2004-11-22 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND SPEC SHEET SUBMITTED
 FOR NEW HEAT PUMP.
 ONE SHOWS 3.8, THE OTHER 5.6.
 PLEASE ALSO SEE ALL CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125%.(HEAT-PUMP)
 215.3,230.42 ETC
  
 2)NOTE: PLEASE SEE ELECTRICAL WIRING
 DIAGRAM FOR POOL. SHOWS 3/0'S ? IS THIS
 FOR FEED TO NEW POOL PANEL?
 PLEASE INDICATE OCP FOR NEW PANEL, SIZE
 OF NEW PANEL AND ALL CONDUCTORS FOR NEW
 PANEL.
 215.5
  
 3)NOTE: PLEASE CORRELATE WIRING DIAGRMA
 WITH ALL NEW ELECTRICAL/POOL EQUIPMENT
 TO BE HOOK-UP.
  
 4)NOTE: PLEASE SEE ENGINEER MUST ALSO
 DATE PLANS WHEN SIGNING. MAY NOT BE
 STAMPED OR PRINTED.MUST BE ORIG WHEN
 SIGNED.
 FS471.025
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  