2005-07-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED 7/5/05
 FOR ENTRY PORCH ARCH DETAIL AND REAR
 PORCH BEAM SUPPORT COLUMNS
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.2ARCHITECT'S SIGNATURE
 AND SEAL.NEITHER THE SUBMITTED LETTER
 OR THE 8.5"X 11" SKETCH SHEETS CARRY
 ORIGINAL SIGNATURE, RAISED SEAL, OR
 PRINTED LICENSE NUMBER OF JAMES E.
 GILGENBACH.
  
 2) 481.219(2) F.S.CERTIFICATE OF
 AUTHORIZATION.JAMES A. GILGENBACH
 ARCHITECTURE & PLANNING DOES NOT HAVE A
 CERTIFICATE OF AUTHORIZATION SO THE
 WORDS "ARCHITECTURE & PLANNING" MUST
 DELETED FROM THE TITLE BLOCK AND
 LETTERHEAD.THEY WERE DELETED ON THE
 PERMIT APPROVED SET OF PLANS.THIS
 COMMENT HAS BEEN MADE THREE TIMES
 ALREADY ON THE PERMIT APPLICATION.THE
 ARCHITECT MUST CEASE USING THE WORDS
 "ARCHITECTURE & PLANNING" IN THIS WAY OR
 THE BOARD OF ARCHITECTURE WILL BE
 INFORMED.
  
 3) FBC* 104.2THE SUBMITTED 8.5"X 11"
 SKETCH SHEET SHOWING A STEEL COLUMN DOES
 NOT CORRELATE WITH THE PERMIT APPROVED
 PLANS.THOSE PLANS DO NOT APPEAR TO
 SHOW A STEEL COLUMN OR INTERIOR PAD BASE
 AND WOULD NEED TO BE REVISED TO SHOW THE
 LOCATION OF THE COLUMN.IF THE LOCATION
 IS NOT SHOWN, THE COLUMN DETAILS CANNOT
 BE REVIEWED/STAMPED.ALSO THE COLUMN
 DETAIL SHEET DOES NOT HAVE A PROJECT
 SPECIFIC TITLE BLOCK OR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE SHEET.IF THAT PERSON IS NOT THE
 ARCHITECT OF RECORD THEN THE ARCHITECT
 MUST REVIEW, STAMP AND INITIAL/DATE THE
 PLAN AS BEING 'REVIEWED'. (REF FBC*
 104.2.1 AND 61G1-16.004FL. ADMIN.
 CODE.)
  
 4) FBC* 104.2.1THE REVISIONS DESCRIBED
 IN THE LETTER MUST BE DRAWN ON THE PLANS
 AND THE REVISED PLANS SUBMITTED FOR
 REVIEW AND RECORDS.
  
 5) FBC* 104.2.1 ON WALL FRAMING DETAILS
 A AND B, SOME OF THE ANCHOR AND STRAP
 REFERENCES DO NOT STATE THE SIZE AND
 NUMBER OF NAILS TO BE USED.ADD NOTES
 TO SPECIFY THE NUMBER AND TYPE OF
 FASTENERS FOR EACH STRAP/TIE.ALSO,
 THESE DETAILS MAKE A TOTAL OF FIVE
 REFERENCES TO EITHER USPRT24T, USP
 RT24F OR USP RT18T TIES.PLEASE NOTE
 THAT WHILE THESE PARTICULAR TIES ARE
 REFERENCED IN THE 2004 USP CATALOGUE,
 THEY DO NOT APPEAR IN THE 2005 CATALOGUE
 SO AVAILABILITY MAY BE LIMITED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN