| Plan Review Notes For Permit 04110843 |
| Permit Number |
04110843 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-01-20 00:00:00 | ******** UNSAT *********** | | | | | | ** PLEASE SEE NOTES LISTED BELOW AS WELL | | | AS NOTES LISTED UNDER MAIN HOUSE PERMIT | | | # 02101307 | | | | | | | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, | | | MISSING EQUIPMENT GROUNDING CONDUCTOR | | | FROM MAIN HOUSE TO THE DETACHED GARAGE. | | | PER 250.32 | | | PLEASE SHOW THE GROUNDING ELECTRODE | | | SYSTEM AT THIS DETACHED GARAGE. PLEASE | | | SEE FBC 104.2.1, WHEREAS THE CODE SHALL | | | NOT BE REFERENCED IN LEIU IF TECHNICAL | | | REQUIREMENTS OR SPECIFIC DETAIL. | | | PLEASE SEE PANEL FOR GARAGE SHOWS MAIN | | | PER 225.32, HOWEVER THE MAIN DISCONNECT | | | AT THE DETACHED BLDG OS REQUIRED PER | | | 225.31. | | | | | | PLEASE SEE HOUSE PERMIT FOR REMAINDER OF | | | RISER DIAGRAM NOTES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|