Plan Review Notes
Plan Review Notes For Permit 04110890
Permit Number 04110890
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE PROVIDE A LOAD
 CALCULATION FOR EXISTING 4000A MAIN.
 220.
 LOADS SHOWN SEEM TO EXCEED RATING OF
 EQUIPMENT. ???
 PLEASE ALSO SEE THESE MAINS ON ORIGINAL
 PLANS WERE CLOSE TO MAX LOAD.
 215.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  