2005-02-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/14/05:
  
 10) STORM PANELS.SUBMITTAL OF THE
 CORRECT SCHEDULE IS NOTED.SHUTTER
 PANEL #19 HAS A 104" SPAN AND A WIND
 PRESSURE OF -36 PSF.THIS EXCEEDS THE
 MAXIMUM DESIGN PRESSURE LISTED, FOR
 THAT
 SPAN, ON THE 'MAX SPAN TABLE' ON THE
 PRODUCT APPROVAL NOA DRAWINF SHEET 2 OF
 3.AMEND THE SCHEDULE TO SHOW SPAN IN
 THE SHORTER DIRECTION OR SUBMIT A
 PRODUCT APPROVAL FOR PANELS WITH
 ADEQUATE SPAN CAPABILITY.ALSO, THE
 'BUCK OPENING SIZES' STATED ON THE
 SCHEDULE ARE SMALLER THAN THE OPENING
 SIZE GIVEN ON PLAN SHEET A1 FOR THE
 FOLLOWING STORM PANEL NUMBERS:
 PANEL #4 - STATED 54" SHOULD BE 56"
 PANEL #8 - STATED 95" SHOULD BE 120"
 PANEL #10 - STATED 54" SHOULD BE 56".
 THE PROPOSED SHUTTERS WILL STILL WORK
 FOR THESE CORRECTED OPENING SIZES.
 AMEND THE SCHEDULE.
  
 11) EXTERIOR SWINGING DOORS.THIS
 COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED. AT LEAST ONE OF THE EXTERIOR
 DOORS SHALL BE IMPACT RATED OR
 NON-GLAZED SO THAT ENTRY TO THE HOUSE
 IS
 STILL POSSIBLE AFTER INSTALLING ALL
 REQUIRED SHUTTERS. AMEND THE PLANS OR
 SUBMIT PRODUCT APPROVALS FOR IMPACT
 RATED DOORS.
  
 17) FIXED WINDOWS.THIS COMMENT HAS
 NOT
 BEEN ADDRESSED.THE AAMA TEST REPORT
 01-44553.02, ATTACHED TO THE SUBMITTED
 SIMONTON FIXED WINDOW STATEWIDE PRODUCT
 APPROVAL (NUMBER FL178), IS FOR A WINDOW
 WITH A SMALLER DIMENSION OF 3'-11".
 THIS IS LESS THAN THE SIZE OF THE ARCHED
 TRANSOM ABOVE THE FRONT ENTRY DOOR.
 ALSO THE CURRENT STATEWIDE PRODUCT
 APPROVAL LISTING FOR FL178 HAS CHANGED
 SUBSTANTIALLY FROM THE VERSIOPN
 SUBMITTED.IT IS NOW NUMBER FL178-R1.
 SUBMIT TWO UP-TO-DATE COPIES OF
 FL178-R1, MARKED TO SHOW WHICH PRODUCT
 MODEL/NAME IS PROPOSED.
  
 18) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED AS THE
 DESCRIBED IMPROVEMENT OR CONSTRUCTION
 WAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING.YOU ARE ADVISED TO RECORD
 THE NOTICE OF COMMENCEMENT AT THE TIME
 OF PERMIT ISSUE TO AVOID POSSIBLE
 EXPIRATION.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
  
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]