| 2004-12-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04110897 |
| | ADD: 2800 N FLAGLER DR |
| | CONT: JOHNATHAN CROMPTON |
| | TEL: (561)722-4020 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE ADDITIONAL INFORMATION, THE |
| | PREMIT APPLICATION DOESN'T INDICATE IF |
| | THIS IS A REPLACEMENT OR NEW GENERATOR. |
| | INDICATE HOW THE GENERATOR WILL TIE INTO |
| | THE REQUIRED FIRE CENTRAL COMMAND |
| | STATION SEE 412.4.,412.7.1.1 AND |
| | 412.7.1.2. |
| | |
| | 2) THE DRAWING SUBMITTED INDICATES THAT |
| | THE GENERATOR WILL SIT ON TOP OF A 10 |
| | STORY BLDG. PROVIDE DETAILS ON THE |
| | EXISTING STEEL WHICH THE NEW GENERATOR |
| | IS TO BE ATTACHED. PROVIDE THE |
| | ATTACHMENT TO THE STEEL, WITH ASSOCIATED |
| | POSITIVE AND NEGATIVE PRESSURES, THE |
| | BLDG IS OVER 60' IN HEIGHT DESIGN TO |
| | ASCE 7-98. |
| | |
| | 3) THE VALUATION ON THE PERMIT IS LOW, |
| | THE GENERATOR CAN'T BE BOUGHT FOR THE |
| | AMOUNT STATED!!!!!!!!! PROVIDE WHAT WORK |
| | IS TO BE COMPLETED? |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |