Plan Review Notes
Plan Review Notes For Permit 04110927
Permit Number 04110927
Review Stop E
Sequence Number 3
Notes
Date Text
2005-04-11 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE SEE HAND-DRAWN CHANGES
 ARE NOT PERMITTED TO PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ARCHITECT
 OR ENGINEER.
 FS 481.221, 471.025
 PLEASE SEE ONLY HAND DRAWN CHANGES ARE
 PERMITTED, HOWEVER "EACH" CHANGE MUST BE
 SIGNED AND DATED.
 PLEASE ALSO SEE BLDG REVIEW NOTES,
 "WHITE-OUT" IS NOT PERMITTED ON PLANS.
  
  
 2)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO MAIN/FIRST
 MEANS OF DISCONNETC. PLEASE SEE
 250.6,250.24, AN EQUIPMENT GROUNDING
 CONDUCTOR SHALL NOT BE INSTALLED.
  
 3)NOTE: PLEASE SEE PLANS INLCUDE PLUMB
 RISER, IF THIS IS NOT PART OF
 CHANGES/REVISION, PLEASE CROSS OUT AS
 "NIC" ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  