| 2004-11-23 00:00:00 | ****** UNSAT ****** |
| | |
| | 1)NOTE: THE LAUNDRY CIRCUIT CALCULATION |
| | MUST COMPLY WITH 220.116(B).(1500 VA). |
| | |
| | 2)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC |
| | NOTE MNETIONS RECEPTS ONLY. |
| | |
| | 3)NOTE: PLEASE MOVE SD "INTO" MASTER |
| | BEDRM. NFPA-72 8-1.4.1.6.2 |
| | |
| | 4)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAINS TO |
| | PANELS. |
| | 250.110,250.122,250.24. |
| | |
| | 5)NOTE: PLEASE SEE PANEL "B" INDICATES A |
| | WHIRLPOOL TUB, YET PLANS DO NOT INDICATE |
| | ELECTRICAL FOR THIS. |
| | |
| | 6)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS FOR |
| | REVIEW AND STAMPING. |
| | ONE SET/COPY OF OLD SHOULD BE SUBMITTED |
| | FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |