| Plan Review Notes For Permit 04110897 |
| Permit Number |
04110897 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-24 00:00:00 | ************ UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | FOR STRUCTUAL COMMENTS. | | | | | | 2)NOTE: PLEASE SEE | | | 230.70,230.72,230.76,230.79 | | | GENERATOR MAY NOT BE PLACED ON ROOF. | | | MAIN/MEANS IF DISCONNECT MUST BE ON | | | GROUND LEVEL FOR FIRE DEPT SHUT-DOWN AND | | | IN CLOSE PROXIMITY TO EXISTING | | | ELECTRICAL EQUIPMENT. | | | | | | 3)NOTE: PELASE SUBMIT COMPLETE PACKAGE | | | ON GENERATOR AND ALL EQUIPMENT.(TRANSFER | | | SWITCH? ETC. | | | ALL SPECS TO SHOW ALL LISTING(S) BY A | | | NRTL. | | | | | | 4)NOTE: PLEASE SEE FBC 104.6.5 FOR | | | VALUATION OF PERMIT. THE VALUE APPLIED | | | AT $2K IS WAY LOW. PLEASE ADJUST. | | | REQUIRED TO INCLUDE VALUE FOR COMPLETE | | | SCOPE OF WORK,ALL LABOR AND MATERIALS | | | WEATHER OWNER SUPPLIED OR NOT. | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) THAT WILL AFFECT THIS | | | PROJECT.*** | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|