2004-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110897
 ADD: 2800 N FLAGLER DR
 CONT: JOHNATHAN CROMPTON
 TEL: (561)722-4020
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE ADDITIONAL INFORMATION, THE
 PREMIT APPLICATION DOESN'T INDICATE IF
 THIS IS A REPLACEMENT OR NEW GENERATOR.
 INDICATE HOW THE GENERATOR WILL TIE INTO
 THE REQUIRED FIRE CENTRAL COMMAND
 STATION SEE 412.4.,412.7.1.1 AND
 412.7.1.2.
  
 2) THE DRAWING SUBMITTED INDICATES THAT
 THE GENERATOR WILL SIT ON TOP OF A 10
 STORY BLDG. PROVIDE DETAILS ON THE
 EXISTING STEEL WHICH THE NEW GENERATOR
 IS TO BE ATTACHED. PROVIDE THE
 ATTACHMENT TO THE STEEL, WITH ASSOCIATED
 POSITIVE AND NEGATIVE PRESSURES, THE
 BLDG IS OVER 60' IN HEIGHT DESIGN TO
 ASCE 7-98.
  
 3) THE VALUATION ON THE PERMIT IS LOW,
 THE GENERATOR CAN'T BE BOUGHT FOR THE
 AMOUNT STATED!!!!!!!!! PROVIDE WHAT WORK
 IS TO BE COMPLETED?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  