| Plan Review Notes For Permit 04110813 |
| Permit Number |
04110813 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-22 00:00:00 | ********** UNSAT ************ | | | | | | 1)NOTE: PLEASE CORRELATE LOAD | | | CALCULATIONS AND SPEC SHEET SUBMITTED | | | FOR NEW HEAT PUMP. | | | ONE SHOWS 3.8, THE OTHER 5.6. | | | PLEASE ALSO SEE ALL CONTINUOUS LOADS ARE | | | TO BE SHOWN AT 125%.(HEAT-PUMP) | | | 215.3,230.42 ETC | | | | | | 2)NOTE: PLEASE SEE ELECTRICAL WIRING | | | DIAGRAM FOR POOL. SHOWS 3/0'S ? IS THIS | | | FOR FEED TO NEW POOL PANEL? | | | PLEASE INDICATE OCP FOR NEW PANEL, SIZE | | | OF NEW PANEL AND ALL CONDUCTORS FOR NEW | | | PANEL. | | | 215.5 | | | | | | 3)NOTE: PLEASE CORRELATE WIRING DIAGRMA | | | WITH ALL NEW ELECTRICAL/POOL EQUIPMENT | | | TO BE HOOK-UP. | | | | | | 4)NOTE: PLEASE SEE ENGINEER MUST ALSO | | | DATE PLANS WHEN SIGNING. MAY NOT BE | | | STAMPED OR PRINTED.MUST BE ORIG WHEN | | | SIGNED. | | | FS471.025 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|