Plan Review Notes
Plan Review Notes For Permit 04110961
Permit Number 04110961
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-08 00:00:00*************** UNSAT******************
  
 ** PLEASE SEE THIS PLANS ARE IN FOR
 "PLAN REVIEW" ONLY AND NOT FOR PERMIT
 APPLICATION.
  
  
 1)NOTE: PLEASE SEE FS 471.025,471.023
 FAC 61G15-23.002. PLEASE SEE MISSING
 LICENSE INFORMATION ON TITLE BLOCK FOR
 ENGINEERING FIRM. PLEASE ALSO SEE ALL
 PLANS/SETS AND SHEETS ARE REQUIRED TO
 BE
 "SIGNED" DATED AND SEALED WHEN
 SUBMITTING FOR PERMIT.
 THIS COMMENT IS FOR ALL TRADES WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES. PLEASE SEE 2.01,2.10
 PLEASE SEE TOWNHOUSE, APT UNITS ARE
 SHOWN W/OUT ANY CIRCUIT #'S SHOWN.
  
 3)NOTE: PLEASE VERIFY LOAD ON SOME
 EXERCISE EQUIPMENT. SHOWS 4 TREADMILLS
 ON ONE CIRCUIT.
  
 4)NOTE: PLEASE SEE NOTE FOR LIGHTNING
 PROTECTION ON E 2.14. PLEASE SEE
 REFERENCE SHOULD BE MADE TO NFPA-780.
 PLEASE NOTE: LIGHTNING PROTECTION IS
 REQUIRED UNDER SEPARATE PERMIT UNLESS
 PLANS AND SPECS ARE SUBMITTED WITH MAIN
 BLDG PERMIT. PLEASE SEE THIS WOULD ALSO
 INCLUDE THE MAIN ELECTRICAL CONTRACTOR
 BEING RESPONSIBLE FOR PERMIT.
  
 5)NOTE: PLEASE SEE 2.14 FOR SOME
 MISSING
 CIRCUITING FOR SLA FIXTURES.
  
 6)NOTE: PLEASE SEE 3.00 WHICH
 IDENTIFIES
 TWO "TOWER ELECTRICAL RMMS. PLEASE
 PROVIDE IDENTIFICATION FOR EACH.
  
 7)NOTE: PLEASE VERIFY IF PHASE II IS
 GOING TO BE A "SEPARATE BLDG" SHOWS
 CONDUIT F-1 FROM FPL VAULT TO STUB OUT
 INTO FUTURE LOCATION HOWEVER GENERATOR
 AND EQUIPMENT FOR PHASE #I IS ALSO
 SHOWN
 AS FEEDING FUTURE PHASE II???
 PLEASE VERIFY TRANSFER OF POWER.
 BLDG-ONE LOSES POWER AND GEN COMES
 ONLINE, BLDG-TWO WHICH HAS NOT LOST
 POWER WILL NOW BE FED FROM GEN WHICH
 HAS
 JUST COME ONLINE? PLEASE REVIEW THIS
 SCENARIO.
  
 8)NOTE: PLEASE CORRELATE IDENTIFICATION
 OF ALL EQUIPMENT AS SHOWN ON ELECTRICAL
 ROOM LAYOUT AND RISER DIAGRAM.
 EDPH/EDP,
 EHA/EH , ME-TH/ MAIN #4, NOT SHOWN. ETC
 215.5
  
 9)NOTE: PLEASE SHOW GRONDING
 ATTACHMENTS
 FOR TRANSFORMER. A SEPARATELY DERIVED
 AC
 SYSTEM THAT IS GROUNDED SHALL COMPLY
 WITH 250.30(A)(1) THROUGH (6).
  
 10)NOTE: PLEASE SEE 4.01 WHICH SHOWS A
 MC#13? PLEASE VERIFY THIS SHOWN AT TWO
 LOCATIONS REDLINED. WOULD THIS BE #14?
  
 11)NOTE: PLEASE SEE LOAD SUMMARY FOR
 MSBH WHICH IS SHOWN AS 1600A, YET
 FEEDER
 SCHEDULE INDICATES A 1200A FEEDERS?
 PLEASE ALSO SEE FEEDER SCHEDULE
 MENTIONS
 1200A FEEDERS, YET NO CONDUIT OR
 CONDUCTOR SIZES ARE SHOWN?? 215.5
 PLEASE SEE 310.16, 240.4C,
 DEVICES RATED OVER 800 AMPERES. WHERE
 THE OVERCURRENT DEVICE IS RATED OVER
 800
 AMPERES, THE AMPACITY OF THE CONDUCTORS
 IT PROTECTS SHALL BE EQUAL TO OR
 GREATER
 THAN THE RATING OF THE OVERCURRENT
 DEVICE DEFINED IN 240.6.
 PLEASE SEE THIS EQUIPMENT IS SHOWN AS
 MLO WHEN A MCB IS REQUIRED IF THIS IS
 GOING TO BE "MAIN #1"
 230.70
  
 12)NOTE: PLEASE SEE CORRELATE THE # OF
 UNTIS WITH #'S OIF UNITS SHOWN ON
 A-SHEETS. PLEASE ADJUST ANY
 RISERS/PANELS AND LOAD CALCULATIONS.
 215.5
  
 13)NOTE: PLEASE SEE RISER INDICATES A
 MAIN DISCONNECT FOR FIRE PUMP
 CONTROLLER
 YET NO INFORMATION IS GIVEN. 215.5
  
 14)NOTE:: PLEASE SEE 240.4 WHERE THE
 OVERCURRENT DEVICE IS RATED OVER 800
 AMPERES, THE AMPACITY OF THE CONDUCTORS
 IT PROTECTS SHALL BE EQUAL TO OR
 GREATER
 THAN THE RATING OF THE OVERCURRENT
 DEVICE DEFINED IN 240.6. THIS NEEDS TO
 BE ADDRESSED IN A COUPLE LOACTIONS.
  
 15)NOTE: PLEASE CORELATE KW RATING OF
 GENERATOR SHOWN ON PLANS AND SPEC
 SHEETS
 SUBMITTED.
 215.5
  
 16)NOTE: PLEASE SEE PANEL RBH IS SHOWN
 AS 225A RATED, YET THIS PANEL IS FED
 FROM MSBH WITH A 250A BRKR. PLEASE
 CORRELATE AND ADJUST.
 215.5
  
 17)NOTE:PLEASE PROVIDE NOTE: FOR RATING
 OF BUS-DUCT.
 PLEASE ALSO SEE 368.6 FOR PENETRATION
 THROUGH WALLS AND FLOORS.
 (1) BUSWAYS SHALL BE PERMITTED TO BE
 EXTENDED VERTICALLY THROUGH DRY FLOORS
 IF TOTALLY ENCLOSED (UNVENTILATED)
 WHERE
 PASSING THROUGH AND FOR A MINIMUM
 DISTANCE OF 1.8 M (6 FT) ABOVE THE
 FLOOR
 TO PROVIDE ADEQUATE PROTECTION FROM
 PHYSICAL DAMAGE.
 (2) IN OTHER THAN INDUSTRIAL
 ESTABLISHMENTS, WHERE A VERTICAL RISER
 PENETRATES TWO OR MORE DRY FLOORS, A
 MINIMUM 100 MM (4 IN.) HIGH CURB SHALL
 BE INSTALLED AROUND ALL FLOOR OPENINGS
 FOR RISER BUSWAYS TO PREVENT LIQUIDS
 FROM ENTERING THE OPENING. THE CURB
 SHALL BE INSTALLED WITHIN 300 MM (12
 IN.) OF THE FLOOR OPENING. ELECTRICAL
 EQUIPMENT SHALL BE LOCATED SO THAT IT
 WILL NOT BE DAMAGED BY LIQUIDS THAT ARE
 RETAINED BY THE CURB.
 PLEASE PROVIDE NOTE FOR REQUIRED
 CURBING.
  
 18)NOTE: PLEASE SEE RISER MENTIONS TO
 PROVIDE "ALTERNATE PRICE" FOR
 CONDUCTORS
 AND CONDUIT TO BUS-TAP BOX LOCATIONS.
 PLEASE PROVIDE CONDUIT/CONDUCTOR SIZES
 ON PLANS AT THIS TIME TO MEET MIN
 REQUIREMENTS. 240.4,310.16
  
 19)NOTE: PLEASE SEE LOCAL
 AMENDMENTS,250.62 NO EQUIPMENT
 GROUNDING
 MAY BE ALUM.
 PLEASE ALSO SEE 310.2 FOR SIZING OF MIN
 ALUM CONDUCTORS.
 PLEASE PROVIDE NOTE FOR COLOR CODING OF
 CONDUCTORS PER LOCAL AMEND. 215.
  
 20)NOTE: PLEASE SEE RTU32, SHOWN WITH
 #12 AWG ON A 100A3P BRKR. PLEASE SEE
 310.16, 240.4 FOR SIZING.CONDUCTORS,
 OTHER THAN FLEXIBLE CORDS, FLEXIBLE
 CABLES, AND FIXTURE WIRES, SHALL BE
 PROTECTED AGAINST OVERCURRENT IN
 ACCORDANCE WITH THEIR AMPACITIES
 SPECIFIED IN 310.15, UNLESS OTHERWISE
 PERMITTED OR REQUIRED IN 240.4(A)
 THROUGH (G).
  
 21)NOTE:PLEASE SEE DISCONNECT SHOWN ON
 RISER DIAGRAM FOR PANEL "P", PLEASE
 PROVIDE INFORMATION FOR DISC SHOWN.
 SIZE, OCP, ETC 215.5
  
 22)NOTE: PLEASE SEE OCP/ AWG FOR FEED
 TO
 ERL FROM ERH. #12, W/ 30A OCP.
  
 23)NOTE: PLEASE SEE SEE MAX
 OVER-CURRENT
 PROTECTION FOR TRANSFORMERS IS 125%.
 PLEASE SEE NUMEROUS TRASNFROMERS SHOWN
 EXCEEDING 125% OCP.
 ERH< E3H/E3L, EH/EL ETC.450.3A
  
 24)NOTE: PLEASE SEE FC PANEL, SHOWN AS
 10A, WITH 100A FEED ?? MISPRINT?
 310.15,240.4 ETC
  
 25)NOTE: PLEASE SEE FEEDERS FOR MC-TH
 SHOWN AS OVERHEAD TO EQUIPMENT. PLEASE
 SEE 230.70 OF LOCAL AMENDMENTS WHICH
 REQUIRE CONCRETE ENCASEMENT FOR
 MORE-THAN 8' OF UNPROTECTED CONDUCTOR
 "INSIDE" THE BLDG.
 PLEASE SEE FEEDER SCHEDULE MENTIONS
 1200A FEEDER, YET NO INFORMATION IS
 GIVEN FOR SIZE AND TYPE.
  
 26)NOTE: PLEASE COMPLETE FEEDER
 SCHEDULE. SHOWS AMERAGE OF WHAT FEEDERS
 NEED TO BE , BUT NO SIZES ARE GIVEN FOR
 CONDUITS, CONDUCTORS, EQUIPMENT
 GROUNDING ETC
 215.5,215.24,250.122,310.16 ETC
  
 27)NOTE:PLEASE SEE EDPH REQUIRED TO
 HAVE
 A MCB FOR DISCONNECTING MENS FROM
 GENERATOR DP/ GEN.
 230.72,230.70 ETC.
 GEN DP LOCATION IS OVER 300' AWAY.
  
 28)NOTE: PLEASE VERFIY THE MAIN SINGLE
 OCP FOR FIRE PUMP. PLEASE SEE FIRE PUMP
 CONTROLLER SPECS MENTIONS, FACTORY SET
 AT LRC.(6X). YET, RISER SHOWS
 DISC(PREVIOUS COMMENT) AND GEN DP SHOWS
 OCP ALSO? VERIFY OF THERE IS OCP ON GEN
 TO GEN DP.
 THE OVERCURRENT PROTECTIVE DEVICE(S)
 SHALL BE SELECTED OR SET TO CARRY
 INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR
 CURRENT OF THE FIRE PUMP MOTOR(S) AND
 THE PRESSURE MAINTENANCE PUMP MOTOR(S)
 AND THE FULL-LOAD CURRENT OF THE
 ASSOCIATED FIRE PUMP ACCESSORY
 EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY.
 THE DISCONNECTING MEANS SHALL BE MARKED
 ?FIRE PUMP DISCONNECTING MEANS.? THE
 LETTERS SHALL BE AT LEAST 25 MM (1 IN.)
 IN HEIGHT, AND THEY SHALL BE VISIBLE
 WITHOUT OPENING ENCLOSURE DOORS OR
 COVERS.
 PLEASE SEE 695 FOR FIRE PUMP.
  
 29)NOTE: PLEASE SEE LOAD ON GENERATOR.
 PLANS INDICATE 1000KW AND 600KW, PLEASE
 CLARIFY WHICH ONE IS GOING TO BE
 INSTALLED.
 GEN LOAD IS NOW SHOWN EXCEEDING RATING
 OF GENERATOR. PLEASE
 PROVIDE INFORMATION ON MEANS OF
 AUTOMATIC SHEDDING.
 N EMERGENCY SYSTEM SHALL HAVE ADEQUATE
 CAPACITY AND RATING FOR ALL LOADS TO BE
 OPERATED SIMULTANEOUSLY. THE EMERGENCY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS.
 THE EMERGENCY SYSTEM MUST BE DESIGNED
 WITH ADEQUATE CAPACITY AND RATING TO
 SAFELY CARRY THE ENTIRE LOAD CONNECTED
 TO THE EMERGENCY SYSTEM AT ONE TIME. IT
 MUST BE CAPABLE OF RESTARTING EMERGENCY
 LOADS, SUCH AS MOTORS, THAT MAY HAVE
 STOPPED, AND IT MUST BE SUITABLE FOR
 THE
 AVAILABLE FAULT CURRENT. USING DEVICES
 THAT LIMIT THE AVAILABLE FAULT CURRENT
 IS ONE METHOD OF ACHIEVING SUITABILITY.
  
 THE ALTERNATE POWER SOURCE SHALL BE
 PERMITTED TO SUPPLY EMERGENCY, LEGALLY
 REQUIRED STANDBY, AND OPTIONAL STANDBY
 SYSTEM LOADS WHERE AUTOMATIC SELECTIVE
 LOAD PICKUP AND LOAD SHEDDING IS
 PROVIDED AS NEEDED TO ENSURE ADEQUATE
 POWER TO (1) THE EMERGENCY CIRCUITS,
 (2)
 THE LEGALLY REQUIRED STANDBY CIRCUITS,
 AND (3) THE OPTIONAL STANDBY CIRCUITS,
 IN THAT ORDER OF PRIORITY. THE
 ALTERNATE
 POWER SOURCE SHALL BE PERMITTED TO BE
 USED FOR PEAK LOAD SHAVING, PROVIDED
 THE
 ABOVE CONDITIONS ARE MET.
 PLEASE ALSO SEE ALL OF 702.5 OPTIONAL
 STANDBY SYSTEM SHALL HAVE ADEQUATE
 CAPACITY AND RATING FOR THE SUPPLY OF
 ALL EQUIPMENT INTENDED TO BE OPERATED
 AT
 ONE TIME. OPTIONAL STANDBY SYSTEM
 EQUIPMENT SHALL BE SUITABLE FOR THE
 MAXIMUM AVAILABLE FAULT CURRENT AT ITS
 TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE
 SYSTEM.
 PROVIDE INFORMATION ON AUTO SHEDDING
 FOR
 ELEVATORS.
  
 30)NOTE: PLEASE SEE
 230.95,240.13,700.7D
 FOR MSBH, MSBE, EDPH,ETC.GROUND-FAULT
 PROTECTION OF EQUIPMENT SHALL BE
 PROVIDED FOR SOLIDLY GROUNDED WYE
 ELECTRICAL SERVICES OF MORE THAN 150
 VOLTS TO GROUND BUT NOT EXCEEDING 600
 VOLTS PHASE-TO-PHASE FOR EACH SERVICE
 DISCONNECT RATED 1000 AMPERES OR MORE..
 TO INDICATE A GROUND FAULT IN SOLIDLY
 GROUNDED WYE EMERGENCY SYSTEMS OF MORE
 THAN 150 VOLTS TO GROUND AND
 CIRCUIT-PROTECTIVE DEVICES RATED 1000
 AMPERES OR MORE. THE SENSOR FOR THE
 GROUND-FAULT SIGNAL DEVICES SHALL BE
 LOCATED AT, OR AHEAD OF, THE MAIN
 SYSTEM
 DISCONNECTING MEANS FOR THE EMERGENCY
 SOURCE, AND THE MAXIMUM SETTING OF THE
 SIGNAL DEVICES SHALL BE FOR A
 GROUND-FAULT CURRENT OF 1200 AMPERES.
 INSTRUCTIONS ON THE COURSE OF ACTION TO
 BE TAKEN IN EVENT OF INDICATED GROUND
 FAULT SHALL BE LOCATED AT OR NEAR THE
 SENSOR LOCATION.
  
 31)NOTE: PLEASE SEE "MAIN" EQUIPMENT
 SHOWN WITH MORE THAN 6-SPACES AS MLO.
 PLEASE ALSO SEE SOME OTHER EQUIPMENT
 NOT
 CLARIFIED WITH # OF SPACES AND SHOWN AS
 MLO. MSBH, EDPH, MSBE, HE SERVICE
 DISCONNECTING MEANS FOR EACH SERVICE
 PERMITTED BY 230.2, OR FOR EACH SET OF
 SERVICE-ENTRANCE CONDUCTORS PERMITTED
 BY
 230.40, EXCEPTION NOS. 1, 3, 4, OR 5,
 SHALL CONSIST OF NOT MORE THAN SIX
 SWITCHES OR SETS OF CIRCUIT BREAKERS,
 OR
 A COMBINATION OF NOT MORE THAN SIX
 SWITCHES AND SETS OF CIRCUIT BREAKERS,
 MOUNTED IN A SINGLE ENCLOSURE, IN A
 GROUP OF SEPARATE ENCLOSURES, OR IN OR
 ON A SWITCHBOARD. THERE SHALL BE NO
 MORE
 THAN SIX SETS OF DISCONNECTS PER
 SERVICE
 GROUPED IN ANY ONE LOCATION. FOR THE
 PURPOSE OF THIS SECTION, DISCONNECTING
 MEANS USED SOLELY FOR POWER MONITORING
 EQUIPMENT, OR THE CONTROL CIRCUIT OF
 THE
 GROUND-FAULT PROTECTION SYSTEM OR
 POWER-OPERABLE SERVICE DISCONNECTING
 MEANS, INSTALLED AS PART OF THE LISTED
 EQUIPMENT, SHALL NOT BE CONSIDERED A
 SERVICE DISCONNECTING MEANS.
  
 32)NOTE: PLEASE SEE 700.9D1 EMERGENCY
 SYSTEMS SHALL MEET THE FOLLOWING
 ADDITIONAL REQUIREMENTS IN ASSEMBLY
 OCCUPANCIES FOR NOT LESS THAN 1000
 PERSONS OR IN BUILDINGS ABOVE 23 M (75
 FT) IN HEIGHT WITH ANY OF THE FOLLOWING
 OCCUPANCY CLASSES: ASSEMBLY,
 EDUCATIONAL, RESIDENTIAL, DETENTION AND
 CORRECTIONAL, BUSINESS, AND MERCANTILE.
 PLEASE SEE RISER.
  
 33)NOTE: PLEASE PROVIDE NOTE FOR
 INFORMATION ON GENERATOR TO WHEATHER
 THIS IS A SEP DERIVED GEN.
 250.30,702.8A
 SIGN SHALL BE PLACED AT THE
 SERVICE-ENTRANCE EQUIPMENT THAT
 INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES.
 A SIGN SHALL NOT BE REQUIRED FOR
 INDIVIDUAL UNIT EQUIPMENT FOR STANDBY
 ILLUMINATION.
 PLEASE SEE WHERE THE GROUNDED CIRCUIT
 CONDUCTOR CONNECTED TO THE OPTIONAL
 STANDBY POWER SOURCE IS CONNECTED TO A
 GROUNDING ELECTRODE CONDUCTOR AT A
 LOCATION REMOTE FROM THE OPTIONAL
 STANDBY POWER SOURCE, THERE SHALL BE A
 SIGN AT THE GROUNDING LOCATION THAT
 SHALL IDENTIFY ALL OPTIONAL STANDBY
 POWER AND NORMAL SOURCES CONNECTED AT
 THAT LOCATION. PLANS WILL NEED TO
 SPECIFY IF SEP DERIVED OR NOT.
  
 34)NOTE: PLEASE SEE 445.13 FOR FEEDER
 FROM GEN TO GDP. THE AMPACITY OF THE
 CONDUCTORS FROM THE GENERATOR TERMINALS
 TO THE FIRST DISTRIBUTION DEVICE(S)
 CONTAINING OVERCURRENT PROTECTION SHALL
 NOT BE LESS THAN 115 PERCENT OF THE
 NAMEPLATE CURRENT RATING OF THE
 GENERATOR.
  
 35)NOTE: PLEASE CORRELATE FEEDER
 SCHEDULE AND GDP. ONE SHOWS 4/0'S 225A
 FEED, AND FEEDER SCHEDULE INDICATES
 400A
 FEEDER? (F-11). PLEASE SEE PREVIOUS
 NOTE
 ON THIS REVIEW FOR CONDUCTORS/CONDUITS
 TO BE ON FEEDER SCHEDULE.
  
 36)NOTE:PLEASE PROVIDE NOTE ON PLANS
 FOR
 EELECTRICAL CONTRACTOR TO PROVIDE
 SIGNAGE FOR ALL DISC MEANS, LOCATIONS
 FIRE-PUMP ETC. A "MAP" "LAYOUT" OF BLDG
 WILL BE REQUIRED IN FIRE COMMAND RMM
 FOR
 ALL LOCATIONS AS WELL AS EACH LOCATION
 OF THESE DISC'S ETC.
 230.2E, 695,700.2,700 ETC
  
 37)NOTE: PLEASE SEE NUMEROUS AREAS ON
 SOME PANEL SCHEDUL WHERE THE OCP
 EXCEEDS
 RATING OF AWG. PLEASE SEE 240.4 FOR
 EXCEPTIONS WHERE OCP MAY EXCEED AWG
 RATING FOR NEXT SIZE UP AND SOME MOTOR
 LOADS. SOME OF THESE HAVE BEEN REDLINED
 AT AREAS OF CONCERN.
  
 38)NOTE: PLEASE SEE NOTE#5 ON UNIT
 "PANEL SCHEDULE NOTES" MENTIONS TO BE
 LOCAK OFF DEVICE, HOWEVER THIS COULD
 NOT
 BE LOCATED ON PANEL SCHEDULES?
 PLEASE NOTE: ANY PROPOSED LOCK-OFF TYPE
 DEVICES/ BRKRS WILL BE REQUIRED TO BE
 REVIEWED AND APPROVED FOR USE AS
 DISCONNECTING MEANS BYAHJ BEFORE
 INSTALLATION.
  
 39)NOTE: PLEASE PROVIDE WIND-LOADING
 FOR
 PROPOSED LIGHT-POLES AND LT-ING
 FIXTURES. THIS IS REQUIRED AT THIS
 TIME.
 PLEASE ALSO PROVIDE NOTE AR LIGHTING
 DETAIL FOR FBC 140 MPH.
  
 40)NOTE: PLEASE SEE POOL IS REQUIRED TO
 BE UNDER SEPARATE PERMIT. IF THERE IS
 GOING TO BE ANY "NIGHT-TIME" (AFTER
 DUSK) SWIMMING, PHOTOMETRICS WILL BE
 REQUIRED TO BE SUBMITTED TO PALM BEACH
 COUNTY HEALTH DEPT FOR REVIEW BEFORE
 SUBMITTING TO THE CITY OF WEST PALM
 BEACH. THIS IS ONLY A NOTE GIVEN AT
 THIS
 TIME.
  
 41)NOTE:PLEASE SHOW CIRCUTING ON PLANS
 FOR ALL UNITS. THESE ARE SHOWN W/OUT
 CIRCUITING AT THIS TIME AND CAN NOT BE
 REVIEWED FOR CODE COMPLIANCE.
 215.5
  
 42)NOTE:PLEASE PROVIDE NOTE ON PLANS
 FOR
 REQUIRED SD PLACEMENT> PLEASE SEE
 NFPA-72 8-1.4.2 FOR SD'S TO BE A MIN OF
 3' FROM BATH DRS, KITCHEN DRS AND 20'
 FROM COOKING APPLIANCES WITH
 EXCEPTIONS.
  
  
 43)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE THERE ARE A COUPLE MISSING.
  
 44)NOTE: PLEASE SEE 240.24E FOR PANEL
 LOCATIONS IN DWELLING UNITS AND GUEST
 ROOMS OF HOTELS AND MOTELS, OVERCURRENT
 DEVICES, OTHER THAN SUPPLEMENTARY
 OVERCURRENT PROTECTION, SHALL NOT BE
 LOCATED IN BATHROOMS
  
 45)NOTE:PLEASE SEE 210.52D, 210.11C3
 FOR
 REQUIRED LOCATIONS OF GFI IN BATHRMS.
 THESE ARE REQUIRED TO BE WITHIN 3' OF
 LAV/SINK EDGE. IT IS NOT PERMITED TO
 CROSS OVER ONE SINK TO MEET THE
 REQUIREMNTS OF SECOND LAV. PLEASE
 EITHER
 ADD AN ADDITIONAL GFI OR MOVE EXISTING
 SHOWN TO BE IN CENTER OF THE TWO.
  
 46)NOTE: PLEASE CLARIFY REQUIREMENST OF
 210.70 FOR UNITS WHICH HAVE GRADE LEVEL
 ACCESS.FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH
 ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES
 OR EXITS WITH GRADE LEVEL ACCESS.
  
 47)NOTE: PLEASE SEE SOME UNIT LAYOUT
 COULD NOT BE LOCATED ON PLANS. THESE
 UNITS ARE SHOWN FOR UNIT TYPE,(B-2,
 P-1,
 P-3 ETC) BUT DI NOT SEEM TO HAVE ANY
 ELECTRICAL SHOWN. THEY APPEAR TO BE
 BLANK? 215.5
  
 48)NOTE: PLEASE PROVIDE ROOM
 DESIGNATION
 ON PLANS.
  
 **** PLEASE SEE ONE SET OF PLANS HAVE
 BEEN REDLINED WITH MOST OF THE AREAS
 WHICH HAVE BEEN NOTED ON THE ABOVE
 COMMENTS. THESE REDLINES MAY HELP WITH
 SOME OF THE NOTES.
  
 **PLEASE SEE ANY POSSIBLE NOTES FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 **PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND INSERT ONLY NEW REVISED
 SHEETS INTO THREE COMPLETE SETS FOR
 REVIEW AND STMAPING. ONE SET OF OLD
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-12-07 00:00:00ONE SET IN ELEC FOR REVIEW.
 NOTES TO FOLLOW.