR SYSTEM COMPLIES |
| | WITH ALL OF THE REQUIREMENTS OF |
| | 11.8.4 OF THE LIFE SAFETY CODE, |
| | 2000 EDITION. |
| | |
| | 33. SINCE THE PROPOSED PROJECT IS |
| | OF THE MIXED OCCUPANCY TYPE THE |
| | MOST STRINGENT OF THE OCCUPANCY |
| | TYPES WILL PREVAIL. |
| | |
| | 34. THE RESIDENTIAL PORTION SHALL |
| | BE CONSIDERED ORDINARY HAZARD FOR |
| | DESIGN PURPOSES. |
| | |
| | 35. EMERGENCY INSTRUCTIONS SHALL |
| | BE PROVIDED TO THE RESIDENTS EVERY |
| | YEAR. |
| | |
| | 36. THE FIRE SPRINKLER HEADS PLANNED |
| | FOR USE SHALL BE QUICK RESPONSE OR |
| | OF THE RESIDENTIAL TYPE. |
| | |
| | 37. ALL ELEVATORS SHALL COMPLY WITH |
| | SECTION 9.4. OF THE LIFE SAFETY CODE, |
| | 2000 EDITION. PLEASE NOTE THIS ON THE |
| | PLANS. |
| | |
| | 38. PLEASE INDICATE WHICH UNITS |
| | ARE EQUIPPPED WITH HEARING IMPAIRED |
| | VISIBILITY DEVICES. |
| | |
| | 39. SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER SYSTEM. |
| | |
| | 40. PLEASE INDICATE ON THE PLANS THE |
| | REQUIRED WATER COLUMN REQUIREMENTS |
| | FOR THE STAIRWELL PRESSURIZATION |
| | SYSTEMS. |
| | |
| | 41. WILL THE GARAGE AND THE TOWER |
| | BE CONSTRUCTED AT THE SAME TIME. |
| | |
| | 42. NO CUTTING OR WELDING OPERATIONS |
| | CAN BE PERFORMED WITHOUT THE APPROVAL |
| | OF THE BUREAU OF FIRE PREVENTION INSIDE |
| | THE BUILDINGS AND SAID OPERATIONS ARE |
| | TO COMPLY WITH NFPA 51B, THE STANDARD |
| | FOR CUTTING AND WELDING OPERATIONS. |
| | |
| | 43. CHAPTER 7 OF NFPA 241 REQUIRES |
| | A FIRE SAFETY PROGRAM BE IMPLEMENTED |
| | FOR BUILDINGS UNDER CONSTRUCTION, |
| | RENOVATION AND DEMOLITION. PLEASE |
| | PROVIDE A COPY OF THIS PLAN FOR REVIEW. |
| | |