| 2004-12-22 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) 713.13 F.S.A NOTICE OF |
| | COMMENCEMENT SHALL BE RECORDED AT PALM |
| | BEACH COUNTY COURTHOUSE AND A COPY |
| | SUBMITTED TO THIS OFFICE BEFORE A PERMIT |
| | CAN BE ISSUED. BLANK FORMS ARE AVAILABLE |
| | FROM THIS OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST |
| | BE RE-RECORDED IF THE DESCRIBED |
| | IMPROVEMENT OR CONSTRUCTION IS NOT |
| | COMMENCED WITHIN 90 DAYS OF RECORDING. |
| | |
| | 2) 61G1-16.004FL. ADMIN. CODE.PLANS |
| | PREPARED BY A REGISTERED ARCHITECT |
| | SHALL |
| | INCLUDE A TITLE BLOCK WITH THE PRINTED |
| | NAME OF THE ARCHITECT SEALING THE |
| | PLANS. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 3) 481.219 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING |
| | ARCHITECTURAL SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION (COA#) |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | NOTE:DBPR RECORDS SHOW A COA# OF |
| | AA26000848 FOR A 'DOING BUSINESS UNDER' |
| | (DBA) NAME OF NEXUSARCHITECTURE, INC. |
| | BUT THE PLANS SHOW NEXUS DESIGN GROUP, |
| | LLC.THE PLANS SHALL REFLECT THE NAME |
| | OF THE LICENSED FIRM. |
| | |
| | 4) FBC 13-103.1.2BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHITECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 5) FBC 1005.7.3SHEET A-1, MEZZANINE. |
| | AS THE EGRESS STAIRWAY FROM THE |
| | MEZZANINE IS OPEN AND DESCENDS INTO THE |
| | FIRST FLOOR ROOM, THE SPACE BENEATH THE |
| | MEZZANINE IS ONLY PERMITTED TO BE |
| | ENCLOSED IF IT IS PROTECTED THOUGHOUT |
| | BY |
| | SMOKE DETECTION, IN ACCORDANCE WITH |
| | NFPA 72, THAT SOUNDS AN ALARM ON THE |
| | MEZZANINE.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 6) FBC 1608.2.1SHEET A-1, THE |
| | HANDRAIL SHALL BE DESIGNED AND |
| | CONSTRUCTED FOR A CONCENTRATED LOAD OF |
| | 200 LB AND A LINE LOAD OF 50 PLF.THESE |
| | LOADS SHALL NOT BE APPLIED |
| | SIMULTANEOUSLY BUT SHALL BE APPLIED |
| | INDIVIDUALLY AT ANY POINT, AND IN ANY |
| | DIRECTION, TO PRODUCE MAXIMUM STRESS IN |
| | EACH OF THE COMPONENTS OR SUPPORTS. |
| | AMEND/ANNOTATE THE PLANS TO SPECIFY |
| | THESE LOADS. IT IS NOTED THAT THE |
| | ARCHITECTURAL PLANS REFER TO THE |
| | STRUCTURAL PLANS AND VICE VERSA, BUT |
| | NEITHER PLAN PROVIDES DETAILS. |
| | |
| | 7) FBC 1608.2.2 SHEET A-1, THE |
| | GUARDRAIL SHALL BE DESIGNED AND |
| | CONSTRUCTED FOR A CONCENTRATED LOAD OF |
| | 200 LB APPLIED IN ANY DIRECTION AT THE |
| | TOP OF THE GUARDRAIL, A CONCENTRATED |
| | HORIZONTAL LOAD OF 200 LB APPLIED ON A 1 |
| | SQ FT AREA AT ANY POINT, AND A LINE LOAD |
| | OF 50 PLF APPLIED HORIZONTALLY AT THE |
| | REQUIRED GUARDRAIL HEIGHT WITH A |
| | SIMULTANEOUS LINE LOAD OF 100 PLF |
| | APPLIED VERTICALLY DOWNWARD ON THE TOP |
| | OF THE GUARDRAIL. THESE LOADS SHALL NOT |
| | BE APPLIED SIMULTANEOUSLY (UNLESS NOTED |
| | ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY |
| | TO PRODUCE MAXIMUM STRESS IN EACH OF |
| | THE |
| | COMPONENTS OR SUPPORTS. |
| | AMEND/ANNOTATE THE PLANS TO SPECIFY |
| | THESE LOADS. IT IS NOTED THAT THE |
| | ARCHITECTURAL PLANS REFER TO THE |
| | STRUCTURAL PLANS AND VICE VERSA, BUT |
| | NEITHER PLAN PROVIDES DETAILS. |
| | |
| | 8) FBC 11-4.24SHEET A-1, THE BREAKROOM |
| | SINK SHALL COMPLY WITH ALL OF THE |
| | ACCESSIBILTY REQUIREMENTS FOR RIM |
| | HEIGHT, KNEE CLEARANCE, BOWL DEPTH, |
| | CLEAR FLOOR SPACE, HOT WATER PIPE |
| | ISOLATION AND FAUCETS.AMEND THE PLANS |
| | TO DEMONSTRATE COMPLIANCE. |
| | |
| | 9) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |