Plan Review Notes
Plan Review Notes For Permit 04110927
Permit Number 04110927
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00****** UNSAT ******
  
 1)NOTE: THE LAUNDRY CIRCUIT CALCULATION
 MUST COMPLY WITH 220.116(B).(1500 VA).
  
 2)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC
 NOTE MNETIONS RECEPTS ONLY.
  
 3)NOTE: PLEASE MOVE SD "INTO" MASTER
 BEDRM. NFPA-72 8-1.4.1.6.2
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.122,250.24.
  
 5)NOTE: PLEASE SEE PANEL "B" INDICATES A
 WHIRLPOOL TUB, YET PLANS DO NOT INDICATE
 ELECTRICAL FOR THIS.
  
 6)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 ONE SET/COPY OF OLD SHOULD BE SUBMITTED
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]