Plan Review Notes
Plan Review Notes For Permit 04110867
Permit Number 04110867
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-21 00:00:00DENIED
  
 INCOMPLETE INFORMATION PROVIDED FOR A
 COMPLETE REVIEW.
 1.SHOW ON PLANS EXISTING FLOOR PLAN
 AND NEW WORK.SHOW FRAMING DETAILS AND
 STRAPS USED IF APPLICABLE
  
 2.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR WINDOWS AND IMPACT
 PROTECTION.ARE YOU INSTALLING ANY
 EXT.
 DOORS?
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLLOWING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SHOW SIZE AND TYPE OF BEDROOM
 WINDOWS ALONG WITH SILL HEIGHT. FBC
 1005.4
  
 4.APPLICATION IS NOT NOTORIZED AND
 NEEDS VALUE ON APPLICATION.
  
 5.SHOW FINISH FLOOR HEIGHT ABOVE
 GRADE.FBC WEST PALM BEACH AMMENDMENT
 1804.1.7
  
 6.VALUATION IS TO LOW BASED ON WORK
 SHOWN.
  
  
 7. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672