Plan Review Notes
Plan Review Notes For Permit 04110927
Permit Number 04110927
Review Stop E
Sequence Number 4
Notes
Date Text
2005-06-07 00:00:00************** NOTES REDLINED *********
  
  
 *** PLEASE SEE BELOW FOR THE SAME ITEM
 PREVIOUSLY NOTED ON TWO PREVIOUS REVIEWS
 WHICH WAS NOT CORRECTED.
 THIS WAS REDLINED ONCE AGAIN.
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO MAIN/FIRST
 MEANS OF DISCONNETC. PLEASE SEE
 250.6,250.24, AN EQUIPMENT GROUNDING
 CONDUCTOR SHALL NOT BE INSTALLED FROM
 METER TO FIRST MEANS OF DISCONNECT.
  
 PLEASE SEE REVISION SHEET DID NOT
 CONTAIN A CHECK OFF FOR PLUMB REVSION,
 YET PLUMB RISER IS ON ELEC SHEET. THIS
 WAS CROSSED OUT.