| Plan Review Notes For Permit 04110927 |
| Permit Number |
04110927 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-04-21 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | REVISION SUBMITTED ON 4/8/05 FOR SHEETS | | | A1, A2, A3, A4 AND A5 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC 104.2.1.3THE USE OF 'WITE-OUT' | | | OR ANY OTHER TYPE OF COVER-UP CORRECTION | | | FLUID/TAPE IS NOT APPROPRIATE FOR PLANS | | | SUBMITTED FOR PERMITTING PURPOSES. | | | SUBMIT NEW PLANS. | | | | | | 2) FBC 104.2.2EACH HAND-DRAWN CHANGE | | | MADE TO COPIES OF PLANS SIGNED AND | | | SEALED BY AN ARCHITECT OR ENGINEER MUST | | | BE SIGNED AND DATED BY THAT DESIGNER OF | | | RECORD. | | | | | | 3) FBC 1606.1.3SHEET A3, ROOF FRAMING | | | PLAN.THE BEARING WALL DETAIL C/2 ON | | | SHEET A2 REFERS TO GALV. METAL ANCHOR | | | STRAPS AT EACH TRUSS.THERE ARE NO | | | TRUSS ANCHORS SHOWN FOR THIS LOCATION ON | | | SHEET A3, ROOF FRAMING PLAN.AMEND THE | | | ROOF FRAMING PLAN. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|