Plan Review Notes
Plan Review Notes For Permit 04110889
Permit Number 04110889
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE VERIFY REQUIRED SHOW
 WINDOW RECEPTS? 210.62
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM PANEL "B" TO "B-1".
 250.110,250.122
  
 3)NOTE: PLEASE SEE MISSING INFORMATION
 ON ARCH'S TITLE BLOCK REQUIRED PER
 FAC 61G1-16.004 . LICENSE #'S REQUIRED
 ALSO PER FS 481.219
 THIS COMMENT IS FOR ALL TRADES AND ALL
 TRADES WHETHER OR NOT COMMENT IS MADE
 BY
 OTHER REVIEWER(S).
  
 4)NOTE: PLEASE SEE PLANS/COVER SHEET
 REFERENCES THE 1999 NEC. PLEASE SEE WE
 ARE UNDER THE 2002 NEC.
 ADOPTED 7/1/2003
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]