Plan Review Notes
Plan Review Notes For Permit 04110927
Permit Number 04110927
Review Stop B
Sequence Number 6
Notes
Date Text
2005-04-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/8/05 FOR SHEETS
 A1, A2, A3, A4 AND A5
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 104.2.1.3THE USE OF 'WITE-OUT'
 OR ANY OTHER TYPE OF COVER-UP CORRECTION
 FLUID/TAPE IS NOT APPROPRIATE FOR PLANS
 SUBMITTED FOR PERMITTING PURPOSES.
 SUBMIT NEW PLANS.
  
 2) FBC 104.2.2EACH HAND-DRAWN CHANGE
 MADE TO COPIES OF PLANS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER MUST
 BE SIGNED AND DATED BY THAT DESIGNER OF
 RECORD.
  
 3) FBC 1606.1.3SHEET A3, ROOF FRAMING
 PLAN.THE BEARING WALL DETAIL C/2 ON
 SHEET A2 REFERS TO GALV. METAL ANCHOR
 STRAPS AT EACH TRUSS.THERE ARE NO
 TRUSS ANCHORS SHOWN FOR THIS LOCATION ON
 SHEET A3, ROOF FRAMING PLAN.AMEND THE
 ROOF FRAMING PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]