| 2005-02-08 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 1/14/05: |
| | |
| | 10) STORM PANELS.SUBMITTAL OF THE |
| | CORRECT SCHEDULE IS NOTED.SHUTTER |
| | PANEL #19 HAS A 104" SPAN AND A WIND |
| | PRESSURE OF -36 PSF.THIS EXCEEDS THE |
| | MAXIMUM DESIGN PRESSURE LISTED, FOR |
| | THAT |
| | SPAN, ON THE 'MAX SPAN TABLE' ON THE |
| | PRODUCT APPROVAL NOA DRAWINF SHEET 2 OF |
| | 3.AMEND THE SCHEDULE TO SHOW SPAN IN |
| | THE SHORTER DIRECTION OR SUBMIT A |
| | PRODUCT APPROVAL FOR PANELS WITH |
| | ADEQUATE SPAN CAPABILITY.ALSO, THE |
| | 'BUCK OPENING SIZES' STATED ON THE |
| | SCHEDULE ARE SMALLER THAN THE OPENING |
| | SIZE GIVEN ON PLAN SHEET A1 FOR THE |
| | FOLLOWING STORM PANEL NUMBERS: |
| | PANEL #4 - STATED 54" SHOULD BE 56" |
| | PANEL #8 - STATED 95" SHOULD BE 120" |
| | PANEL #10 - STATED 54" SHOULD BE 56". |
| | THE PROPOSED SHUTTERS WILL STILL WORK |
| | FOR THESE CORRECTED OPENING SIZES. |
| | AMEND THE SCHEDULE. |
| | |
| | 11) EXTERIOR SWINGING DOORS.THIS |
| | COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED. AT LEAST ONE OF THE EXTERIOR |
| | DOORS SHALL BE IMPACT RATED OR |
| | NON-GLAZED SO THAT ENTRY TO THE HOUSE |
| | IS |
| | STILL POSSIBLE AFTER INSTALLING ALL |
| | REQUIRED SHUTTERS. AMEND THE PLANS OR |
| | SUBMIT PRODUCT APPROVALS FOR IMPACT |
| | RATED DOORS. |
| | |
| | 17) FIXED WINDOWS.THIS COMMENT HAS |
| | NOT |
| | BEEN ADDRESSED.THE AAMA TEST REPORT |
| | 01-44553.02, ATTACHED TO THE SUBMITTED |
| | SIMONTON FIXED WINDOW STATEWIDE PRODUCT |
| | APPROVAL (NUMBER FL178), IS FOR A WINDOW |
| | WITH A SMALLER DIMENSION OF 3'-11". |
| | THIS IS LESS THAN THE SIZE OF THE ARCHED |
| | TRANSOM ABOVE THE FRONT ENTRY DOOR. |
| | ALSO THE CURRENT STATEWIDE PRODUCT |
| | APPROVAL LISTING FOR FL178 HAS CHANGED |
| | SUBSTANTIALLY FROM THE VERSIOPN |
| | SUBMITTED.IT IS NOW NUMBER FL178-R1. |
| | SUBMIT TWO UP-TO-DATE COPIES OF |
| | FL178-R1, MARKED TO SHOW WHICH PRODUCT |
| | MODEL/NAME IS PROPOSED. |
| | |
| | 18) 713.13(2) F.S.THE NOTICE OF |
| | COMMENCEMENT MUST BE RE-RECORDED AS THE |
| | DESCRIBED IMPROVEMENT OR CONSTRUCTION |
| | WAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING.YOU ARE ADVISED TO RECORD |
| | THE NOTICE OF COMMENCEMENT AT THE TIME |
| | OF PERMIT ISSUE TO AVOID POSSIBLE |
| | EXPIRATION. |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |